ACS contsys Sonicont USN020 Manual

Ultrasonic filling level transmitter

Advertisement

Quick Links

Sonicont USN020
Ultrasonic filling level transmitter
Non-contact measurement of filling levels
in liquids, pastes and coarse bulk materials
Technical manual
11.12
Main features
Non-contact filling level measurement
in liquids up to 2m
in bulk materials up to 1m
Process temperature range from – 40 °C to +85 °C
Accuracy ≤ 0,2%
Integrated evaluation electronic
3-wire with current signal 0/4...20 mA
3-wire with voltage signal 0...10 V
4x PNP switch output
Bluetooth-Interface
Enclosure and display rotatable for optimal operability in
each installation position
Viewing angle optimized TFT-LCD display for best
readability
Easy handling by clear menu navigation
Extensive diagnostic functions for system analysis
Measure data memory for up to 1 million measuring values

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Sonicont USN020 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ACS contsys Sonicont USN020

  • Page 1 Sonicont USN020 Ultrasonic filling level transmitter Non-contact measurement of filling levels in liquids, pastes and coarse bulk materials Technical manual 11.12 Main features Non-contact filling level measurement in liquids up to 2m • in bulk materials up to 1m •...
  • Page 2 You have purchased a high-grade and modern measuring device of ACS-CONTROL-SYSTEM GmbH. We want to give thanks for your purchase and for your confidence to us. The actual technical manual includes instructions for installation, electrical connection and inauguration, as well as the technical data of the device. Modifications, that answer the purpose of the technical progress, are reserved by ACS-CONTROL-SYSTEM GmbH without prior notice.
  • Page 3 Index Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Function .
  • Page 4 Application The device is a non-contact electronic ultrasonic filling level transmitter for continuous measuring of filling levels in liquids, pastes and coarse bulk materials. The use of a non-contact operating measuring systems opens a broad range of application possibilities like e.g. at aggressive process materials. Function The transducer of the ultrasonic sensor transmits ultrasonic pulses to the product surface.
  • Page 5: Safety Notes

    Safety notes Each person that is engaged with inauguration and operation of this device, must have read and understood this technical manual and especially the safety notes. Installation, electrical connection, inauguration and operation of the device must be made by a qualified employee according to the informations in this technical manual and the relevant standards and rules.
  • Page 6: Installation Notes

    Installation The correct function of the device within the specific technical data can only be guaranteed, if the permitted process and environmental temperatures (see chapter „Technical data“) will not be exceeded. Installation notes Drive the system pressure free prior installation resp. deinstallation of the sensor. The screw-in of the thread process connection by using the terminal housing, the connection plug resp.
  • Page 7: Nozzle Installation

    Nozzle installation Use a pipe nozzle if you cannot maintain the blocking distance in any other way. The interior of the nozzle must be smooth and may not contain any edges or welded joints. In particular, there should be no burr on the inside of the tank side nozzle end. Note the specified limits for nozzle diameter and length.
  • Page 8: Installation Place

    Installation place Level measurement Do not install the sensor in the middle of the tank (C). We recommend leaving a distance • between the sensor and the tank wall (A) measuring 1/6 of the tank diameter. In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.
  • Page 9 Installation in narrow shafts In narrow shafts with strong interference echoes, we recommend using a stand pipe resp. an ultrasound guide pipe (e.g. PE or PVC wastewater pipe) with a minimum diameter of 100 mm. Make sure that the pipe is not soiled by accumulated dirt. If necessary, clean the pipe at regular intervals.
  • Page 10: Electrical Connection

    Electrical connection The electrical connection of the device must be carried out according to the respective country specific standards. Incorrect installation or adjustment could cause applicationally conditioned risks. Potential equalization - earthing The device must be grounded. The metallic parts of the device are electrically connected with the socket of the plug M12. Connection cable Use only shielded signal and measurement wires and install these wires separated from power leading wires.
  • Page 11: Switch Output

    Signal 0…10 V A load resistor, e.g. the measuring shunt of an evaluation device, requires at a definitive output voltage an output current. Due to the limitation of that output current, it results in a minimum value for this resistor, where a correct function is still possible. This resistor can be calculated by the following term: / 3mA Lmin...
  • Page 12: Connection Scheme

    Connection scheme Signal 0/4…20 mA / 0…10 V Conductor color standard connection cable M12: BN = brown, WH = white, BU = blue The connection cable in not enclosed in the delivery contents. Signal 0/4…20 mA / 0…10 V / 2x PNP switch output Conductor color standard connection cable M12: BN = brown, WH = white, BU = blue, BK = black, GY = grey The connection cable in not enclosed in the delivery contents.
  • Page 13: Operation And Display Parts

