Temperature protection relay

Advertisement

DPR-145 User Manual
DPR-145
TEMPERATURE
PROTECTION RELAY
▪ PT100 INPUTS: 4
▪ RELAY OUTPUTS: 4
▪ RS-485 MODBUS PORT
▪ UNIVERSAL SUPPLY
DESCRIPTION
DPR-145 is a precision unit designed for the
temperature protection of dry type or resin filled
MV transformers. The unit offers a high degree of
protection against electromagnetic disturbances.
The unit has 4 temperature inputs of PT100 type.
Three of them are used for the transformer
protection. The fourth input may be used as core
temperature protection or ambient temperature
monitoring.
Alarm and trip levels of the unit are independently
adjustable for first 3 sensors and the fourth
sensor input.
Alarm levels are adjusted using the program
mode. If no operation is performed, then the unit
will exit program mode in 3 minutes.
The unit offers a cable compensation function in
order to prevent long cables from impairing the
measurement precision.
The unit has 4 dry contact relay outputs rated 6A.
FAN: provides cooler fan control
TRIP: high temperature failure relay
ALARM: pre-alarm relay
FAULT: sensor or internal failure indicator
The unit offers an automatic self test feature. The
self test consists on the verification of sensor
inputs and internal memory integrity.
The standard isolated RS-485 MODBUS RTU
communication port is not affected by ground
potential differences and allows safe transfer of
information to remote management and
automation systems.
The supply input is isolated from sensor
connections.
1 degrees C measurement precision
4 x PT100 analog inputs
Allows cable length compensation
Automatic detection of sensor failures
Automatic and manual self test
4 x relay outputs, 5A/250Vac
Fully isolated RS-485 serial port
MODBUS-RTU communication
Recording of maximum temperatures
Front panel programmable
2 alarm thresholds for channels 1-2-3
2 alarm thresholds for channel 4
Easy to read, 3 digit 14mm led display
Supply voltage range: 19-400VDC (85-305VAC)
Reduced panel depth, easy to install
Wide operating temperature range, -20 to +70°C
Sealed front panel (IP65 with gasket)
2 part connection system
-1-
V-3.0
(14.09.2016)
FEATURES

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DPR-145 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Datakom DPR-145

  • Page 1 ▪ RS-485 MODBUS PORT ▪ UNIVERSAL SUPPLY DESCRIPTION FEATURES DPR-145 is a precision unit designed for the 1 degrees C measurement precision temperature protection of dry type or resin filled MV transformers. The unit offers a high degree of 4 x PT100 analog inputs protection against electromagnetic disturbances.
  • Page 2 DPR-145 User Manual V-3.0 (14.09.2016) SAFETY NOTICE WARNING Failure to follow below instructions may result in death or serious injury. • Electrical equipment should be installed only by qualified specialist. No responsibility is assumed by the manufacturer or any of its subsidiaries for any consequences resulting from the non-compliance to these instructions.
  • Page 3: Table Of Contents

    DPR-145 User Manual V-3.0 (14.09.2016) TABLE OF CONTENTS Section 1. INSTALLATION 1.1. FRONT / REAR PANELS 1.2. MECHANICAL INSTALLATION 1.3. ELECTRICAL INSTALLATION 2. PUSHBUTTON FUNCTIONS 3. DISPLAYS 3.1. MODES OF OPERATION 4. ALARMS 4.1. ALARM MENU 5. PROGRAMMING 5.1. ENTERING THE PROGRAM MODE 5.2.
  • Page 4: Installation

    DPR-145 User Manual V-3.0 (14.09.2016) 1. INSTALLATION Before installation: • Read the user manual carefully, determine the correct connection diagram. • Remove all connectors and mounting brackets from the unit, then pass the unit through the mounting opening. • Put mounting brackets and tighten. Do not tighten too much, this can brake the enclosure.
  • Page 5: Front / Rear Panels

    DPR-145 User Manual V-3.0 (14.09.2016) 1.1 FRONT / REAR PANELS 1.2 MECHANICAL INSTALLATION Panel Cutout Required Panel Depth...
  • Page 6: Electrical Installation

    DPR-145 User Manual V-3.0 (14.09.2016) 1.3 ELECTRICAL INSTALLATION Do not install the unit close to high electromagnetic noise emitting devices like contactors, high current busbars, switchmode power supplies and the like. Although the unit is protected against electromagnetic disturbance, excessive disturbance can affect the operation, measurement precision and data communication quality.
  • Page 7: Pushbutton Functions

