5 amp automatic load control relay

Advertisement

Installation Instructions/User Manual
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
Wiring Discriptions
Wire Color
Description
BLACK
Normal Hot
RED
Wall Switch Input (Self-
Test Input)
WHITE
Normal Neutral or other
Phase
BLUE
Emergency Hot
YELLOW
Emergency Hot Switched
to load
WHITE/BLUE
Emergency Neutral or
other Phase
WHITE/VIOLET
Remote test Input
(Class 2, Dry Contact
WHITE/RED
Input)
ORANGE (N/O)
Feedback / Dimmer
VIOLET (C)
Contact
WHITE/YELLOW (N/C)
To test the ELCR periodically, repeat the appropriate Test Procedure above in accordance with national and local codes.
Troubleshooting
Condition
Action
• Check Emergency Power Input wiring (Blue & White/Blue
Red LED is OFF
Green LED is OFF
• Check Normal Power Input wiring (Black and White wires)
Yellow LED is ON but Load
• Check bulbs and ballast.
is OFF
• Check Load wiring (Yellow wire and Load's neutral).
• Verify Load's operating voltage is the same as the
• Replace unit
Load is ON but Yellow LED
• Replace Unit
is OFF
Yellow LED and Load do not
• Check bulbs and ballast
turn on when being tested
• Check wiring connections if using a remote test option
• Press local test button on the unit
• Replace unit
Yellow LED and Load will not
• Verify status of Normal Power Input
turn OFF
• Open Wall Switch Input
• Verify that no test inputs are stuck closed. (i.e. Remote Test
Notes
N/A
Must be from same branch circuit as
Black and White. When switched off, a
two second delay keeps the load on to
test Emergency Power. Does not test
Feedback/Dimmer Output
N/A
N/A
Switches out the voltage put in on Blue
N/A
When wiring multiple units together,
White/Violet must be a shared common.
Test is performed when Input is CLOSED
N/O is OPEN when Normal Power is
Absent or Remote test Input is CLOSED.
N/C opposite.
N/O is CLOSED when Normal Power is
Present or Remote Test Input is OPEN.
N/C opposite.
Wall Switch Input does not test this
output.
wires) and voltage
and voltage.
Emergency Power Input Voltage.
is not closed).
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Testing Procedures
Four Options to test the ELCR after
Installation
Initial Test for Correct Wiring
Apply Emergency Power to the Emergency Power Input and Normal
Power to the Normal Power Input. (If using the Wall Switch Input, apply
Normal Power to the switch also, but keep the switch OFF/OPEN.)
a. The Red LED (Emergency Power available) should be ON.
b. The Green LED (Normal Power available) should be ON.
c. The Yellow LED (Load Status) should be OFF.
d. The Load should be OFF.
e. The Feedback/Dimmer Contact (N/O) should be CLOSED.
Local Test Button
1. Turn switched circuit OFF. Emergency light should be OFF.
2. Press and hold "Local Test Button"
3. Emergency light should turn ON.
4. Release "Local Test Button" and emergency light should turn OFF.
Remote Test Button
(Model ELCTB - sold separately)
1. Turn switched circuit OFF. Emergency light should be OFF.
2. Press and hold "Remote Test Button"
3. Emergency light should turn ON.
4. Release "Remote Test Button" and emergency light should turn OFF.
Wall Switch
1. Turn ON wall switch if not already on.
2. Emergency light should turn ON.
3. Turn wall switch OFF.
4. Emergency light will remain on for two seconds before turning off.
Page 4 of 4
Rev 06/06/22
DL_ELCR_INST_R01