Mitsubishi Electric SUZ-KA09NA2 Service Manual page 22

Split-type, heat pump air conditioners hfc utilized r410a, outdoor unit
Table of Contents

Advertisement

I Check of outdoor fan motor
Check the connection between the
connector CN931 and CN932.
Disconnect the connectors CN931
and CN932 from the inverter P.C.
board.
Is the resistance between each ter-
minal of outdoor fan motor normal?
(Refer to 10-4.)
No
(Fixed to either 5 or 0 VDC)
Replace the outdoor fan motor.
OCH699A
Yes
Disconnect CN932 from the inverter P.C. board, and turn on the
power supply.
Rotate the outdoor fan motor manually and measure the voltage
of CN931.
Between 1(+) and 5(-)
Between 2(+) and 5(-)
Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0
No
VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
No
Replace the inverter P.C. board.
22