Addressable Wall Sounder/Beacon Outdoor Use-IP65
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt
SUPPLY VOLTAGE
LOOP CURRENT - QUIESCENT
LOOP CURRENT - SOUNDER/BEACON ACTIVE
MAXIMUM S
OUNDER OUTPUT
RESET/START-UP TIMES
PROTECTION CATEGORY
COLOUR / CASE MATERIAL
OPER. TEMPERATURE / MAX. HUMIDITY
DIMENSIONS
WEIGHT
ORDER CODE
VALKYRIE AS IP65
VALKYRIE ASB IP65
VALKYRIE ASI IP65
VALKYRIE ASBI IP65
NOTE: Address programmed on switches 1-5 has an OFFSET of 94.
For example if D.I.L. switches 1-5 are all set to OFF the actual
GLOBAL FIRE EQUIPMENT S.A.
TECHNICAL SPECIFICATIONS
Loop Powered - 20 V to 30 V DC
550 uA max. with isolator
10 mA - 280 mW @ 28 V DC inc. isolator
108 dB (@ 1 meter - 30 V DC)
20 seconds max.
Type B - Outdoor Use / Rating IP65
Red / ABS & PC -
-25 C to 70 C / 95% RH Non-Condensing
112 (D) x 110 (H) mm inc. base
315 g inc. base & 350 g inc. packaging
| CERTIFICATE |
DESCRIPTION
1328-CPR-0299
ADDRESSABLE WALL SOUNDER - IP65 RATED
1328-CPR-0299
ADDRESSABLE WALL SOUNDER/BEACON - IP65 RATED
1328-CPR-0299
ADDRESSABLE WALL SOUNDER - IP65 RATED W/ LOOP ISOLATOR
1328-CPR-0299
ADDRESSABLE WALL SOUNDER/BEACON - IP65 RATED W/ LOOP ISOLATOR
SOUNDER BASE - LOOP CONNECTIONS
Please note that this device is polarised.
LOOP IN
sounder address, as read by the panel, will be 94.
Flame Retardant rating 94V0
o
o
MANUAL - 02/2018
MADE IN PORTUGAL - EU
LOOP OUT
To next device
in loop or return
to panel

Advertisement

loading
Need help?

Need help?

Do you have a question about the VALKYRIE AS IP65 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Global Fire Equipment VALKYRIE AS IP65

  • Page 1 MANUAL - 02/2018 Valkyrie AS IP65 MADE IN PORTUGAL - EU Addressable Wall Sounder/Beacon Outdoor Use-IP65 GLOBAL FIRE EQUIPMENT S.A. Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt...
  • Page 2 MECHANICAL SPECIFICATION 112 mm D.I.L. SWITCHES CONFIGURATION Switches 1-5 Address Switches Sounder Type ON (1) used to configure address 1 ON = 1 Switch No. 8 OFF (0) in the range 94-125 2 ON = 2 OFF = Shadow 3 ON = 4 ON = Normal Switch 6 and 7 Tone Selection...

This manual is also suitable for:

Valkyrie asb ip65Valkyrie asi ip65Valkyrie asbi ip65