RD ADA1
CARBON DIOXIDE CONTROLLER (CO
- Information, on the LCD display, of the level of CO
- Equipped with a voltage-free contact output
- Test function to ensure correct operation of the controller
- Option to change the alarm thresholds
STARTING UP
Immediately after powering, the controller starts the sensor
heating phase; the display shows the message "HEAt" with
the icon "
" flashing.
Later, during normal operation, the display will show the CO
level detected.
The "
" icon is always on.
LEVEL
ON/OFF
By pressing the key "
", if enabled, it is possible to switch
the controller on and off (see step 8 in the "Installation"
paragraph).
BACKLIGHT
Pressing any keys activates the backlight of the display which
will switch off automatically after approximately 30 seconds.
TEST FUNCTION
To verify correct operation of the controller, press and hold the
"TEST" key for more than 20 seconds; the "OUT 1" output
key will be activated and the display will light up the "
icon for approximately 30 seconds and the message in motion
"- - - -" will be shown to indicate that the test is in progress.
Press the key " " to exit the "TEST" function at any time.
ALARM THRESHOLD DISPLAY
During normal operation, by pressing the "▲" or "▼" keys,
will show on the display (for approximately 6 seconds) the CO
threshold set.
RESET
To reset the controller remove voltage from the device for a
few seconds and then switch it back on again.
Note: the data set will not be reset; the device will just be
activated again.
OPERATION
In normal operation, the LCD displays the "
and the concentration of CO
2
environment in which it is installed.
If the device detects a concentration of CO
than the value set in the user parameter 'CO2t', the output
OUT1 will be activated. Activation of the output will be
indicated on the display by the icon "
The output will be disabled if the concentration of CO
below the value set in the user parameter "CO2t" minus the
hysteresis value of the device.
OUT 1 OUTPUT ACTIVATION GRAPH
HYS
(CO
2
N.C.
Position
Legend:
hysteresis value (fixed and immutable)
HYS:
CO
T:
alarm threshold set
2
CO
R:
CO
detected
2
2
FAULT CONDITION
The controller constantly performs a diagnosis of the internal
circuit to verify its correct operation.
Where a fault condition is detected, the display will show the
'FAULT' icon and an indication of the type of fault detected
while the OUT1 output will be activated.
CALIBRATION:
The controller continuously performs a sensor auto-calibration ,
based on the measurements of the last 14 days, without
requiring the intervention of the operator.
RDADA10001SE 029094 220917
)
2
measured by the internal sensor
2
ERROR MANAGEMENT
Sensor Fault
If the device detects an anomaly on the internal sensor, the
display will show the message:
2
"SnEH":
"SnI2":
These reports will be present until the fault is removed.
Internal memory fault
In the event that the device detects a data storage fault, the
display will show the message "SnE2" with the "
TEST
"
flashing.
This type of problem can be solved by restoring the device
default data, by accessing the user parameter 4 "dEFt" and
selecting "dFon".
If the problem is resolved, it is possible to manually reset all
the data to the value before reset.
Conversely, if the fault persists, replace the device.
2
USER PARAMETER SETTING
To adjust the user parameters of the device, proceed as
follows:
1. Press and hold for more than 20 seconds the key "
the display will show the "PARAMETER" icon and the first
user parameter " CO2t ".
2. Repeatedly press the key "
the user parameters:
" CO2T "
" icon
LEVEL
" T_LO "
(in ppm) measured in the
" T_UP "
" dEFt " DEFAULT DATA Management
that is greater
2
3. Press the " ▲ " or " ▼ " key to modify the parameter
selected; the "SET" icon will flash
4. Press the " ▲ " or " ▼ " key again to change the value;
OUT 1
".
each modification is stored automatically .
falls
2
5. To set the user parameter press the key "
6. To exit the selected user parameter modification mode,
press the key "
