Pfannenberg DTS 8 E Series Operating And Assembly Instruction Manual

Side-mounted cooling units
Table of Contents

Advertisement

Quick Links

外挂式机柜空调操作及安装说明书
DTS 8xxxE 系列
Operating and assembly instruction
For side-mounted cooling units
DTS 8xxxE
685408014B /10-2016

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DTS 8 E Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pfannenberg DTS 8 E Series

  • Page 1 外挂式机柜空调操作及安装说明书 DTS 8xxxE 系列 Operating and assembly instruction For side-mounted cooling units DTS 8xxxE 685408014B /10-2016...
  • Page 2: Table Of Contents

    自检功能 1 手册提示 ............... 2 ............5 10.7 设置的可能性 ..........5 10.8 2 搬运 ............... 2 运输 11 参数查看与设置 ..........5 ..............2 储运 ..............2 12 清洁和维护 ............6 开箱 ..............2 清洁 12.1 ..............6 维护 3 供货范围 ............... 2 12.2 ..............
  • Page 3: 手册提示

    危险! 机组的钣金件边缘有可能残留金属毛刺,在维护或安 请在安装机组前完整仔细阅读此手册。 装时务必带保护手套。 本手册构成标准供货不可分割的一部分, 要求保障时,需要提供故障的确切信息(如有可能请提供照 必须保存至机组报废为止 片),机种型号和序列号。 1 手册提示 3 供货范围 此手册为百能堡机电设备有限公司(以下简称百能堡)提供 供货范围包括: 的门装或侧装螺栓固定,外挂式机柜空调系列的安装运行指 • 机柜空调 南。 • 附件包(包括紧固件,插头式电气连接器等) 提示 • 特殊的附件(如适用) 每台机柜空调的技术规格及安装、连接和操作相关信息也可 • 技术规格书 在随机附带的单独文件中查询。本手册中,安全提示和其他 • 使用说明书 信息以下形式出现: 4 一般信息 • 百能堡可以妥善处理旧设备,但客户需承担运输费用. 危险! • 百能堡生产的机柜空调不含以下物质: 如果没有严格遵守所述的措施,将有生命危险或造成健康危 - 多氯三联苯 害。...
  • Page 4: 配置与功能

    水。为了避免对电控柜及本制冷系统发生任何损害,必须排 危险! 出冷凝水。 任何清洁或维护操作之前,需切断机柜空调电源。 冷凝水排放方式如下: 只有原厂备件可以使用。 • 带冷凝水蒸发器(可选)的制冷设备在正常情况下,可以 蒸发掉水分。但为防止蒸发器故障后产生的冷凝水溢流,请 7 功能 连接冷凝水管路,然后再通过水管排出。 7.1 配置与功能 始终确保冷凝水正确地排出。 设备配置: 在特定情况下有可能会发生凝结水过量,例如,机柜不密 1) 高品质关键零部件 封或机柜内部温度经常低于露点温度。 2) 压缩机保护装置 注意: 3) 智能控制系统 4) 冷凝水蒸发器 (可选) 在正常运行过程中发生冷凝水过量 请检查机柜的密 5) 2~400V交流供电(可选) 封。 我们建议安装一个门接触开关,当机柜门被打开时 机 设备功能: 1) +15℃~+55℃外部环境温度 柜空调将自动关闭 以防止过度冷凝水。 2)...
  • Page 5: 电气连接

    • 机柜空调应当经由断路器连接到电源(请选择合适的断 按压在门板上, 然后将密封条9或10或12外边线与8或11外边 路器),断开断路装置时 其触点间隙应不少于 毫米。 线对齐后贴在门板上。 • 电源线上不可以串接温度传感器。 3) 在机柜内侧,取出附件包内的螺栓、平垫片、弹垫、螺母 • 电源线上需要串接铭牌注明的保险丝 作为线路保护。 及螺栓(标号3,4,5,6,7)将空调锁紧。 • 电源连接和维修,如果适用,只能由授权的经过培训的电 4) 将出水管通过机柜空调底板,使冷凝水能自由流下,并将 工来进行。 水管切至所需长度。 电源连接: 电源电压和频率必须符合铭牌标示值。 注意: 如果电压过高可能会导致器件损坏。 一般空调的额定电压 或 。 230V 400V 门触点: · 为了避免任何破坏性的影响,建议使用一根带护线套的双 绞线电缆。 警告 无需另接外部电源。 如果门触点开关未被使用,需将其短接。 故障指示 对于故障信号指示有1对连接触点可使用(见技术附页线路 图)...
  • Page 6: 操作显示器

