Valkyrie AS IP65
Addressable Wall Sounder/Beacon Outdoor Use-IP65
Sítio dos Barrabés, Armazém Nave Y, Caixa Postal 908-Z, 8150-016 São Brás de Alportel - PORTUGAL
Tel: +351 289 896 560 • Sales: sales@globalfire.pt • Technical Support: techs@globalfire.pt • www.globalfire.pt
SUPPLY VOLTAGE
LOOP CURRENT - QUIESCENT
LOOP CURRENT - SOUNDER/BEACON ACTIVE
MAXIMUM S
OUNDER OUTPUT
RESET/START-UP TIMES
PROTECTION CATEGORY
COLOUR / CASE MATERIAL
OPER. TEMPERATURE / MAX. HUMIDITY
DIMENSIONS
WEIGHT
ORDER CODE
VALKYRIE AS IP65
VALKYRIE ASB IP65
VALKYRIE ASI IP65
VALKYRIE ASBI IP65
NOTE: Address programmed on switches 1-5 has an OFFSET of 94.
For example if D.I.L. switches 1-5 are all set to OFF the actual
GLOBAL FIRE EQUIPMENT S.A.
TECHNICAL SPECIFICATIONS
Loop Powered - 20 V to 30 V DC
550 uA max. with isolator
10 mA - 280 mW @ 28 V DC inc. isolator
108 dB (@ 1 meter - 30 V DC)
20 seconds max.
Type B - Outdoor Use / Rating IP65
Red / ABS & PC -
-25 C to 70 C / 95% RH Non-Condensing
112 (D) x 110 (H) mm inc. base
315 g inc. base & 350 g inc. packaging
| CERTIFICATE |
DESCRIPTION
1328-CPR-0299
ADDRESSABLE WALL SOUNDER - IP65 RATED
1328-CPR-0299
ADDRESSABLE WALL SOUNDER/BEACON - IP65 RATED
1328-CPR-0299
ADDRESSABLE WALL SOUNDER - IP65 RATED W/ LOOP ISOLATOR
1328-CPR-0299
ADDRESSABLE WALL SOUNDER/BEACON - IP65 RATED W/ LOOP ISOLATOR
SOUNDER BASE - LOOP CONNECTIONS
Please note that this device is polarised.
LOOP IN
sounder address, as read by the panel, will be 94.
Flame Retardant rating 94V0
o
o
MANUAL - 02/2018
MADE IN PORTUGAL - EU
LOOP OUT
To next device
in loop or return
to panel
Need help?
Do you have a question about the VALKYRIE AS IP65 and is the answer not in the manual?