Flame detector
FD 329/330-3-1 «Vega»
User manual
MRBP.425241.001 UM
2022
1

Advertisement

Table of Contents
loading

Summary of Contents for IGM Vega FD 329-3-1

  • Page 1 «IGM-Detector» Co Ltd Address: 27 Engels Prospect, building 5, litera A Saint-Petersburg 194156, Russia, Tel: 8 (800) 234-66-90 Website: www.igm-pribor.com E-mail: support@igm-pribor.ru Flame detector FD 329/330-3-1 «Vega» User manual MRBP.425241.001 UM 2022...
  • Page 2: Table Of Contents

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Contents Page Introduction ..........................3 Intended use ..........................3 Technical specifications ....................... 4 Contents of delivery ....................... 6 Configuration and operation ....................7 Safety precautions ....................... 10 Mounting ..........................11 Mounting location ......................11 Preparation .........................
  • Page 3: Introduction

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 1. Introduction This user manual (UM) is intended to describe design, principle of operation and operating routine of flame detectors «Vega» 329/330-3-1 (hereinafter FD 329/330-3-1 «Vega»). The UM contains basic technical data, guidelines for connection, maintenance service, as well as other information, necessary for the correct operation, storage and repair of flame detectors «Vega».
  • Page 4: Technical Specifications

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 3. Technical specifications Housing material - Aluminium - Marine grade stainless 1 Ex d IIC T6…Т4 Gb Х; Ex tb IIIC T85°C EX-marking …135°C Db Х Sign Х, following the ex-marking, means that while mounting a detector you should use a cable gland and a plug, certified according to TR CU and having a marking according to...
  • Page 5 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Shelf life and conservation of detectors 10 years in the manufacturer's packaging Warranty storage period 6 months since manufacturing Warranty life - 18 months from the day of commissioning; more than months since manufacturing.
  • Page 6: Contents Of Delivery

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 4. Contents of delivery Package includes: Name Identification Number FD 329/330-3-1 «VEGA» Flame detector User manual MRBP.425241.001UM 1 in a set Datasheet MRBP.425241.001DS Approval documentation 1 package in a set, (certificates delivered –...
  • Page 7: Configuration And Operation

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 5. Configuration and operation 5.1 Appearance Figure 1 – FD 329/330-3-1 «VEGA» appearance...
  • Page 8 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 5.2 Overall dimensions Figure 2 - Overall dimensions of the detector with a mounting bracket 5.3 Construction The detector housing is a flameproof enclosure, inside which all detector devices are located, including sensitive elements that convert the electromagnetic radiation of the flame into an electrical signal, electronic amplifiers and filters, digital-to-analog converters, a microprocessor, display elements, optical elements for checking the operability of channels.
  • Page 9 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» FD 329/330-3-1 «VEGA» is resistant to false alarm. It doesn’t respond to UF radiation sources other than flame, such as electric welding, artificial lighting, sunlight, lightning, high voltage arc, X-rays and gamma rays, etc. Notice: It is not recommended to operate FD 329/330-3-1 «VEGA»...
  • Page 10: Safety Precautions

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 6. Safety precautions Any person who is familiar with the configuration, has studied this UM, has been briefed on safety precautions when working with electrical installations and have an electrical safety qualification group of at least III, including in hazardous areas, is admitted to operate the flame detector.
  • Page 11: Mounting

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 7. Mounting 7.1 Mounting location For the correct mounting of the detector, the following factors must be taken into account:  The location of the detectors must ensure unobstructed control of the entire protected area;...
  • Page 12: Preparation

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega»  Availability of a sufficient number of detectors to protect the controlled area;  The detector must be mounted on a rigid surface that is not subject to vibrations;  The detector must be easily accessible for periodic maintenance service; ...
  • Page 13: Detector Connection

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 8. Detector connection 8.1 Power source requirements Before connection it is necessary to: - Calculate the total power consumption rate of the gas detection system in watts, taking into account cold start. - Select a power source with the appropriate power for the calculated load.
  • Page 14: Connection Diagrams

