Hydrocont SN50 Hydrostatic filling level transmitter Measurement of filling levels in liquids Technical manual 10.14 Main features Finely graded filling level measuring • Measuring ranges from -1 to 20 bar Measuring spans from 0,05 to 20 bar • Ceramic membrane for various applications...
Page 2
You have purchased a high-grade and modern measuring device of ACS-CONTROL-SYSTEM GmbH. We want to give thanks for your purchase and for your confidence to us. The actual technical manual includes instructions for installation, electrical connection and inauguration, as well as the technical data of the device. Modifications, that answer the purpose of the technical progress, are reserved by ACS-CONTROL-SYSTEM GmbH without prior notice.
Application The device is an electronic hydrostatic filling level transmitter for continuous measuring of filling levels in liquids within pressure-less container. The use of a capacitive measuring sensor with ceramic membrane and the corresponding excellent characteristics, allows the use in nearly all fields of industry. Optionally the device can be equipped with a process diaphragm seal.
Signal processing The pressure signal, that is transmitted by the membrane to the sensor is converted into an electrical signal and processed by the integrated evaluation electronic according to the respective preferences. The measuring value is diagrammed at the display, whereby it can be selected between different display styles (digital value / manometer / chart / bar graph).
Installation The correct function of the device within the specific technical data can only be guaranteed, if the permitted process and environmental temperatures (see chapter „Technical data“) will not be exceeded. Installation place The installation of the device at locations where high pressure blows can occur should be avoided. At a filling level measurement in liquids, the device should be installed below the lowest measuring point.
Page 7
Process diaphragm seal A process diaphragm seal together with the measuring transmitter forms a closed, calibrated system, that is filled by openings in the process diaphragm seal and in the measuring system of the measuring transmitter. These openings are sealed and may not be opened. The standard reference temperature for pressure diaphragm seal systems is +20°C.
Electrical connection The electrical connection of the device must be carried out according to the respective country specific standards. Incorrect installation or adjustment could cause applicationally conditioned risks. Potential equalization - earthing The device must be grounded. The earthing can be carried out by the metallic process connection. The metallic parts of the device are electrically connected with the socket of the plug M12.
Load resistor Signal 0/4…20 mA A load resistor, e.g. the measuring shunt of an evaluation device, requires a minimum supply voltage. Dependent on the connected supply voltage, it results in a maximum value for this resistor, where a correct function is still possible. This resistor can be calculated by the following term: = (U - 7 V) / 20mA...
Connection scheme Signal 0/4…20 mA / 0…10 V Conductor color standard connection cable M12: BN = brown, WH = white, BU = blue The connection cable in not enclosed in the delivery contents. Signal 0/4…20 mA / 0…10 V / 2x PNP switch output Conductor color standard connection cable M12: BN = brown, WH = white, BU = blue, BK = black, GY = grey The connection cable in not enclosed in the delivery contents.
Operation Operation and display parts A – LCD display • Display of measuring value, device state and operation menu B - Key Down • In the selection menu navigation downwards In the set menu decreasing of value • Used, in combination with the key up, for leaving selection and set menu without applying •...
Function scheme A - Damping B - Position adjustment C1 - Primary unit > e.g. bar C2 - Primary unit > m D1 - Density > not available (at primary unit bar/mbar) D2 - Density > e.g. 1,0194 kg/dm E - Offset adjustment > e.g. no offset F1 - Min/Max adjustment >...
Page 13
G1 - Linearization > primary unit - display scaling e.g. 0..0,7 bar resp. 1..9 m = 0..2000 m G2 - Linearization > percent 0..100 % - lin. percent 0..100 % G3 - No linearization J - Signal output > e.g. 0..100 % = 4..20 mA resp. 0..20 mA resp. 0..10V K - Error signal evaluation L1 - Switch / reset switch point S1 L2 - Switch / reset switch point S2...
Menu structure The entrance to the different function areas of the selection and set menu layer is done by the main menu (push the key Enter/Shift right for 3 seconds). If failures are registered (see chapter diagnose/failure), these are indicated prior the jump into the main menu.
