Mechanical Specification
NOTE: All dimensions in mm
TECHNICAL SPECIFICATIONS
SUPPLY VOLTAGE
LOOP CURRENT - QUIESCENT
LOOP CURRENT -ALARM LOW. FREQ.
LOOP CURRENT -ALARM HIGH. FREQ.
LOOP CURRENT -ALARM BEACON
SOUNDER OUTPUT - CONTINUOUS
SOUNDER OUTPUT - LOW FREQ.
SOUNDER OUTPUT - HIGH FREQ.
MAX. CABLE SIZE
MAX. HUMIDITY
OPERATING TEMPERATURE
ENCLOSURE - MATERIAL
PROTECTION CATEGORY
DIMENSIONS
WEIGHT
ORDER CODE
VALKYRIE AS IP65
VALKYRIE ASB IP65
Global Fire Equipment S.A.
MARF - Armazens F3 e F4, Sítio do Guelhim, Estoi, 8009-021 FARO, PORTUGAL
Tel: + 351 289 896 560 Fax: + 351 289 865 587
Sales sales@globalfire.pt Technical Support techs@globalfire.pt
112
VALKYRIE A IP65
Loop: 17V to 30 V DC
0.5 mA
4.1 mA (Max.) - 2.6 mA (Min.)
7.5 mA (Max.) - 3 mA (Min.)
1.4 mA
102 dB @ 1 m (Max.) - 97 dB @ 1 m (Min.)
103 dB @ 1 m (Max.) - 98 dB @ 1 m (Min.)
110 dB @ 1 m (Max.) - 100 dB @ 1 m (Min.)
2.5 mm
95% RH Non-Condensing
0 ºC to 40 ºC
Red ABS
IP65
112 mm (W) x 110 mm (H)
315 g - 350 g including packaging
DESCRIPTION
Valkyrie Addressable Wall Sounder - IP65 Rated
Valkyrie Addressable Wall Sounder/ Beacon - IP65 Rated
VALKYRIE A IP65
Addressable Wall Sounder/ Beacon
Outdoor Use-IP65
The VALKYRIE A IP65 is a wall mounted
Addressable Sounder/ Beacon with low
power consumption. It is specifically
designed to be used outdoors. Up to 32
individually addressed sounders can
be installed per loop occupying
address 94 to 125. The address is set
using switches 1 to 5 of the 8 way DIL
switch. Four different tones are
available and selected using DIL
switches 6 and 7.
When individual address reporting is
not required, VALKYRIE A IP65 can be
configured as a Shadow Sounder. In
this case sounders do not occupy an
address in the loop thus freeing up
addresses for more detection devices.
Shadow sounders do not report back to
the control panel so their presence on
the loop is not monitored. Shadow
sounders draw current from the loop
(4.1mA in alarm) and must be included
in loop load calculations.
INSTRUCTION MANUAL V.07/2011
Features
•
Outdoor Use - IP65
•
Complies with EN54-3
•
Low current consumption
4.1 mA for combined Sounder/Beacon
•
110 dB maximum sounder output at 1 m
•
Synchronization for fast activation
•
Compatible with all GFE addressable panels
Need help?
Do you have a question about the VALKYRIE A IP65 and is the answer not in the manual?
Questions and answers