7-3. Dip Switch Settings
Switch Pole
Function
Thermistor<Intake temperature
1
detection>position
2
Filter clogging detection
3
Filter life
4
Air intake
SW1
5
Remote indication switching
Mode
6
Humidifier control
Selection
7
Air flow
8
Heat thermostat OFF
9
Auto reset function
10
Power ON/OFF
MODELS
SW2
PVFY-
P12E00B
Capacity
1~6
code
PVFY-
setting
P18E00B
PVFY-
P24E00B
MODELS
SW3
Function
1~10
PVFY-P24, 30E00B
Selection
SW4
PVFY-P12~54E00B
Unit
ON
1~4
OFF
Selection
1 2 3 4 5
Note
:The DipSW setting is effective during unit stopping ( remote controller OFF ) for SW1,2,3 and 4 commonly and the
power source is not required to reset.
18
ON
Built-in remote controller
Provided
2,500hr
Effective
Thermostat ON signal indication Fan output indication
Always operated while the heat is ON
Low
Setting air flow
Effective
Effective
SW2
MODELS
SW2
PVFY-
ON
ON
OFF
OFF
P30E00B
1 2 3 4 5 6
1 2 3 4 5 6
PVFY-
ON
ON
OFF
OFF
P36E00B
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
SW3
PVFY-P12, 18, 36,
ON
OFF
48, 54E00B
1 2 3 4 5 6 7 8 9 10
<At delivery>
Operation by switch
OFF
Indoor unit
Not provided
100hr
Not effective
Operated depends on the condition
Extra low
Reset to SW1-7
Not effective
Not effective
MODELS
SW2
PVFY-
ON
OFF
P48E00B
1 2 3 4 5 6
ON
PVFY-
OFF
P54E00B
1 2 3 4 5 6
1 2 3 4 5 6
MODELS
SW3
ON
OFF
1 2 3 4 5 6 7 8 9 10
Remarks
Address board
<At delivery>
ON
OFF
1 2 3 4 5 6 7 8 9 10
Indoor controller board
Set while the unit is off.
<At delivery>
Set for each capacity.
Indoor controller board
Set while the unit is off.
Indoor controller board
Set while the unit is off.