    Operation Operation and display parts A – LCD display • Display of measuring value, device state and operation menu B - Key Down In the selection menu navigation downwards • In the set menu decreasing of value • Used, in combination with the key up, for leaving selection and set menu without applying •...
  • Page 14: Function Scheme

    Function scheme A - Commissioning B - Vessel type C - Noise filter D - Pulse rate E - Limit min/max F - Echo loss G - Damping H - Min/Max Adjustment > e.g. 1,8..0,4 m = 0..100 % I1 - Linearization > Level - display scaling e.g. 0,4..1,8 m = 0..2000 m I2 - Linearization >...
  • Page 15: Menu Structure

    Menu structure The entrance to the different function areas of the selection and set menu layer is done by the main menu (push the key Enter/Shift right for 3 seconds). If failures are registered (see chapter diagnose/failure), these are indicated prior the jump into the main menu.
  • Page 16 Output The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure. Switch output S1 / S2 / S3 / S4 Enabled Each switch output can be activated resp.
  • Page 17 Switch Delay Time / Reset Switch Delay Time – extended menu structure The activation resp. deactivation of the switch output can be biased with a delay time (resolution 0,01s), to realize simple sequence control system. The input range is indefinite. Default >...
  • Page 18: Operating Mode

    Error Indication Function The switch output is activated, if the device has detected a failure behavior (see chapter diagnose/ failures). Default > Hysteresis Function Operating Mode The operating mode defines the function direction of the switch output. • Normal Open / NO At the output there is no signal, if the switch condition is not fulfilled.
  • Page 19: Error Signal

    Error Signal Defines, dependent on the operating mode, the analogue output signal regarding operating range and if errors (see chapter diagnose/failures) are registered. Operating mode 4-20mA • A - Off >> 3.9-21mA B - 3.6mA C - 22mA Operating mode 0-20mA •...
  • Page 20: Basic Setting

    Invert Signal Inverts, dependent on the operating mode, the analogue output signal. 4-20 mA >> 20-4 mA • 0-20 mA >> 20-0 mA • 0-10 V >> 10-0 V • Default > No Basic Setting The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure.
  • Page 21 Min/Max-Adjustment The min/max-adjustment set the measuring range limits. 2 points are defined, that set the ratio of the measured sistance signal and the operating range of the device. The current measuring value is indicated in the display. The input of the measuring range limits 0% and 100% are not mandatory. Values within the measuring range e.g.
  • Page 22 Limit min/max – extended menu structure If the measuring value exceeds the limits of the Min/Max-Adjustment, these limits are kept at activated function. An exceedance is not possible. At deactive function measurement values besides the limit values are output. This function is especially useful at a flow measurement to avoid negative flow measuring values. deactive •...
  • Page 23 Damping – extended menu structure The damping influences the reaction speed of display, output signal and switch output at a change of the measuring signal. The behavior of display and output signal follows an exponential characteristic with the damping time constant t.
  • Page 24: Sensor Tag

    Predefined linearization curves Linear - no linearization • Volume linearization Horizontal cylindrical vessel • • Spherical vessel Flow linearization • Venturi, trapezodial weir, rectangle weir Palmer-Bowlus-Flume • V-Notch, triangle weir • Free linearization characteristic with up to 40 points Custom •...
  • Page 25: Factory Reset

    Factory Reset The factory reset changes all settings to default values. The factory reset does not concern: Diagnose data • Historical measuring data • Storage interval • Custom defined linearization • Display The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure.
  • Page 26 Unit – extended menu structure This menu item is only available at indicator value scaled If a scaled indicator value is used, additionally an unit can be selected, that is indicated in the display (not at indicator type vertical bargraph). The unit is only indicated as text and is not included into calculations.
  • Page 27 Indicator Type Dependent on the requirements the measuring values can be indicated in different types. • Digital Switch points, active or deactive Sensor TAG Digital measuring value Unit Horizontal scaled bargraph Mark of switch points at the bargraph • Manometer Round pointer scale Mark of the switch points at the pointer scale Unit...
  • Page 28 Vertical Bargraph • Vertical percentual scaled bargraph Chart • Scaled graphical measuring value-to-time-window Selected historical digital measuring value with unit und time distance in days/hours/minutes/ seconds Digital measuring value with unit Navigation of a measuring value cursor with cursor keys within the graphic window. By simultaneous pushing the keys Up and Down (minimum 3 seconds) the point of time in days/ hours/minutes/seconds can be input, where the cursor should be positioned.
  • Page 29: Password Protection