    机柜空调具有上电检测、运行时实时监测功能。上电检测过 并及时上报。 程中如果有故障,空调会发出相应的报警,这使得在进入工 10.8 设置的可能性 作模式之前更方便的排查设备故障。 机柜空调可通过操作显示器来选择柜内不同设定温度以及 参数。(见第11节) 警告 注意: 机柜空调只能在装有前盖的情况下运行,否则会因散 热不良造成机柜空调被损坏。 机柜空调设定参数的改变需由授权的人来完成! 10.2 操作显示器 11 参数查看与设置 机柜空调装有操作显示器。上电后操作显示器显示0.0℃,3S 机柜空调可以通过操作显示器对参数进行监控设置。 后显示柜内实时温度,表明机组在正常操作模式。如果发生 • 机柜空调电子控制系统包括主控制系统、操作显示系统。 故障或有报警输出时,操作显示器显示报警代码,警报灯点 亮并伴随报警声,这使诊断机柜空调故障更容易(见章节 14)。 10.3 启动测试模式 通电前,若门触点断开,则机柜空调不启动,直到门触点闭 合后, 机柜空调进入自测试模式,自测试模式将不受外部环境 影响。 机柜空调运行启动模式持续 30 秒, 之后是测试模式持 面板上的指示灯从左到右排列的功能含义如下表: 续 110 秒。测试模式时,有故障设备继续运行,直到测试模 式结束,产生相应的报警代码,如有故障则需解除故障后进 指示灯...
  • Page 7: 清洁和维护

    可 调 整 参 数 值 的 大 小 , 调 整 到 正 确 的 数 值 后 再 次 按 • 用软刷或高压空气进行作业。 “Select”键确认修改,然后按“Mode”键返回上层菜单 步骤如下: 或者静置 5min 自动返回主界面。如果不需要修改,直接 1)断开机柜空调电源。 2)打开外壳。 3)清洁风道。 4)清洁外风机。 按“Mode”键返回上层菜单即可。 5)清洁交换器。 6)装回外壳 注意: 7)接通电源并观察上电自检,确保设备运转正常。 普通用户只使用“t1”, 即机柜内设定温度,其他 防止电气元件漏电。...
  • Page 8: 故障排除

    14 故障排除 尽管有精心维护,还是有可能产生故障。机柜空调的实时自检功能能够准确的自行诊断设备故障。 如果机器发生故障,操作显示器显示相关报警代码,用户可根据下表中的报警代码查找,使得诊断更容易。 报警列表 报警代码 描述 故障排除方法 1)检查感温头 Pb1; 2)检查连接线是否损坏; AL01 Pb1 报警 3)检查接头是否插错位。 1) 检查门开关; AL02 机柜门打开 2)检查接线是否松动; 3)检查接线是否接错。 1)查看是否 AL02 报警,此时设备停止工作; 2)检查内外风机是否正常工作; 3)检查压缩机是否正常工作; AL03 超温告警 4)检查冷凝器是否脏堵; 5)检查内部风口是否堵塞,风道是否顺畅; 6)检查热负荷。 警告:非授权人员不可检修此设备。 15 保障条款 以下情况保障将失效: · 机组的不恰当使用,不适宜的运行条件或不遵守操作指导; · 在腐蚀或酸性空气环境下使用; · 由脏污或脏堵的过滤垫造成的损坏; ·...
  • Page 9: 附表 I

