UNI TEMP
UNI TEMP is a constant
temperature controller. It is
designed for mounting on mixing
valve.
It is also equipped with mounting
kit for assembly on mixing valves
of other manufacturers.
Controller has a fixed angle
rotation of 90° and possibility of
With DIP switches inside actuator
is possible to set the following
parameters:
- Direction of rotation (direct
CW / inverse CCW)
- Different temperature ranges
depending on the application
- Reaction factor x1/x10

Technical data

Electrical data
Supply voltage
Power
Connection cable
Sensor type
Functional data
Torque
Rotation time
Manual override
Position indication
Recommended mounting
position
DIP switch settings
Safety
Protection class
Degree of protection
Ambient temperature
Media temperature
Storage temperature
Maintenance
Weight
Enclosed mounting
FIRŠT (ROTOMIX, ROTOMIX G), ESBE (VRG, VRB), ACASO (TERMOMIX), BARBERI,
kit
FEROTERM, PAW, EURONORM, ESBE, IMP, DANFOSS, BESSER, SELTRON, LOVATO,
TUXHORN, STRAWA, CIMBERIO
FIRŠT-ROTOTEHNIKA, s.p., Radegunda 54, 3330 Mozirje, info@?rst.si, http://www.?rst.si
PE VELENJE: Koroška c. 56a, 3320 Velenje, tel:++386 (0)3 898 35 00, fax: ++386 (0)3 898 35 35
It is intended for:
maintaining a constant temperature in boiler heating circuit (protection
against condensation),
use in under floor heating applications, industrial processes, heat
accumulators,
use in domestic hot water systems or swimming pools (individual
systems, SPA, public swimming pools).
24VAC, 50Hz, ± 10%
5VA
2x0,5mm , length 2m
KTY 81-210 PVC (cable length 1.5m), insulation: -30°C to
105°C (adapter set enclosed)
max 12Nm
73s/90°
Manual or permanent with pushbutton (for maintenance
purposes)
Handle position on controller cover
All positions except upside down
1. Direction of rotation (direct CW / inverse CCW)
2. Different temperature ranges depending on the
application (0°C..100°C, 60°C..85°, 20°C..70°C,
25°C..45°C)
3. Reaction factor x1/x10
II
IP44 (IEC 60529 (2001-02))
0..+55°C
According to valve's specifications
-20°...+80°C
Maintenance-free
Approx. 480g (without valve)
2
cX4-1011-UNI-TEMP-product-info_v1-en.cdr
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UNI TEMP and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for First UNI TEMP

  • Page 1 UNI TEMP UNI TEMP is a constant temperature controller. It is designed for mounting on mixing valve. It is also equipped with mounting kit for assembly on mixing valves of other manufacturers. Controller has a fixed angle rotation of 90° and possibility of manual control.
  • Page 2 UNI TEMP Electrical installation: l=1,5m Sensor KTY81-210 24VAC, 50Hz Dimensions: Order information: Code Article Voltage Time Torque 21135 UNI TEMP/MR-B-01 24VAC, 50Hz 73s/90° max. 12Nm Enclosed mounting kit for following mixing valves: FIRŠT (ROTOMIX, ROTOMIX G), ESBE (VRG, VRB), ACASO (TERMOMIX), BARBERI, FEROTERM, PAW, EURONORM, ESBE, IMP, DANFOSS, BESSER, SELTRON, LOVATO, TUXHORN, STRAWA, CIMBERIO.
  • Page 3 UNI TEMP Mounting on the valve: FIRŠT (ROTOMIX G), ESBE, ACASO Mixing valves ESBE VRB, VRG 3-way mixing brass valve (TERMOMIX), BARBERI, FEROTHERM, ROTOMIX F3 PAW, EURONORM, IMP, DANFOSS, ROTOMIX F4 BESSER Mounting kit Code Enclosed mounting kit 58024 FIRŠT (ROTOMIX, ROTOMIX G), ESBE...
  • Page 4 UNI TEMP Settings: 1 Mechanical indication. Indicator can be set according to the valve assembly 2 Button for manual/auto control 3 Handle for manually controlling the drive, which also serves for the indication position of the valve 4 Button for adjusting the required temperature. When adjusting the temperature, the set value flashes on LCD screen.
  • Page 5 UNI TEMP Controller behavior diagram as a function of temperature: Example: -Desired temperature: 50 C ° -Xp parameter – proportional control range of valve (10K) T (°C) 100% closing Nearer the desired temperature (50 °C shorter pulses. opening area °C...
  • Page 6 UNI TEMP Examples: UNI TEMP UNI TEMP Maintain a constant temperature of heat reservoir Solid fuel boiler - Maintain a constant temperature in heating circuit TEMP UNI TEMP DTC100/2 UNI TEMP Floor heating - Maintain a Solar pool heating - Maintain a constant temperature of...
  • Page 7 UNI TEMP In compliance with standards All our products fulfil the essential safety and protection requirements for CE conformity marking according to the following directives: EMC directive: 2004/108/EEC / LV directive: 2006/95/EEC / PAH directive 2005/69/EEC. In compliance with standards: EN 60730-2-14;...

This manual is also suitable for:

Uni temp/mr-b-0121135

Table of Contents