    Language The menu navigation can be done in the following different languages. Deutsch • English • Default > Deutsch Password Protection For the protection of the settings against unauthorized persons individual or all main menu items can be protected by a password. At each activation of the main menu the password protection is active.
  • Page 30 View – extended menu structure For the adaption of the display to the requirements of the installation situation the view of the display can be rotated by 180°. In combination with the mechanical rotatability of app. 330° a readability from all directions in all installation positions is possible. Normal •...
  • Page 31: Envelope Curve

    Diagnose Envelope curve The current measuring signal is displayed as curve. The envelope curve is displayed, below those the measuring signal is ignored. The valid measuring signal is marked by a vertical mark. Downright the characteristic curve the current distance value is displayed with unit m and the corresponding measured signal level in dB.
  • Page 32 Failure The device registrates multiple of short time or also continuous existing functional failures in type and frequency of occurrence. Echo lost - No measurable echo signal available • Over Range - exceeding the signal output range (dependent on Operating Mode) •...
  • Page 33 Data The device is able to record app. one million measuring values loss-protected. The recording is made in ring memory method, whereas after an overflow the oldest measuring values are overwritten next. The stored measuring values can be displayed graphically in the indicator type chart or exported as CSV-file per Bluetooth-interface.
  • Page 34 Send/receive settings The current settings can be transmitted to or received from a Bluetooth end device as a configuration file. Configurations can be also sent directly from device to device. At the transmission of settings some parameter are not transmitted. Sensor TAG •...
  • Page 35 For a protected resp. encoded data transmission a PIN must be input. The input range is limited to values from 000000 to 999999. Default > no PIN allocated Visibility To transmit a file to the device, it must be visible in the Bluetooth network. Other end devices can identify only visible devices.
  • Page 36: Start-Up Procedure

    Start-up procedure Level measurement The filling level is calculated by the device due to the distance of the filling material surface to the sensor. Sub menu Basic Setting Commissioning • Min/Max Adjustment • Sub menu Display Indicator value fill level •...
  • Page 37: Volume Measurement

    Volume measurement For the indication of the tank volume a display scaling can be made. If a nonlinear tank style is used, a linearization must be set. Predefined linearization curves for some tank styles are available. Sub menu Basic Setting Commissioning •...
  • Page 38: Flow Measurement

    Flow measurement For the indication of the flow amount a display scaling can be made. If a nonlinear flow opening style is used, a linearization must be set. Predefined linearization curves for some flow opening styles are available. Sub menu Basic Setting Commissioning •...
  • Page 39: Maintenance

    Maintenance The device is free of maintenance. Special substances can lead to solid coatings on the membrane. Seized depositions can lead to faulty measurement results. In the case of coat forming liquids the membrane must be regularly cleaned e.g. with clear water. Don’t use sharp tools or aggressive chemicals for cleaning.
  • Page 40: Technical Data

    Technical Data Auxiliary power supply Supply voltage U Preference output 0/4...20 mA 9..30 V , reverse polarity protected Preference output 0…10 V 14..30 V , reverse polarity protected Residual ripple U ≤ 2 V ≤ U ≤ U Smin Smax Supply current I Preference output 0/4...20 mA ≤...
  • Page 41: Measuring Accuracy

    Input Measuring range Liquids up to 2m Bulk materials up to 1m Blocking distance BD ≤ 0,15m (typ. 0,06m) Operating frequency 125kHz Emitting angle α 10° ±2° at -3 dB Detection radius r = 0,044m (L = 0,5m / α = 10°) = 0,087m (L = 1,0m / α...
  • Page 42: Environmental Conditions

    Environmental conditions The permitted environmental temperature range results from the combination of standard range and expansion, whereby the range is defined by the narrowest limitation. Environmental temperature -20°C...+50°C Expansion Backlight LCD ≤ 80% >> -20°C...+60°C Backlight LCD ≤ 60% -20°C...+70°C >>...
  • Page 43: Dimension Drawings

    Dimension drawings Terminal enclosure Process connection Type G10 - G 1” ISO 228-1 ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
  • Page 44: Order Code

    Order Code Type USN020 Standard Process connection G10 G 1“, ISO 228-1 Electronic - output 3-wire, signal 0/4…20mA - 0…10V 3-wire, signal 0/4…20mA - 0…10V, 2x PNP 3-wire, signal 0/4…20mA - 0…10V, 4x PNP Electronic - function without Bluetooth-Interface others Material process connection (process wetted) PVDF / Steel 1.4404/316L or 1.4571/316Ti...

Table of Contents