Page 15
Navigation The navigation in a submenu and in a selection window is done by the keys Up and Down. The selection of a submenu and the selection of a setting in a selection menu is done by the key Enter/Shift right. The jump backward from a submenu to the higher-level menu is done by the menu item back or by the simultaneous pushing the keys Up and Down.
Page 16
Output The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure. ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 17
Switch output S1 / S2 / S3 / S4 Enabled Each switch output can be activated resp. deactivated separately. • • Default > Yes Switch Point / Reset Switch Point The input values refers to the set display value, in the set primary unit or acc. to display scaling. The current measuring value is indicated on the display.
Page 18
Window function The window function realizes a signal range – acceptance region –, where the switch output is set to a definitive switch state. The switch range is determined by definition of switch point and reset switch point. The switch output is activated, if the current measuring value is inside the area that is defined by the switch point and the reset switch point and if the set switch point delay time has been expired.
Page 19
Error Signal Defines, dependent on the operating mode, the analogue output signal regarding operating range and if errors (see chapter diagnose/failures) are registered. Operating mode 4-20mA • A - Off >> 3.8-20.5mA B - 3.6mA C - 22mA Operating mode 0-20mA •...
Page 20
Invert Signal Inverts, dependent on the operating mode, the analogue output signal. 4-20 mA >> 20-4 mA • 0-20 mA >> 20-0 mA • 0-10 V >> 10-0 V • Default > No ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Basic Setting The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure. Operating Mode Definition for the use of the device for pressure or level measurement. The change of the setting erases an eventual min/max-adjustment.
Page 22
Primary Unit The primary unit defines the internal reference unit of the measuring signal. At the change of the primary unit an automatic conversion is calculated. At the change of the primary unit from a pressure unit to a height unit the gravitational acceleration mean value 9,81 m/s2 is used.
Page 23
Damping The damping influences the reaction speed of display, output signal and switch output at a change of the measuring signal. The behavior of display and output signal follows an exponential characteristic with the damping time constant t. Within the time period t the output signal increases respectively by 63% of the existing deviation. With 99,3%, the end value is nearly achieved after 5 t.
Position Adjustment – extended menu structure By the use of the position adjustment measuring errors caused by the installation position can be corrected. This errors can be caused e.g. by the dead weight of the measuring membrane, by the filling fluid of a process diaphragm seal or by a higher process temperature.
Page 25
Linearization – extended menu structure Due to the integrated linearization function it is possible, to linearize a measuring signal e.g. for volume calculation of conical or horizontal cylindrical vessels or also for flow calculation. A - Tank with linearization points 1 / 2 / 3 / 4 B - Characteristic pressure - level not linearized C - Characteristic pressure - level linearized Predefined linearization curves...
Page 26
Input mode custom defined linearization Percent / Linearized Percent • Base Unit / Display Scaling • CSV-file via Bluetooth-interface • The percentual input (referring to the measuring range) is only possible without applying measuring value - dry adjustment -, whereby the input in primary unit e.g. bar and display scaling e.g. liter can be done without applying measuring signal - dry adjustment - as well as with applying measuring signal –...
Page 27
Display The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure. Indicator value – extended menu structure The measuring value can be alternatively displayed in the set primary unit e.g. bar or meter, or with any desired scaling referring percentual to the measuring range.
Page 28
Scaling – extended menu structure This menu item is only available at indicator value scaled. By defining a scaling the measuring range can be rescaled into any desired numerical range. This allows e.g. the indication of the volume in liter. The current measuring value is indicated in the display.
Page 29
Indicator Type Dependent on the requirements the measuring values can be indicated in different types. Digital • Switch points, active or deactive Sensor TAG Digital measuring value Unit Horizontal scaled bargraph Mark of switch points at the bargraph • Manometer Round pointer scale Mark of the switch points at the pointer scale Unit...
