Mechanical Specifications - LG MULTI V WATER 5 ARW Series Engineering Manual

Table of Contents

Advertisement

General
An LG Multi V Water 5 variable refrigerant flow (VRF) Water Source Unit (WSU) operates
as either a heat pump or a heat recovery system. The WSU consists of a single, dual or triple
frame system connected to indoor units (IDU) (and heat recovery units for heat recovery
systems) with a single refrigerant piping system connected using factory designed and supplied
Y-branches and headers, and having integrated controls. The WSU has integrated controls and
can be operated with its control system or with a building management system.
A Multi V Water 5 heat pump and heat recovery system is a VRF system that can operate in
either heat pump mode (cooling or heating) or heat recovery mode (with indoor units in cooling
or heating modes simultaneously).
The heat recovery unit is capable of being designed for minimum piping and maximum design
flexibility. Individual indoor units or zones can change modes (cooling to heating or heating
to cooling) within a maximum time of three (3) minutes to ensure indoor temperature can be
properly maintained.
HRUs allow minimum piping and maximum design flexibility. Every indoor unit or zone of a
heat recovery system is independently capable of operating in either heating or cooling mode
regardless of the mode of other indoor units. The system ensures properly maintained indoor
temperature by changing the mode of individual indoor units or zones (cooling to heating or
heating to cooling) within a maximum time of three (3) minutes.
LG components are manufactured in a facility meeting International Organization for Standard-
ization (ISO) 9001 and ISO 14001 standards. ISO 9001 defines quality management and ISO
14001 defines environmental management. The units are listed by Intertek Electrical Testing
Laboratories (ETL) and bear the CSA Group (CSA) label. Wiring in these units are in
accordance with the National Electrical Code (NEC).
Temperature Ranges
Heat pump or heat recovery systems
Water Source Units can operate in cooling, heating, or synchronous mode with entering water temperatures (EWT) of 50°F to 113°F.
Casing / Frame
Water Source Units are constructed with galvanized steel, bonderized and finished with powder coat baked enamel paint. Each frame has a
removable inspection panel to allow access to service tool connection, DIP switches, auto addressing, and error code display without
removing the entire front panel. The entire front panel of the WSU is removable for maintenance.
WSU frames are completely factory assembled, piped and wired. Dual and triple frame WSUs must be field piped with factory designed and
supplied Y-branch kits to manifold them together into a single refrigerant circuit.
Refrigerant System
The refrigeration system is a single refrigeration circuit using R410A refrigerant. The WSU is provided with factory-installed components
including refrigerant sensors, check valves, oil separator, accumulator, hot gas bypass valve, four-way reversing valve, electronic controlled
expansion valve (EEV), high and low side charging ports, high pressure safety switch, service valves, and interconnecting piping. Also
included is an integral subcooler assembly consisting of a double spiral tube-type subcooling heat exchanger and EEV providing refrigerant
subcooling modulation up to 25ºF.

MECHANICAL SPECIFICATIONS

Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG " is a registered trademark of LG Corp.
Multi V Water 5 Water Source Units
Figure 2: Single Frame Multi V Water 5
Water Source Unit.
WSU PRODUCT DATA | 9