EMC3B
Multi-Function Control System for Fire Resisting Rolling Shutters
Aesthetic IP65 enclosure
Battery backup as standard
Combined audio/visual Warning
Normally open volt free contact
Standard operation - audio visual delay then close
Part close operation
Mains fail
Application
The fire control panel provides total control of commercial and industrial fire resisting rolling
shutters in the event of a fire. The EMC3B interfaces directly with the fire alarm on site and
provides the fire resisting rolling shutter with the intelligence to close in the event of a fire,
protecting both occupants and premises from exposure to smoke and flame damage.
Detection of mains failure, low batteries, fire signals and via volt free relays can also
interface with building management, escalators and lifts.
Operating Principle
45 Progress Road, Leigh-on-Sea, Essex, SS9 5PR
www.guardiandoors.net

Advertisement

loading

Summary of Contents for Guardian EMC3B

  • Page 1 The fire control panel provides total control of commercial and industrial fire resisting rolling shutters in the event of a fire. The EMC3B interfaces directly with the fire alarm on site and provides the fire resisting rolling shutter with the intelligence to close in the event of a fire, protecting both occupants and premises from exposure to smoke and flame damage.
  • Page 2: General Arrangement

    General Arrangement 139.50 51.75 36.00 51.75 69.75 69.75...
  • Page 3 External & Internal P.C.B. Features TP40 LED2 LED3 LED4 LED5 LED6 LED7 CONN7 RoHS Compliant TP41 Risk of fire and explosion Do not short circuit battery terminals Do not charge under air tight conditions Do not disassemble, drop or mechanical shock Do not expose to flame or spark Keep out of reach of children RECYCLE BIN...
  • Page 4 External & Internal P.C.B. Features Description Printed Circuit Board Hinges Protective mains insulation cover ( DANGER! Risk of electric shock if removed) Charge O.K. L.E.D. Sounder - If the sounder is continuously active then check that the fuses are OK & the battery voltage is within range (>28 or <20) High Efficiency L.E.D.`s Alternative Conduit/Cable entry positions...
  • Page 5: Terminal Layout

    Terminal Layout Fire Signal 1 Fire Signal 2 Connections Connections 9 10 11 12 13 14 16 17 18 19 21 22 23 24 Mains Solenoid A/Vis Photo Photo Fail Output Output Output Input Fire Signal 2 Fire Signal 1 Fit Link Fit Link Volt-free...
  • Page 6 Terminal Connection Details Photocell Connections A N/C volt-free output will be present to slave the photocell input (`9` & `10`). Photo MINI Standard Terminals Connections for the N/C switch connections from a photocell (Link if not used). Photo (Link Controls Stock Code: 33-1005) Photocell Terminals Fire Signal '1' Connections...
  • Page 7 Terminal Connection Details Fire Signal '2' Connections Link these terminals to use Fire Signal 2 as a volt-free input or leave these terminals free if a 24VDC fire signal is to be used. Fit Link 20 21 Connection for a N/O volt-free Fire signal. or...
  • Page 8 D.I.L. Switch & Potentiometer Function Details D.I.L. Switch `1` Operation Part Close Function ON/OFF D.I.L. Switch `2` Operation Close on Mains Fail Function ON/OFF D.I.L. Switch & Potentiometer Operation D.I.L. Switch `1` OFF - Audio/Visual Delay Delay Min. 30 seconds Max.
  • Page 9 EMC-3B Audio/Visual Control Panel Operation Basic Operation On receipt of a Fire signal, the audio/visuals will activate. D.I.L. Sw.1 OFF D.I.L. Sw.2 OFF After a delay, set by the Delay pot. (30-91secs), the door will close to the Fully Closed position, set by the Run timer (60-183 secs). Once the Run timer has timed out (60-183secs) the panel will pulse the solenoid output and reset.
  • Page 10 Example Wiring Connections EMC-3B c/w Solenoid Operation Only Fire Signal 1 Fire Signal 2 Connections Connections 9 10 11 12 13 14 16 17 18 19 21 22 23 24 Mains Solenoid A/Vis Photo Photo Fail Output Output Output Input Fire Signal 2 Fire Signal 1 Fit Link...
  • Page 11 Example Wiring Connections EMC-3B c/w MINI Standard Operation Fire Signal 1 Fire Signal 2 Connections Connections 9 10 11 12 13 14 16 17 18 19 21 22 23 24 Mains Solenoid A/Vis Photo Photo Fail Output Output Output Input Fire Signal 2 Fire Signal 1 Common...
  • Page 12 Declaration of Incorporation Product: Audio/Visual Fire Door Interface Type: EMC-3B Version: Declaration is in compliance with: Machinery Directive 98/37/EC, meeting the Essential Health & Safety Requirements relating to the Design and Construction of Machinery and also the Supply of Machinery (Safety) Regulations, as implemented in the United Kingdom.