5 amp automatic load control relay

Advertisement

Installation Instructions/User Manual
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
Electrical Specifications
Normal Power Supply Voltage
120-277VAC
Normal Power Current Draw
24mA max
Normal Power Operating Frequency
50/60Hz
Emergency Power Supply Voltage
120-277Vac
Emergency Power Current Draw
88mA max
Emergency Power Operating Frequency
50/60Hz
Remote Test Input (Class 2, Dry Contact)
ELCTB or other switching method
Feedback/Dimmer Contact Switching Capability
1A Resistance @ 30Vdc
(Dry Contact Output 1, N/O - N/C)
Relay Contact
5A Electronic/LED Ballast @ 120-277VVAC
SPST
5A Ballast @ 120-277VAC
1: If not using ELCTB Remote Test Button (sold separately), switching methods should be rated for at least 24Vdc. External
voltage should not be supplied to this input. No specific current rating is required.
2: To maintain Class 2, a maximum of 45 total test inputs can be wired in parallel per ELCTB
Installation
ALL INSTALLATIONS AND WIRING SHOULD BE DONE BY QUALIFIED PERSONNEL
Figure B
Ballast
Ballast
Channel
Cover
Figure A
OPERATION
The ELCR will activate an Emergency lighting load automatically upon
the loss of Normal Power. If Normal Power is absent, the status of the
load cannot be overridden. However, if the Normal Power is present,
the Emergency lighting load can be controlled by other means in order
to use it as a Normal Lighting load, depending on the wiring setup.
When used as Normal Lighting, a two second delay will keep the Load
on after Wall Switch is turned off, to perform a Self-Test on the unit.
When Normal Power is present, the N/O status contact will automatically
close. Therefore, when Normal Power is absent, the N/O status contact
will open (perfect for 0-10V dimming controls). The N/C contact will
operate opposite of N/O. A red LED indicates the Emergency Power is
available. A Green LED indicates that Normal Power is present. A Yellow
LED copies the status of the load; if the LED is on, the load is on.
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Mechanical Specifications
Housing UL accepted for use in Plenum
Wire 16" 600V Rated
Operating Temperature -30° to 140° F (-35° to 60° C)
Humidity Range 5 to 95% (noncondensing)
Rated for dry and damp locations only
1,2
Approvals UL listed, UL924, C-UL
STEPS
1. Remove all sources of power.
2. Remove ballast channel cover.
3. Mount ELCR as shown in Figures A and B.
4. Wire the ELCR using an illustration from the "Typical
Applications" section on page 3 or similar setups for
different application.
5. Before applying power, review the Important Safeguards
at the beginning of this document.
6. Finish installation as required by the NEC, NFPA, state,
local, and other codes. Test the ELCR using the "Test
Procedure" on page 4.
MAINTENANCE
No routine maintenance is required for the
ELCR. Occasionally, this device should be tested
to ensure that it works correctly in accordance
with national and local codes.
Using Emergency Lighting as Normal Lighting
Generator
or Inverter
Hot
Generator
or Inverter
Neutral
Utility
Hot
Utility
Neutral
*
The Red wire must be on
the same branch circuit as the
Black wire.
To use Remote Test Input, the
Red wire must be de-energized.
Input can also be sent by a controller.
Overriding a 0-10Vdc Dimmer
Generator
or Inverter
Hot
Generator
or Inverter
Neutral
Utility
Hot
Utility
Neutral
*
The Red wire must be on
the same branch circuit as the
Black wire.
To use Remote Test Input, the
Red wire must be de-energized.
Input can also be sent by a controller.
^
Class 2 Remote Test Input (N/O) for
button, controller, or re alarm panel
Remote Test Button (Model ELCTB)
sold separately
When not using the Remote
Test Input, cap o the White/
Red and White/Violet wires
individually.
Page 2 of 4
Rev 06/06/22
DL_ELCR_INST_R01
Installation Instructions/User Manual
Typical Applications
Automatic
ELCR
Transfer
Emergency
Switch
Panel
Blue
Emergency
Breaker
R
White/Blue
Emergency
Neutral
*
Red
Control
Normal
Circuitry
Panel
Wall
Switch
Black
Normal
Breaker
G
White
Normal
Neutral
Automatic
ELCR
Transfer
Emergency
Switch
Panel
Yellow
Blue
Emergency
Breaker
R
Y
Wht/Blue
White/Yellow
Emergency
Neutral
Violet
Control
Normal
Circuitry
Orange
Panel
Black
Normal
White/Red
Breaker
G
White
Normal
White/Violet
Neutral
*
Red
H
N
+
-
0-10V
Dimmer
Control
currentlighting.com/dual-lite
© 2022 HLI Solutions, Inc. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
ELCR Series
5 AMP AUTOMATIC LOAD CONTROL RELAY
Normal /
Emergency Lighting
Yellow
Y
White/Yellow
Violet
Normal Power
Feedback Status
Orange
(Dry Contact Output)
White/Red
^
White/Violet
^
Class 2 Remote Test Input (N/O) for
button, controller, or re alarm panel
Normal Lighting
Remote Test Button (Model ELCTB)
sold separately
When not using the Remote
Test Input, cap o the White/
Red and White/Violet wires
individually.
Normal /
Emergency Lighting
^
Normal Lighting
Page 3 of 4
Rev 06/06/22
DL_ELCR_INST_R01