Current Dual-Lite LED1EM Installation & Owner's Manual page 2

Advertisement

OUTLET BOX
(NOT PROVIDED)
GROUND SCREW
FIXTURE BAR
OUTLET BOX SCREWS
(NOT PROVIDED)
CANOPY SCREW
CANOPY SCREW
CANOPY
WIRING
KNOCKOUT
EXIT HOUSING
WASHERS
GREEN
HEX NUTS
GROUND
WIRE
NIPPLE
WASHER
LOCKNUT
WHITE
WIRE
ORANGE WIRE
FOR 277v HOOKUP ONLY
BLACK WIRE
FOR 120v HOOKUP ONLY
1).
Unpack and check for concealed transit damage. Report all transit damage to delivering carrier and file claim.
2).
Remove END PLATE (two END PLATE SCREWS).
PAGE 3
3).
Carefully slide EXIT BOARD(s), FACEPLATE(s) and SHIELD(s), half-way out.
4).
Disconnect EXIT BOARD PLUG(s).
5).
Carefully remove EXIT BOARD(s), FACEPLATE(s), and SHIELD(s) from unit.
6).
Select (top, end, or back) WIRING KNOCK-OUT and remove it.
7).
OPTIONAL: Mount CANOPY to EXIT HOUSING with 2 CANOPY SCREWS, WASHERS & HEX NUTS (provided).
8).
INSURE AC OUTLET POWER IS OFF TO PREVENT ELECTROCUTION !!!
9).
Mount FIXTURE BAR to OUTLET BOX (with 2 OUTLET BOX SCREWS).
10). Screw NIPPLE into FIXTURE BAR.
11). Locate wires from exit sign transformer. Select and use either the BLACK WIRE (for 120v hookup) or ORANGE WIRE (for 277v
hookup). Use only one of these two wires. Unused wire should be capped.
12). Insert selected (BLACK or ORANGE) WIRE along with WHITE WIRE and GREEN GROUND WIRE through LOCKNUT, WASHER,
KNOCKOUT HOLE, NIPPLE, and BRACKET BAR.
13). Attach wires to service - insuring proper connection (white to white, black to black or orange to 277v, and green to GROUND SCREW
provided on FIXTURE BAR.
14). Slip HOUSING AND WASHER onto NIPPLE. (Secure with LOCKNUT. CAUTION: SECURE, BUT DO NOT OVER TIGHTEN !!!)
15). IMPORTANT: In signs with battery, red and black lead wires must be connected to battery or sign will not work upon power outage !!!
16). Select flash or no flash on AC fail with J-1 (See page 3).
17). Select proper ARROW KNOCKOUTS and very carefully remove them (SEE DETAIL ABOVE)!
18). Slide EXIT BOARD(s) back halfway into unit and reconnect EXIT BOARD PLUG(s).
19). Slide EXIT BOARD(s), FACEPLATE(s) and SHIELD(s), back into unit. Replace END PLATE (two END PLATE SCREWS).
20). Apply AC power and Push Test Button... EXIT !!!
ARROW KNOCKOUT(s):
Carefully, punch the point of the arrow
through the back of the plate. Then
carefully work it back and forth to remove.
SPECIAL NOTE:
After connecting Unit to AC
power, the loose Transformer
Wires must be routed and
secured to Unit every
3 inches, using Adhesive-
Backed Mounting Platforms
EXIT BOARD
and Cable Ties (provided).
EXIT BOARD PLUG
END PLATE
SCREW
END PLATE
END PLATE
SCREW
INSTALLATION
PAGE 2
Circuit Board CB2e
(In Battery Units)
J-1
12 TO 24 VOLTS AC OR DC
FAI OPTION
(RED+/BLACK-)
P-3
SW1
P-2
TRANSFORMER
1790-000
TO BATTERY
(RED+/BLACK-)
(RED+/BLUE-)
ALL BATTERY UNITS HAVE (FIELD SELECTABLE) EMERGENCY FLASHING OPTION
If you want the unit to flash during AC power failure, place jumper (see above) on only the upper post
of J-1. If you want the unit to stay on solid during AC power failure, place jumper across both posts of
J-1.
FIRE ALARM OPTION (FAP)
The flashing FAP option requires field wiring to the red and black wires provided on the connector P-
3 (on Battery units) and P-1 (on AC only units). The FAP can be activated with a 12 to 24 VAC signal, or
a polarized input (positive to red) of 12 to 24 VDC. The maximum current required to activate the FAP
is less than 2 MA per exit.
NOTE: If you are using a system that reverses polarity upon alarm you should connect its positive
to the black wire and its negative output to the red wire. This way when the polarity reverses the
FAP will activate. SPECIAL NOTE: Regardless of the selection of J-1, the exit will flash with the
introduction of FAP signal.
BEEPER OPTION (AVAILABLE ONLY ON BATTERY UNITS)
The audible beeper is a factory installed option on pins 3 & 4 of P-3, and requires no field wiring. If
ordered as a FAP-BPR option (Fire alarm beeper), it becomes active only with the introduction of an
FAP signal. If ordered as a BPR option (Beeper only), it will become active with the loss of AC power.
FIELD SELECTABLE
(FLASH/NON-FLASH)
JUMPER
SOUNDER OPTION
(RED+/BLACK-)
Circuit Board CB4B (In AC Only Units)
TO EXIT
P-1: Optional FAP
Hookup Wires
(factory installed)
PAGE 3

Advertisement

loading

This manual is also suitable for:

Dual-lite led2emDual-lite led1acDual-lite led2ac, dual-lite pled1emDual-lite pled2emDual-lite pled1acDual-lite pled2ac