Page 30
Vertical Bargraph • Vertical percentual scaled bargraph Chart • Scaled graphical measuring value-to-time-window Selected historical digital measuring value with unit and time distance in days/hrs/mins/secs Digital measuring value with unit Navigation of a measuring value cursor with cursor keys within the graphic window By simultaneous pushing the keys Up and Down (minimum 3 seconds) the point of time in days/hrs/mins/secs can be input, where the cursor should be positioned After 5 minutes of inactivity the measuring value cursor is automatically set to 0s.
Password Protection For the protection of the settings against unauthorized persons individual or all main menu items can be protected by a password. At each activation of the main menu the password protection is active. An unknown or forgotten password can be erased by use of a service code and an activation code. These codes can be requested at the manufacturer.
Page 32
Simulation – extended menu structure The symbol E at a menu item indicates its position in the extended menu structure. This extended menu structure can be shown in the submenu display by the menu item menu structure. Output Switch Output The switch output is activated resp.
Page 33
Diagnose Operation Cycles The number of operation cycles per switch output is indicated. An operation cycle is a complete change of the switch state till back to the start state, thus deactive - active - deactive. ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 34
Failure The device registrates multiple of short time or also continuous existing functional failures in type and frequency of occurrence. Overpressure - exceeding the nominal measuring range by 3% • Underpressure - exceeding the nominal measuring range by 3% • Over Range - exceeding the signal output range (dependent on Operating Mode) •...
Page 35
Data The device is able to record app. one million measuring values loss-protected. The recording is made in ring memory method, whereas after an overflow the oldest measuring values are overwritten next. The stored measuring values can be displayed graphically in the indicator type chart or exported as CSV-file per Bluetooth-interface.
Page 36
Send measure data The recorded measuring values can be transmitted as a CSV-file to a Bluetooth end device. For the selection of the measuring values that should be transmitted, the start time and the length must be defined. Start Time •...
Page 37
Receive CSV Lin . table To simplify enormous linearization procedures directly at the device, it is possible to generate a linearization table as CSV-file and transmit it into the device. There are different tank calculation programs available to calculate the linearization of a tank form comfortably.
Page 38
Receive firmwareupdate The internal software of the device (firmware) can be updated by a new firmware, that could include functional improvements, functional extensions, new functions or also customer specific modifications. At the file transmission the safety of the power supply must be ensured. A power fail can lead to a completely irreversible device failure.
Start-up procedure Pressure measurement The sensor is preconfigured to pressure measurement dependent on the pressure range alternatively in unit mbar or bar by factory. Only a few changings must be optionally made. Sub menu Basic Setting Position Adjustment • Primary Unit •...
Level measurement The filling level is calculated by the device with entering the gravitational acceleration mean value 9,81m/s and the density of the process material into the equation. Sub menu Basic Setting Position Adjustment • Operating Mode Level • Primary Unit •...
Volume measurement The operation mode level is used. For the indication of the tank volume a display scaling can be made. If a nonlinear tank style is used, a linearization must be set. Predefined linearization curves for some tank styles are available. Sub menu Basic Setting •...
Flow measurement The operation mode level is used. For the indication of the flow amount a display scaling can be made. If a nonlinear flow opening style is used, a linearization must be set. Predefined linearization curves for some flow opening styles are available. Sub menu Basic Setting •...
Maintenance The device is free of maintenance. Special substances can lead to solid coatings on the membrane. Seized depositions can lead to faulty measurement results. In the case of coat forming liquids the membrane must be regularly cleaned e.g. with clear water. Don’t use sharp tools or aggressive chemicals for cleaning.
Page 44
Repair A repair may only be carried out by the manufacturer. If the device must be sent back for repair, the following informations must be enclosed: An exact description of the application. • • The chemical and physical characteristics of the product. A short description of the occurred error.
Technical Data Auxiliary power supply Supply voltage U Preference output 0/4...20 mA 9..30 V , reverse polarity protected Preference output 0…10 V 14..30 V , reverse polarity protected Residual ripple U ≤ 2 V ≤ U ≤ U Smin Smax Supply current I Preference output 0/4...20 mA ≤...
