Download Print this page

Advertisement

Quick Links

Product Name:
Model No.:
Issue Date
:
1. The product shall be installed by a professional electrician. Please disconnect
the power before installation, wiring or changing the setting of by DIP switch
2. Please read the relevant contents of this manual carefully before using the
product.
3. This product is only suitable for indoor environment.
4. Ensure that the product is installed in a relatively dry and ventilated
environment.
5. Before the product is powered on, please confirm that the input voltage range
meets the requirements of the manual.
6. Keep out of reach of children.
LIFEBEING SENSOR
INSTRUCTIO
LifeBeing sensor (RS485 Protocol)
MSA043D 485
2021-07-01
Attention
page 1 of 12
MSA043D 48
5
N
Version: A0

Advertisement

loading

Summary of Contents for HDL LifeBeing MSA043D 485

  • Page 1 LIFEBEING SENSOR MSA043D 48 Version: A0 INSTRUCTIO Product Name: LifeBeing sensor (RS485 Protocol) Model No.: MSA043D 485 Issue Date 2021-07-01 Attention 1. The product shall be installed by a professional electrician. Please disconnect the power before installation, wiring or changing the setting of by DIP switch 2.
  • Page 2 LIFEBEING SENSOR MSA043D 485 Version: A0 1. Features This is a RS485 protocol sensor of independently flush mounting(compatible with 86 type box). The sensor, controlling and exchanging data through RS485 protocol, has functions of big motion, minor motion, breathing detecting+light sensing and so on. Adopting 5.8GHz RS, high gain low impedance technology, MSA043D is achieving presence detecting as its big advantage.
  • Page 3 LIFEBEING SENSOR MSA043D 485 Version: A0 3. Function Adopting fixed 30S cyclically reporting mechanism, the product, transmits human condition information(no human-existing/human-existing:big motion mode, minor motion mode, breathing mode) and illumination data through RS485 communication protocol. Big motion actives Minor motion& Breathing signal maintains Detecting the signals of human greatly moving (walking) in detecting area within 30S.
  • Page 4 LIFEBEING SENSOR MSA043D 485 Version: A0 Standard Communication Command Function Table DATA3 Writing& Function Name Data Range Default Value comman Reading 0x03 Work state 0x05 Detection area 0-100 100% 0x06 Application scenarios 0x07 Block Sensor 32bit 0x08 LED Indicator 0x09 Light sensor 0-1200Lux 0x0A...
  • Page 5 LIFEBEING SENSOR MSA043D 485 Version: A0 2. Work State: this function automatically reports the working status of the sensor Values HEAD Function Value (DATA1-D (DAT Function (DATA0) (DATA4) (DATA5) (DATA6) ATA2) No human-existing 0x51 0xFFFF 0x06 0x03 0x01 data0+...+data5 Big motion 0x51 0xFFFF 0x06...
  • Page 6 LIFEBEING SENSOR MSA043D 485 Version: A0 5. Time of Blocking Sensor: block sensor, this function can make the sensor lock to not output any state and mode, the minimum lock time unit is 1ms, and the sensor will automatically output after the lock time countdown is completed.
  • Page 7 LIFEBEING SENSOR MSA043D 485 Version: A0 9.Hold Time: this function can set the hold time of turning on the light after the sensor is triggered. Value Value HEAD Function (DATA1-D (DAT (DATA5-DAT Function (DATA0) (DATA4) (DATA7) ATA2) Min: 2s 0x51 0xFFFF 0x07 0x0D...
  • Page 8: Dimension (Unit: Mm)

    LIFEBEING SENSOR MSA043D 485 Version: A0 Note 1. The default compensation factor is 1 times. For different installation environments, set the corresponding compensation factor after verifying and calibrating with the illuminance meter. 2. Return 000005FF01XX, If there is no above features or command is issued incorrectly. 3.
  • Page 9 LIFEBEING SENSOR MSA043D 485 Version: A0 7. Structure Note: Long press the switch for 3S to reset, and the product enters the initialization state. 8. Detecting Area Note: 1. Considered the features of electromagnetic wave transmitting, the effective range of radar will vary to some extent as the radar is related to size of transmitter and material and thickness of the target cover.
  • Page 10: Installation Instruction

    LIFEBEING SENSOR MSA043D 485 Version: A0 9. Installation Instruction 1) Flush mounting 1. Ceiling mounting with a cut of 55-65mm 2. Connect wire on the terminal 3. The middle circle is the reset button 4. Bending the spring clip backward to push it into the pre-opened hole in the ceiling 5.
  • Page 11: Remote Control

    LIFEBEING SENSOR MSA043D 485 Version: A0 10. Remote Control 11. Initialization After first power on, the indicator light will be off after flashing for 20 seconds. During the initialization, sensor is not able to detect moving objects signal. Turn on or off indicator and set the detecting area through serial protocol.
  • Page 12 LIFEBEING SENSOR MSA043D 485 Version: A0 4) Avoid the detection window of the daylight sensor of the detector irradiated by an invalid light source, which will interfere with the measurement of ambient light. 5) The product should not be too close to the wireless router at least more than 2m apart, when it is installed and used.