The red indicator LED near the test button indicates that the battery is being charged.
Continuous red and green is normal up to 24 hours after extended power failure.
Pressing the test button will simulate a power outage. After checking indicators (as above), press test
button to check the entire emergency circuitry. If the "EXIT" lights up during normal operation and
during this test, it is operating!
Once fully charged, the battery will automatically recharge in 24 hours. Our charging circuitry
maintains optimum battery voltage levels to provide superior battery life. If "emergency flashing"
is selected, this unit is UL listed to operate for 12 hours for LED1EM/PLED1EM and 8 hours for
LED2EM/PLED2EM. If "non flashing" is selected, this unit is UL listed to operate in the emergency
mode for 6 hours for LED1EM/PLED1EM and 4 hours for LED2EM/PLED2EM.
The emergency flashing feature is intended for locations where permitted by local codes. Flash rate
is 68 cycles/minute (±10%) at 50% duty cycle. Not intended to be cycled on and off by external control
except when factory equipped with FAP (optional fire alarm interface).
NOTE: Replace with original equipment only. Use of other batteries will void the U.L. listing.
TRANSFORMER
ORANGE (277V)
BLACK (120V)
WHITE (COM.)
GREEN (GND)
LED1EM/PLED1EM
and
LED2EM/PLED2EM
CHECKING DIAGNOSTIC INDICATORS
The green LED indicates that the unit is receiving power.
Once battery is charged; continuous red and green indicators
indicate dead battery or malfunction and service is required.
REPLACEMENT PARTS
P-1
3
5
BLUE
TO SIGN FACE
1
BLUE
6
4
2
BATTERY
Circuit Diagram
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
TEST BUTTON
ORANGE (277V)
BLACK (120V)
WHITE (COM.)
GREEN (GND)
LED1AC/PLED1AC
P-1
TRANSFORMER
1
BLUE
BLUE
2
RED
5
12 TO 24 VOLTS AC OR DC
FAP OPTION
and
LED2AC/PLED2AC
ledseries-installinstr-0603385_a_R01
4
RED
TO SIGN FACE
6
BLUE
BLACK
3
Circuit Diagram
Page 4 of 4