7. To exit programming of the user parameters, press the key
"
PARAMETER 1: CO2t
Setting this parameter enables definition of the value of CO
beyond which the device enters the alarm phase and activating
T)
(CO
R) ppm
2
the OUT1 output.
Data
N.O.
CO
Position
Relay status
ATTENTION
The adjustment range is linked to the values set in the
T-LO and T-UP user parameters.
PARAMETER 2: T_LO
This parameter sets the value of the lower bound for the alarm
threshold adjustment, which can be set in the user parameter
"CO
t".
2
Data
T_LO
PARAMETER 3: T_UP
This parameter sets the value of the upper bound for the alarm
threshold adjustment, which can be set in the user parameter
"CO
t".
2
"SnEH" or "SnI2"
Fault upper limit on the CO
Sensor.
2
This fault may be linked to environmental
conditions: change the air in the environment and
wait a few hours.
If the fault persists, replace the device.
Fault communication with the CO
This fault can be resolved by resetting the device.
If the problem persists, replace the device.
" to cyclically scroll through
alarm threshold
lower limit threshold
upper limit threshold
".
" again or wait 30 seconds without pressing any key.
Regulation range
t
T_LO .. T_UP
2
Regulation range
500 .. 2000 ppm
Via del commercio, 9/11
I-36065 Casoni di Mussolente (VI)
Tel.: +39.0424.567842 - Fax.: +39.0424.567849
http://www.seitron.it - e-mail: info@seitron.it
Data
T_UP
PARAMETER 4: dEFt
Using this parameter, by selecting the "dFon" data, it is
possible to restore, in the device, the default values set in the
factory.
Conversely, by setting "no" the stored data is maintained.
Data
sensor.
dEFt
2
Note: resetting the DEFAULT data, new heating of the sensor
is activated.
TECHNICAL SPECIFICATIONS
Power:
Absorption:
" icon
Screen resolution
Hysteresis (HYS):
Timeout parameters:
pressing
Sensor type
Detection range:
Precision:
Rated current:
Backlight Off :
Action type:
Overvoltage category:
";
Pollution degree
Tracking Index (PTI):
Class of protection against
electric shock :
Impulse voltage rated:
Number of manual cycles:
Number of automatic cycles: 100000
Software class:
EMC testing voltage:
EMC testing current:
Exclusion distance tolerance
Short circuit fault mode
Temperature
".again
ball pressure test:
Degree of protection:
Operating temp:
Storage temp:
Humidity limits:
Dimensions:
2
Container:
Material:
Colour:
Mounting:
Default
900ppm
WARRANTY
Default
In the view of a constant development of their products, the
900ppm
manufacturer reserves the right for changing technical data
and features without prior notice. The consumer is guaranteed
against any lack of conformity according to the European
Directive 1999/44/EC as well as to the manufacturer's
document about the warranty policy. The full text of warranty
is available on request from the seller.
Regulation range
Default
500 .. 2000 ppm
1200ppm
Regulation range
Default
NO / dFon
NO
85-264V~ 47-440Hz
2.0 VA max.
1ppm.
75ppm - non-modifiable
20 sec. Approximately from last
NDIR
0 .. 2000 ppm
±30ppm ±3% of reading
5(1)A 250V~ SPDT (Voltage-free)
20 sec.
Approximately from last pressing
1
II
2
175
II
2500V
50000
A
230V~ 50Hz
34mA
±0.15mm
75°C
IP30
0°C. 40°C.
- 10°C. + 50°C.
20%. 80% RH
non-condensing
132 x 87 x 23.6 (LxAxP)
ABS V0 self-extinguishing.
Signal white (RAL 9003)
Wall or on recessed box 503.
ENGLISH

Advertisement

loading

Summary of Contents for Seitron RD ADA1

  • Page 1 I-36065 Casoni di Mussolente (VI) - Equipped with a voltage-free contact output Tel.: +39.0424.567842 - Fax.: +39.0424.567849 - Test function to ensure correct operation of the controller http://www.seitron.it - e-mail: info@seitron.it - Option to change the alarm thresholds STARTING UP ERROR MANAGEMENT...
  • Page 2 INSTALLATION - Connect the controller base to the wall plate (pass DESCRIPTION OF CONTROLS the wires through the rectangular openings). Align the base holes with the special wall plate teeth, WARNING then press the base to the left until the plate’s - For correct measurement of carbon dioxide (CO ) in the plastic teeth click (Fig.