TPI 3480 Series Installation Instructions Manual

Advertisement

Quick Links

3480/RCH SERIES
MOUNT HORIZONTAL POSITION ONLY.
DO NOT INSTALL ANY CLOSER THAN 12" TO NEAREST WALL
CHECK TO SEE THAT SERVICE VOLTAGE IS THE SAME AS HEATER VOLTAGE.
ALL WIRING MUST CONFORM TO THE NATIONAL ELECTRIC CODE AND EXISTING LOCAL CODE
REQUIREMENTS.
WARNING: To avoid the risk of fire, shock or personal
injury; make sure that the power source is disconnected
before attempting to install, service, clean or disas-
semble the heater or any of its components. If the power
disconnect is out of the line of sight, lock in in the open
position and tag it to prevent the application of power.
INSTALLATION INSTRUCTIONS:
1. Detach heater unit from the ceiling mounting plate
in the recessed can by disengaging the stabilizing
arms on ceiling plate from the heater unit.
4 - #8 drive screws.
2. For a dropped or suspended ceiling, anchor the
recessed can useing either threaded rod, or wire in
an approved method that is sufficient to support
the heater assembly such that the bottom edge of
the recessed can just rest on the T-bar frame. For
plaster or similar finished ceilings, the can should
be installed so the flanges (of the can) are even
with the interior finish or ceiling line.
3. For plaster or other similar finish ceilings attach
the PT3480 accessory plaster frame to the
recessed can using 8 - #8 x 3/4 drive screws.
(detail "AA")
IMPORTANT: OWNER SHOULD RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
NOTE: If plaster frame is required for installation
order it as an option.

GENERAL INFORMATION

4. Hang heater unit from two stabilizing arms on the
ceiling mounting plate in the can. Be sure to
engage the two arms with the hooked ends on the
ceiling plate with the slots in the heater plate.
5. Connect the heater leads with their corresponding
supply leads in the outlet box (75
used). The outlet box is permanently attached to
the top of the can. After this is complete, install the
ceiling plate access hole cover with
2 - #8 drive screws which have been provided.
6. Swing the heater unit up to the ceiling mounting
plate and secure with 4 - #8 drive screws that have
been provided. Do this by placing one screw in
each of the four stabilizing arms on the ceiling
plate.
7. Install heater exterior grille by attaching it directly to
the heater unit. Rotate the exterior grille so that the
two 1/4" dia. holes in the exterior grille aligne with
the manual reset limit control located on the bottom
of the venturi of the heater assembly, also make
alignements so that the venturi of the heater
assembly is on the outside the venturi of the
exterior grille. Secure to the four bracket arms on
the heater case with 4 - 10/32 x 3/4 button head
machine screws provided.
1
INSTALLATION
INSTRUCTIONS
ATTENTION: Read carefully
before attempting to install
or operate the heater.
O
C wire must be
FORM: 9480
ECO 1-5917
REV. 06/08

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3480 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TPI 3480 Series

  • Page 1 3480/RCH SERIES INSTALLATION INSTRUCTIONS NOTE: If plaster frame is required for installation order it as an option. ATTENTION: Read carefully before attempting to install or operate the heater. GENERAL INFORMATION MOUNT HORIZONTAL POSITION ONLY. DO NOT INSTALL ANY CLOSER THAN 12” TO NEAREST WALL CHECK TO SEE THAT SERVICE VOLTAGE IS THE SAME AS HEATER VOLTAGE.
  • Page 2 3480 / RCH SERIES CEILING HEATER CAUTION: To avoid the risk of fire, shock or personal injury; do not insert or allow any foreign objects or hands to enter any ventilation or exhaust openings. THERMAL CUTOUT IDENTIFICATION WIRING DIAGRAMS: Shown on pages 4, 5, 6 and 7 All 480V Models employ a automatic limit control.
  • Page 3 3480 / RCH SERIES CEILING HEATER REPLACEMENT PARTS REF DESCRIPTION CODE / PART NO. Bottom Grille 3480COMPGRL Fan Blade 51554-002 Circular Louver 56561-101 Hole Plug 57882-001 ACC Mtg. Bracket 54871-001 Disconnect Switch 51617-003 Control Relay See Variations Below 41274-001 24 V COIL 28163-004 120 V COIL 28163-006 208/277 V COIL Class 2 Transformer...
  • Page 4 3480 / RCH SERIES CEILING HEATER WIRING DIAGRAM WIRING DIAGRAM FOR WIRING DIAGRAM FOR SINGLE PHASE 208, 240 SINGLE PHASE 208, 240 OR 277V HEATERS OR 277V HEATERS WD-2 WD-1 WIRING DIAGRAM FOR WIRING DIAGRAM FOR SINGLE PHASE 208, 240 SINGLE PHASE 208, 240 OR 277V HEATERS WITH OR 277V HEATERS WITH...
  • Page 5 3480 / RCH SERIES CEILING HEATER WIRING DIAGRAM WIRING DIAGRAM FOR SINGLE WIRING DIAGRAM FOR SINGLE PHASE 208, 240 OR 277V PHASE 208, 240 OR 277V HEATERS WITH DISCONNECT HEATERS WITH DISCONNECT SWITCH, DOUBLE POLE SWITCH, DOUBLE POLE TAMPERPROOF THERMOSTAT TAMPERPROOF THERMOSTAT AND FAN DELAY AND FAN DELAY...
  • Page 6 3480 / RCH SERIES CEILING HEATER WIRING DIAGRAM WIRING DIAGRAM FOR THREE WIRING DIAGRAM FOR THREE PHASE 208, 240V HEATERS WITH PHASE 208, 240V HEATERS WITH DISCONNECT SWITCH, DOUBLE DISCONNECT SWITCH, DOUBLE POLE TAMPERPROOF THERMO- POLE TAMPERPROOF THERMO- STAT AND FAN DELAY STAT AND FAN DELAY 3-“T2S”...
  • Page 7 3480 / RCH SERIES CEILING HEATER WIRING DIAGRAM HEATING ELEMENT HEATING ELEMENT CRIMP NUT CRIMP NUT REMOTE MTD. RELAY MOTOR REMOTE MTD. RELAY MOTOR 57912-002 "F" 208V 57912-002 "F" 208V 57912-003 "H" 240V 57912-003 "H" 240V LIMIT CONTROL LIMIT CONTROL BLACK BLACK BLACK...

This manual is also suitable for:

Rch series81rch221rch271rch281rch321rch3 ... Show all

Table of Contents