Tamas Hydronic Panels
User Guide
Version 1.0
Low Loss Header Series
Installation and Commissioning Guide
4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747
www.tamashydronic.com

Advertisement

loading

Summary of Contents for Tamas Low Loss Header Series

  • Page 1 Tamas Hydronic Panels User Guide Version 1.0 Low Loss Header Series Installation and Commissioning Guide 4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747 www.tamashydronic.com...
  • Page 2: Table Of Contents

    Tamas Hydronic Panels Low Loss Header Series Table of Contents Table of Contents Introduction..........................4 Components..........................5-7 Operation............................ 8 Technical Data..........................9-12 Wiring............................13 Commissioning........................... 14 Warranty............................15 This User Guide is Applicable to: Low Loss Header Boiler Panels (DHW Priority)
  • Page 3 The following parts lists and application drawings are general samplings. Each panel configuration dictates the required components, including pump type. See the Technical Data section of the manual for specific information on each part in your particular variation of the Tamas Low Loss Header Panel.
  • Page 4: Introduction

    Tamas Hydronic Panels Low Loss Header Series Overview, Options and Dimensions Introduction Low Loss Header Panel Low Loss Header Expansion Panel Low Loss Header Boiler Panel T-LL-00-1400 Model Shown T-LL-EX-0120 Model Shown T-LL-BD-2110 Model Shown Description Main Features When used in conjunction with boilers, the low-loss header •...
  • Page 5: Components

    12” 27” 27” Components 22” x 26” Galvanized Backpan Tamas Ball Valves Tamas Control Box with 5’ Power Cable Stainless Steel Low Loss Header Zone Pumps UPS 15-58 Hose Bib Hook-Up 24V AC Transformer with Internal Fuse Manual Air Vent Temperature Gauge 4516 112 Ave S.E.
  • Page 6 27” 27” Components 22” x 26” Galvanized Backpan Temperature Gauge Tamas Control Box with 5’ Power Cable Tamas Ball Valves Zone Pumps UPS 15-58 Thermostatic Mixing Valve 24V AC Transformer with Internal Fuse 4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747 www.tamashydronic.com...
  • Page 7 21.5” 12” 27” Components 22” x 26” Galvanized Backpan Tamas Ball Valves Tamas Control Box with 5’ Power Cable Stainless Steel Low Loss Header Zone Pumps UPS 15-58 Hose Bib Hook-Up 24V AC Transformer with Internal Fuse Air Vent Temperature Gauge Boiler Pump UPS15-58 / UPS 26-99 4516 112 Ave S.E.
  • Page 8: Operation

    Tamas Hydronic Panels Low Loss Header Series Operation Operation 3 Temp Low Loss Header Panel with Expansion Panel Application Expansion Connec ons T-LL-BD-1400 T-LL-EX-1120 Boiler Fan Coil DHW Tank Radiant Zone Operation of the Primary When a Low Loss Header Panel is connected to a boiler system, the panel regulates the water distribution quantity to accommodate demand.
  • Page 9: Technical Data

    Tamas Hydronic Panels Low Loss Header Series Technical Data UPS 15-58 3 Speed Pump UPS 15-58 Three Speed Pump Performance Min fluid temp 10 Bar Max system pressure NSF Std 61 Annex G 4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747 www.tamashydronic.com...
  • Page 10 Tamas Hydronic Panels Low Loss Header Series Technical Data UPS 26-99FC/BFC SUPERBRUTE UPS 26-99 Pump Without Check Valve With Check Valve Flow (GPM) Flow range: 0 - 34 U.S. GPM Head range: 0 - 30 FEET , e l Maximum fluid temperature: 230°F (110°C)
  • Page 11 Tamas Hydronic Panels Low Loss Header Series Technical Data Thermostatic mixing valve (ASSE-1017 listed*) • Anti-scald function. • Snap-on cover for protection and to prevent unauthorized adjustment or tampering. • Cover label for recording settings including recorded outlet temperature and date installed.
  • Page 12 Tamas Hydronic Panels Low Loss Header Series Technical Data Tamas Low Loss Header Delta T Max Flow Rate BTU Load 24.2GPM 242000 24.2GPM 280000 24.2GPM 365000 24.2GPM 420000 24.2GPM 475000 Dimensions 1" NPT thread 1/2 " NPT thread Bottom 4516 112 Ave S.E. Calgary, Alberta • Tel: (403) 279 0020 • Fax: (403) 279 0747 www.tamashydronic.com...
  • Page 13: Wiring

    Thermostat Connections Drawn: See reverse for Connect the thermostat for a space heating zone to the terminal block on the Tamas Panel. Do not supply 24V power to Thermostat Wiring Options Thermostat Wiring Options the thermostat circuits or attempt to supply 24V AC for any other application.
  • Page 14: Commissioning

    Low Loss Header Series Commissioning System Filling Procedure 1. Disconnect power from the Tamas Hydronic panel 2. Close all isolation valves to the zones 3. Begin filling the panel through the provided hose bib connection on the panel 4. Open the supply isolation valve on the panel for the first zone 5.
  • Page 15: Warranty

    Limitation of Liability. In no event will Tamas Hydronic Systems Inc. be liable for any damages, including loss of data, loss of profits, costs of cover or other incidental, consequential or indirect damages arising out of the installation, maintenance, commissioning, performance, failure or interruption of a Tamas Hydronic Systems Inc.
  • Page 16 /TamasHydronicSystems Custom, Reliable Hydronic Systems /TamasHydronic Tamas Hydronic Systems Inc. Phone: 1 (403) 279 0020 4516 112 Avenue SE Fax: 1 (403) 279 0747 /company/tamas-hydronic-systems Calgary, Alberta T2C 2K2 info@tamashydronic.com...