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 3. The information network organization must be carried out in a way that the voltage drop on the –24 V wire between the central processor and the detector does not exceed 8 4.
  • Page 15 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Figure 5 – Connection diagram for an ultra-explosion-proof detector EEx de. Figure 6 – Connection diagram for a detector with uninsulated output 4-20 mA...
  • Page 16 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Figure 7 – Connection diagram for an explosion-proof detector ЕЕх via RS-485 interface Figure 8 – Connection diagram for two explosion-proof detectors EEx via RS-485 interface...
  • Page 17 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Terminal box Figure 9 – Connection diagram for two detectors and a digital channel RS-485 via terminal...
  • Page 18: Commissioning

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Notice: 250 Ohm is necessary to ensure the correct operation of the HART interface, in case of 4-20 mA controller low resistance, it is not necessary to install resistance at the FD 329/330-3-1 «VEGA»...
  • Page 19: Output Signals And Led Indicators Description

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» AN OTHER MALFUNCTIONS! 3.OPEN THE DETECTORS IN A HAZARDOUS AREA WITH POWER ON Detector’s housing must be grounded. Output signal and LED indicators description FD 329/330-3-1 «VEGA» generates the following output signals: - analogue signal with the following meanings: a) 1.9…2.1 mA –...
  • Page 20 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» It is possible to change the sensitivity and signal processing time to reduce the effect of interference when identifying a fire or a nearby location of the alleged fire site («far/near» and «fast/slow»...
  • Page 21: Functionality Check

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 9.1 Functionality check After the equipment mounting and wiring it is necessary to perform FD 329/330-3-1 «VEGA» functionality check. In addition, this check should be carried out regularly at intervals of once every 6 months during maintenance. 9.1.1 Manual mode To check the detector’s functionality by the method of illumination, a special test radiation source is used.
  • Page 22: Automatic Mode

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» For switching, it is necessary to: - put the magnet to the recess on the detector (see figure 12) (a click will be heard), - turn off the power for 5 seconds, - turn on the power and remove the magnet in 5-10 seconds.
  • Page 23: Factory Default

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 9.2 Factory default Table 2 № Operation Description Factory Notice mode default «Far – Far 25 meters Switching using the service near» Near 15 meters program «Fast-slow» Fast – standard mode Slow In the slow mode, high noise Slow –...
  • Page 24: Maintenance Service

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» 10. Maintenance service Maintenance service includes: FD 329/330-3-1 «VEGA» visual inspection; FD 329/330-3-1 «VEGA» clearing; Grounding and explosion-protection state check; Functionality check. Visual inspection. During visual inspection it is necessary to check: -standby mode indication by the detector;...
  • Page 25: Packaging

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Any other malfunctions in the operation or due to external influences require the detector to be stopped until it is completely restored or replaced with a serviceable detector. Troubleshooting must be done in the following order: 1.
  • Page 26: Marking And Sealing

    FD 329/330-3-1 «VEGA» must be sealed with the manufacturer’s seals. 16. Warranty The manufacturer Co Ltd «IGM-Detector» guarantees the compliance of the flame detector FD 329/330-3-1 «VEGA» with the requirements of the technical conditions provided that the consumer follows operating, transportation and storage terms of this UM.
  • Page 27 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» - in cases of defects caused by force majeure (consequences of natural disasters, fires, floods, high-voltage discharges, lightning, etc.), accident, intentional or careless actions of the consumer or third parties. Appendix A FD 329/330-3-1 «VEGA»...
  • Page 28 MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» To change the exchange rate over the RS-485 channel it is necessary to write a code corresponding to a certain exchange rate to the register with address 0x01, placing it in the lower byte of the register (In the upper byte - the device address).
  • Page 29: Appendix B Ex-Protection Drawing

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Appendix B Ex-protection drawing...
  • Page 30: Revision History Sheet

    MRBP.425241.001 UM version 1.1 01.05.2022 FD 329/330-3-1 «Vega» Revision history sheet № Sheet number (pages) Total Chang sheet of the Signature Date change replace null number docum (pages)