➢ Battery connection diagram
➢ BMS PIN Definition
Communication interface between inverter and battery is RS485 or CAN with a RJ45 connector.
When using the RS485 protocol, please note that PIN2 must be disconnected!
➢ Power Connection Battery:
Step 1. Use the 2 AWG wire and strip the cable to 15mm. Select two O-terminals with an aperture of M8.
Insert the stripped line into the O-terminal and clamp it with a crimping clamp.
Step2. Cross the battery cable although the battery port. Connect battery cable to battery terminal.