    DPR-145 User Manual V-3.0 (14.09.2016) 2. PUSHBUTTON FUNCTIONS Programming and measuring screens are opened using 3 pushbuttons on the front panel. PUSHBUTTON FUNCTION Switched between operating modes. IF HELD PRESSED DURING 5 SEC: Switches to the Alarm menu. (Trip, Fault and Alarm...
  • Page 8: Displays

    DPR-145 User Manual V-3.0 (14.09.2016) 3. DISPLAYS Alarm Leds Selected Mod Leds Channel Leds Program Led Test Led SELECTED CHANNEL LEDS: indicates ALARM LEDS: indicates the type of the related channel to alarm or alarm if any. information on display.
  • Page 9: Alarms

    DPR-145 User Manual V-3.0 (14.09.2016) 4. ALARMS The unit continuously monitors various abnormal conditions during operation. Programmable alarm limits are provided for every measured value. If any fault condition occurs, the related alarm led (TRIP, FAULT or ALARM) turns on, alarm code is displayed, the alarm relay operates and the alarm code is added to the alarm menu.
  • Page 10: Alarm Menu

    DPR-145 User Manual V-3.0 (14.09.2016) 4.1 ALARM MENU PUSHBUTTON OPERATION DISPLAY In order to enter the Alarm menu, the MODE pushbutton should be held pressed during 5 seconds in SCAN, AUTO, MAN or MAX modes. The related channel led and the ALARM led of the last occurres alarm will turn on.
  • Page 11: Programming

    DPR-145 User Manual V-3.0 (14.09.2016) 5. PROGRAMMING 5.1 ENTERING THE PROGRAM MODE In order to provide the maximum flexibility of use, the unit features various programmable parameters. Parameters are recorded in a non-volatile memory and are not affected by power failures.
  • Page 12: Lamp Test

    DPR-145 User Manual V-3.0 (14.09.2016) 5.2 LAMP TEST When exiting the PROGRAM mode, the unit makes a LAMP TEST during 5 seconds. During LAMP TEST all leds will turn on. At the end of 5 seconds or if MODE button is depressed the LAMP TEST is terminated.
  • Page 13: Modifying Program Parameters

    DPR-145 User Manual V-3.0 (14.09.2016) 5.4 MODIFYING PROGRAM PARAMETERS TUŞ İŞLEM EKRAN The parameter to be modified is selected with MODE button. When the parameter name is on display, hold the MENU button pressed during 5 seconds. The parameter value will be displayed.
  • Page 14 DPR-145 User Manual V-3.0 (14.09.2016) DISPLAY DESCRIPTION FAULT RELAY TEST () Used to test the FAULT relay. The value of “1” activates the relay. The value of “0” deactivates it. ALARM RELAY TEST () Used to test the ALARM relay. The value of “1”...
  • Page 15 DPR-145 User Manual V-3.0 (14.09.2016) DISPLAY DESCRIPTION FAN OFF PARAMETER () Adjusts Fan Turn OFF Temperature. ALARM ENABLE PARAMETER () 0: No alarm is generated from this channel 1: if the temperature read from this channel is over Alx limit, then an alarm is generated.
  • Page 16: Modbus Communications

    DPR-145 User Manual V-3.0 (14.09.2016) 6. MODBUS COMMUNICATION 6.1 DESCRIPTION The unit offers serial data communication port allowing it to be integrated in automation systems. The serial port is of RS-485 MODBUS-RTU standard. It is fully isolated from power supply and measurement terminals for failure-free operation under harsh industrial conditions.
  • Page 17: Program Parameters

    DPR-145 User Manual V-3.0 (14.09.2016) 6.2 PROGRAM PARAMETERS 12 parameters are available in total. Parameter values may be modified with Function 10 (Write Multiple Registers). All values should be sent at once. ADDRESS NAME DESCRIPTION LENGTH TYPE unsigned Channel 1 Alarm temperature (°C)
  • Page 18: Commands

    DPR-145 User Manual V-3.0 (14.09.2016) 6.3 COMMANDS Commands should be sent with Function 6 (Write Single Register). ADDRESS VALUE DESCRIPTION 16384 Reset Maximum Temperatures 16385 Reset all Alarms 16386 Arrow Down pushbutton 16387 Arrow Up pushbutton 16388 MODE pushbutton 16389...
  • Page 19: Sensor Data

    -20°C to +70 °C (-4°F to 158°F) 2014/35/EC (LVD) Standards: Max Relative Humidity: 2014/30/EC (EMC) EN 61010 (safety) 95% non condensing EN 61326 (EMC) DATAKOM Elektronics Inc. Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: datakom@datakom.com.tr http: www.datakom.com.tr -19-...

Table of Contents