    附表 I 显示参数(操作显示器) 参数 描述 最小值 最大值 默认值 单位 内循环回风温度 ℃ 启动温度 ℃ 门开关,0 代表门开关断开,1 代表门开关闭合 内风机,0 代表停止工作,1 代表正在工作 外风机,0 代表停止工作,1 代表正在工作 压缩机,0 代表停止工作,1 代表正在工作 故障报警,0 代表有故障输出,1 代表无故障,设备正常工作 AL01 Pb1 报警,0 代表有故障,1 代表无故障 AL02 机柜门打开,0 代表有故障,1 代表无故障 AL03 超温告警,0 代表有故障,1 代表无故障 * 为客户可改参数。...
  • Page 10 1 Hints on the manual ..........10 10.6 Equipment fault ..........14 10.7 Self-check function ..........14 2 Handling .............. 10 10.8 Setting possibilities ..........14 2.1 Transport............. 10 2.2 Storage ..............10 11 Parameters View and Settings ......14 2.3 Unpacking ............10 12 Cleaning and Maintenance .........15 3 Scope of delivery and options ......
  • Page 11: Hints On The Manual

    They must be sent to one of our works shipment/postage •Prior to transport remove the cooling unit and pack it paid. • All cooling units produced by Pfannenberg are free separately if the complete switch cabinet is to be transported.
  • Page 12: Name Plate

    The compressor (1) compresses the refrigerant until high 6 Safety pressure is achieved. During this process temperature Cooling units produced by Pfannenberg are designed increases. In the condenser (2) heat is dissipated to for application dissipating heat from switch cabinets (IP ambient air, the coolant becoming liquid.
  • Page 13: Installations

    The condensate is discharged in the following way: To facilitate installation with heavy units, M8 lifting eyes •In case of normal condensate drainage a reservoir can be screwed into the upper fixing on the equipment housing. Simple‟‟ one man installation‟‟ is thereby (option) collects the condensate which is then drained by means of a hose.
  • Page 14: Electrical Connection

    Power supply connection: Both mains voltage and frequency must correspond to the nominal values indicated on the name plate of the cooling unit. Attention: The cooling unit may be damaged if the voltage is too high. It‟s nominal voltage is 230V or 400V. Door contact: In order to avoid any disruptive influences, it is recommended that a sheathed cable with twisted pair...
  • Page 15: Operate The Display

    measured by temperature sensor.The cooling unit can be Test mode t=30s-40s Internal fan start up; set at different internal temperature through operating t=40s-50s External fan start up console display, (See attached table) the system will Internal fan stop; Disallowed when exceeds the limit temperature. t=50s-80s Compressor start up The cooling unit has the function of power-on self-test, the...
  • Page 16: Cleaning And Maintenance

    · On any interface, home page will be shown without pressing any button for 300s. Caution: Please set the parameter in the specified range (Appendix Operation panel 1) and incorrect setting will cause the machine to be unable to work properly. 12 Cleaning and Maintenance Light Description...
  • Page 17: Maintenance

    12.2 Maintenance 13 Stopping using Please disconnect the cooling unit when it is not in use for After equipment malfunction, it will automatically prompt a longer period. Ensure that non-authorize persons the fault code, please refer to Chapter 14 of the main fault cannot start the cooling unit.
  • Page 18: Trouble Shooting

    14 Trouble shooting In spite of careful maintenance, the equipment is likely to have a failure. Functions of real-time self-check can diagnose the failure by equipment itself. If a fault occurs, operation display will show the relevant alarm code, user match tech code with below list to get a shooting easily.
  • Page 19 Appendix I Shown parameters (operation display) Parameter Description Min. Max. Default Unit ℃ Air return of inner cycle ℃ * T1 Internal setting temperature Door switch, 0 means open, 1means close Internal fan, 0 means OFF, 1 means ON External fan, 0 means OFF, 1 means ON Compressor, 0 means OFF, 1 means ON Alarm, 0 means alarm output, 1 means units work normal AL01...
  • Page 20 百能堡机电设备(苏州)有限公司 中国苏州工业园区兴浦路333号,现代工业坊5-1-D 邮编:215021 电话:+86-512-6287-1078 传真:+86-512-6287-1077 邮箱:service@pfannenberg.cn http://www.Pfannenberg.cn Pfannenberg (Suzhou) Pte. Ltd. 5-1-D, No.333 Xingpu Road, Modern Industrial Park, SIP, Suzhou 215021, Jiangsu, P.R.C Tel: +86-512-6287-1078 Fax: +86-512-6287-1077 e-mail: service@pfannenberg.cn http: //www.pfannenberg.cn 685408014B /10-2016 685408014_V0.1...

Table of Contents