"WSRD" Interlocked Receptacles — 30, 60 & 100 Ampere
Read instructions carefully and with full
understanding for safe installation and
WSRD NEMA 4 Series:
Interlocked Appleton Powertite™ Compatible
Receptacle with heavy duty single throw dis-
connect switch.
ELECTRICAL RATINGS:
Maximum Voltage: 600VAC at 50-60 Hz*,
250 VDC 30, 60,100 Amperes — Continuous
Line Current not to exceed 80% of fuse rating
employed in other than motor circuits.
* For 400 Hz applications, consult factory.
Compliances:
• UL Listed
• UL50 for Enclosures
• UL1682 for Receptacles
• NEC wire bending space, Table 373-6(b)
• Federal Specifi cation WS865C
• Major automotive specifi cations
STANDARD FEATURES:
• Epoxy coated fi nish on receptacle and switch
housing.
• Factory installed fuse pullers for fusible
OPTIONS:
• Electrical Interlocks :
Except as expressly provided by Appleton
Electric LLC (Appleton) in writing, Appleton
products are intended for ultimate purchase
by industrial users and for operation by per-
sons trained and experienced in the use and
Maintenance of this equipment and not for
consumers or consumer use. Appleton
warranties do not extend to, and no reseller
is authorized to extend Appleton's warranties
to, any consumer.
EGS Electrical Group • 800-621-1506 • www.appletonelec.com
1 N.O. or 1 N.C.
2 N.O. or 2 N.C.
FIGURE A
Shown Above:
WSRD SERIES
Non-Fused Version Catalog Number WSRD63542N4WSD
TABLE A
HORSEPOWER RATING:
DC
Catalog Number
Volts
Sheet Metal Enclosure NEMA 12
WSRD3352SQ
250
WSRD33542SQ
250
WSRD3352WSQ
250
WSRD33542WSQ
250
WSRD6352SQ
250
WSRD63542SQ
250
WSRD6352WSQ
250
WSRD63542WSQ
250
WSRD10352SQ
250
WSRD10342SQ
250
WSRD10352WSQ
250
WSRD103542WSQ
250
Stainless Steel Enclosure NEMA 3, 3R, 4, 4X, 12
WSRD3352N4SD
250
WSRD33542N4SD
250
WSRD3352N4WSD
250
WSRD33542N4WSD
250
WSRD6352N4SD
250
WSRD63542N4SD
250
WSRD6352N4WSD
250
WSRD63542N4WSD
250
WSRD10352N4SD
250
WSRD10342N4SD
250
WSRD10352N4WSD
250
WSRD103542N4WSD
250
331114-1
INSTRUCTION SHEET
AC
Switch
HP Rating AC
Amp
Volts
Type
Stand.
600
30
Fused
7.5
600
30
Non-Fused
600
30
Fused
7.5
600
30
Non-Fused
600
60
Fused
600
60
Non-Fused
600
60
Fused
600
60
Non-Fused
600
100
Fused
600
100
Non-Fused
600
100
Fused
600
100
Non-Fused
600
30
Fused
7.5
600
30
Non-Fused
600
30
Fused
7.5
600
30
Non-Fused
600
60
Fused
600
60
Non-Fused
600
60
Fused
600
60
Non-Fused
600
100
Fused
600
100
Non-Fused
600
100
Fused
600
100
Non-Fused
Rev. B 08/12/08
Max
20
--
30
20
--
30
15
50
--
60
15
50
--
60
30
75
--
75
30
75
--
75
20
--
30
20
--
30
15
50
--
60
15
50
--
60
30
75
--
75
30
75
--
75
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Appleton WSRD Series and is the answer not in the manual?

Questions and answers

Summary of Contents for EGS Appleton WSRD Series

  • Page 1 Appleton WSRD63542N4WSD Non-Fused warranties do not extend to, and no reseller WSRD10352N4SD Fused WSRD10342N4SD Non-Fused is authorized to extend Appleton's warranties WSRD10352N4WSD Fused to, any consumer. WSRD103542N4WSD Non-Fused Rev. B 08/12/08 EGS Electrical Group • 800-621-1506 • www.appletonelec.com Page 1...
  • Page 2 DISCONTINUE USE IMMEDIATELY! This condition could cause serious or fatal personal injury due to electrocution and/or equipment damage. Repair with the proper replacement part(s) before continuing service. 331114-1 Rev. B 08/12/08 EGS Electrical Group • 800-621-1506 • www.appletonelec.com Page 2...
  • Page 3 • Failure to do so may result in over-stressed wire termina- tions which could cause the conductors to pull out of the disconnect switch lugs. This could cause serious or fatal injuries due to electrocution. 331114-1 Rev. B 08/12/08 Page 3 EGS Electrical Group • 800-621-1506 • www.appletonelec.com...
  • Page 4 (ASSEMBLY VIEW WITH COVER OPEN) Unit shown is Catalog Number WSRD6352SQ (NEMA 12 Version) Dimension in Inches Device Rating 30 & 60 Amp 16.75 16.50 22.25 100 Amp 20.75 20.50 26.25 331114-1 Rev. B 08/12/08 EGS Electrical Group • 800-621-1506 • www.appletonelec.com Page 4...
  • Page 5 ➃ the housing , since the range of travel (swing) of the cover is adequate to service the inside of the unit. 331114-1 Rev. B 08/12/08 Page 5 EGS Electrical Group • 800-621-1506 • www.appletonelec.com...
  • Page 6 • Torque the lug screw to the appropriate value shown in investigated and repaired as necessary. "TABLE C" and "TABLE F". 331114-1 Rev. B 08/12/08 EGS Electrical Group • 800-621-1506 • www.appletonelec.com Page 6...
  • Page 7 "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suit- ability of the product for his intended use and assume all risk and liability whatsoever in connection herewith. 331114-1 Rev. B 08/12/08 Page 7 EGS Electrical Group • 800-621-1506 • www.appletonelec.com...
  • Page 8 331114-1 Rev. B 08/12/08 EGS Electrical Group • 800-621-1506 • www.appletonelec.com Page 8...

This manual is also suitable for:

Appleton wsrd3352sqAppleton wsrd33542sqAppleton wsrd3352wsqAppleton wsrd33542wsqAppleton wsrd6352sqAppleton wsrd63542sq ... Show all

Table of Contents