Output Bluetooth-Interface Version Bluetooth 2.1 + EDR Specification Class 2 Transmit power ≤ 2,5mW/4dBm Range ≤ 10m Measuring accuracy Reference conditions EN/IEC 60770-1 resp. EN/IEC 61003-1 T = 25 °C, relative humidity 45...75 %, environmental air pressure 860..1060 kPa Calibration position Vertical, process connection bottom side Warm-up time ≤...
Process conditions The permitted process temperature range results from the combination of standard range, expansion and limitation, whereby the range is defined by the narrowest limitation. Process temperature -40°C...+100°C Expansion Temperature decoupler -40°C...+125°C Process diaphragm seal + temperature decoupler -10°C...+200°C Process diaphragm seal - Others depending on Requirement Limitation Gasket - FPM -25°C...+200°C...
Environmental conditions The permitted environmental temperature range results from the combination of standard range and expansion, whereby the range is defined by the narrowest limitation. Environmental temperature -20°C...+50°C Expansion Backlight LCD ≤ 80% >> -20°C...+60°C Backlight LCD ≤ 60% -20°C...+70°C >>...
Materials - not process wetted Terminal enclosure CrNi-steel Control panel surface PC / PES Electrical connection part Device plug PUR Pressure compensation element Enclosure PBT Membrane PES Gaskets FPM – fluorelastomere (Viton®) Pressure transmitting liquid Silicone oil (only at construction form type Vegetable oil H –...
Dimension drawings Terminal enclosure Temperature decoupler ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Process connection Construction form S - Standard Type A - G 1½“ ISO 228-1 Length L1 ≤ 300 mm Construction form K - short construction form, flush-mounted Type 8 - G ¾“ ISO 228-1 - flush mounted Type 9 - G ½“ ISO 228-1 - flush mounted ACS-CONTROL-SYSTEM GmbH l Lauterbachstr.
Page 52
Type A - G 1½“ ISO 228-1 - flush mounted Construction form F - flush mounted Type N - DN40 DIN 11851 – flush mounted Type M - DN50 DIN 11851 – flush mounted ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 53
Type O - Varivent® N, Ø68 mm Type L - DRD DN50, Ø65 mm Type R - Flange DIN EN 1092-1, A (B - DIN 2527), DN25 ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 54
Type F - Flange DIN EN 1092-1, A (B - DIN 2527), DN40 Type G - Flange DIN EN 1092-1, A (B - DIN 2527), DN50 Type H - Flange DIN EN 1092-1, A (B - DIN 2527), DN80 ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 55
Type J - Flange DIN EN 1092-1, A (B - DIN 2527), DN100 Type T - Tri-Clamp 2“ (ISO 2852 DN51 / DIN32767 DN50) Type B - Coupling nut adapter Ø44mm ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 56
Construction form T - Extension cable Type A - G 1½“ ISO 228-1 / Probe extension A / E Length L1 ≤ 100 000 mm Dimension drawings of other process connections on request ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 57
Construction form R - Tube extension Type A - G 1½“ ISO 228-1 / Probe extension D – Ø40mm Length L1 ≤ 3000 mm Dimension drawings of other process connections on request ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Page 58
Type 8 - G ¾“ ISO 228-1 / Probe extension F - Ø22mm Length L1 ≤ 2000 mm Dimension drawings of other process connections on request Construction form H – Process diaphragm seal Dimension drawings on request ACS-CONTROL-SYSTEM GmbH l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l info@acs-controlsystem.de...
Order Code Type SN50 Standard Construction form Standard - process connection A Short construction form, flush-mounted - process connection 8 / 9 / A Extension cable - probe extension A / E Tube extension - probe extension D / F Flush-mounted - process connection N / M / O / L / R / F / G / H / J / T / B Process diaphragm seal metallic membrane, vegetable oil FN1, steel 1.4404/316L, process temperature -10°C..+200°C Special construction form...
Need help?
Do you have a question about the Hydrocont SN50 and is the answer not in the manual?
Questions and answers