4. Installation Instructions
Installation Steps:
1. Place and mount the BBINT50A, see chapter 5
2. Connect the BBINT50A, see chapter 6
3. Configure the BBINT50A, see chapter 7
CAUTION
Read the entire manual before installing the BBINT50A. Keep the manual in a safe location
for future reference.
•
Operating temperature range: -20 up to +60 ºC, >40 ºC derating power
[-4 up to +140 ºF, >40 ºF derating power].
•
Never use the BBINT50A at a location where there is danger of gas or dust explosions.
Never Mount the BBINT50A in such a way that airflow through the heatsink is
obstructed. This device requires a minimum of 10cm of clearance on every side.
•
Do not install the BBINT50A in the same compartment as gassing batteries. Do not mount
in the same area as batteries that might release corrosive sulphur fumes or explosive gasses.
•
Be sure that the output of the supplying source is switched off during installation. Also be sure
that no load is connected to the batteries during installation, to prevent hazardous situations.
•
Use cables with an appropriate size, see the following table.
Models
BBINT50A
Min. 3 Nm – max. 5 Nm
Recommended cable sizes DC input/output
Minimum cable size Input
16 mm2 [AWG 6]
10
Minimum cable size Output
16 mm2 [AWG 6]