KE2 Compressor Sequencer
Quick Start Guide
Setpoints - Continued
Setpoint
DIg IN 1, 2, 3 mODE
DIg IN 1, 2, 3 STATE
Aux TEmP OFFSET
SuCT PRESSuRE OFFSET
SuCT TEmP OFFSET
DISCH TEmP OFFSET
DISCH PRESS OFFSET
mAx DISCH PRES
mIN SuCTION SH
mAx SuCTION SH
mIN/mAx SH DELAy
mAx DISCH TEmP
mAx DISCH TEmP
DELAy
mAx DIS PRS DELAy

Manual Menu

Name
mANuAL CONTROL
CLEAR ALARmS
FACTORy RESET
WEB PASSWORD RESET
KE2 SmART ACCESS mODE
DHCP mODE
© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Description
Sets the function of the Digital Input
Sets whether the switch activates with Open or Closed Open / Closed
An offset added or subtracted from the auxiliary tem-
perature sensor reading, if needed
An offset added or subtracted from the suction line
pressure transducer reading, if needed
An offset added or subtracted from the suction tem-
perature sensor reading, if needed
The offset added or subtracted from the discharge
temperature sensor reading, if needed
An offset added or subtracted from the discharge
pressure transducer reading, if needed
Turns system of when exceeded
The lowest acceptable superheat. Turns system off
when exceeded
The highest acceptable superheat
The amount of time, in minutes, before an alarm is
initiated when the minimum or maximum superheat
setting is surpassed.
The maximum discharge temperature before an alarm
is initiated. Turns off system when exceeded.
The amount of time, in minutes, before an alarm is
initiated when the Maximum Discharge Temperature
setting is surpassed.
The amount of time, in minutes, before an alarm is
initiated when the Maximum Discharge Pressure set-
ting is surpassed.
Description
Clear all active alarms
Reset the controller to the factory default setpoints
Reset the web password to the factory default
Turn KE2 Smart Access on or off
Turn DHCP mode on or off
Range / Options
HG Defr Req, 2nd Pres, Comp Mod, Oil Safety
Sw, Hi Pres Switch, Sys Off
-5 to 5 Fº / -2.8 to 2.8K
-5 to 5 Fº / -2.8 to 2.8K
-5 to 5 Fº / -2.8 to 2.8K
-5 to 5 Fº / -2.8 to 2.8K
-5 to 5 Fº / -2.8 to 2.8K
100 to 500 psig
5 to 50 ºF / 2.8 to 27.8K
25 to 200 ºF / 13.9 to 111.1K
0 to 254 minutes
25 to 300ºF /-3.9 to 148.9 ºC
0 to 254 minutes
0 to 254 minutes
Range
Reset
Reset
Disable, Enable
Disable, Enable
Default
Disabled
Closed
0 Fº/K
0 Fº/K
0 Fº/K
0 ºF/K
0 ºF/K
450 psig
15 ºF / 8.3K
50 ºF / 27.8K
Disabled
268
ºF/131.1ºC
Disabled
Disabled
Default
Disable
Disable