Designed Lifetime; Certification - Honeywell Krom Schroeder VAN Series Operating Instructions Manual

Magnetic relief valve
Table of Contents

Advertisement

Switching frequency of closed position indicator: max.
5 x per minute.
switching
current
cos φ = 1
0.1
0.5
1
3
* Limited to max. 200,000 cycles for heating systems.
9.4 Air flow rate Q
Air flow rate Q for a pressure loss of Δp = 1 mbar
(0.4 "WC):
∆p = 1 mbar (0,4 "WC)
Q [m
VAN 110
VAN 115
VAN 120
VAN 125
VAN 225
VAN 232
VAN 240
VAN 250

10 DesIGneD LIFetIMe

This information on the designed lifetime is based on
using the product in accordance with these operat-
ing instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture) in
accordance with EN 13611, EN 161 for VAN:
type
switching
VAN 110 – 225
VAN 232 – 250
You can find further explanations in the applicable
rules and regulations and on the afecor website (www.
afecor.org).
This procedure applies to heating systems. For ther-
moprocessing equipment, observe local regulations.
switching cycles*
cos φ = 0.6
500,000
500,000
300,000
250,000
200,000
100,000
100,000
Air flow rate
3
/h]
Q [sCFH]
4.4
155.4
5.6
197.7
8.3
293.1
10
353.1
15.5
547.3
19.5
688.5
21
741.5
22.5
794.5
Designed lifetime
time (years)
cycles
500,000
10
200,000
10

11 CeRtIFICAtIon

11.1 Declaration of conformity
We, the manufacturer, hereby declare that the products
VAN with product ID No. CE-0063BU1564 comply with
the requirements of the listed Directives and Standards.
Directives:
– 2014/35/EU – LVD
– 2014/30/EU – EMC
– 2011/65/EU – RoHS II
– 2015/863/EU – RoHS III
Regulation:
– (EU) 2016/426 – GAR
Standards:
– EN 161:2011+A3:2013
The relevant product corresponds to the tested type
sample.
The production is subject to the surveillance proce-
dure pursuant to Regulation (EU) 2016/426 Annex III
paragraph 3.
Elster GmbH
Scan of the Declaration of conformity (D, GB) – see
www.docuthek.com
AGA approved
Australian Gas Association
eurasian Customs Union
The product VAN meets the technical specifications
of the Eurasian Customs Union.
11.2 UKCA certified
Gas Appliances (Product Safety and Metrology etc.
(Amendment etc.) (EU Exit) Regulations 2019)
BS EN 161:2011+A3:2013
11.3 ReACH Regulation
The device contains substances of very high concern
which are listed in the Candidate List of the European
REACH Regulation No. 1907/2006. See Reach list
HTS at www.docuthek.com.
11.4 China RoHs
Directive on the restriction of the use of hazardous sub-
stances (RoHS) in China. Scan of the Disclosure Table
China RoHS2, see certificates at www.docuthek.com.