KE2 Compressor Sequencer OEM
Quick Start Guide
This reference should remain on site with the installed KE2 Compressor Sequencer

Product Summary:

Pg. 1
The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc-
tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups.
Pg. 1
Pg. 2
For dual suction groups, the controller is applicable to both racks with a shared common dis-
charge, or independent discharge lines. Suction pressure can be controlled to either a fixed
setpoint, or a floating suction pressure for maximum efficiency.
Pg. 3
Each stage of loading can be set to: fixed speed compressor, variable speed compressor
Pg. 4
① ②
tal compressor
Pg. 5
a Master Liquid Line Solenoid, or as a Hot Gas Defrost Relay.
Communication:
As is standard with many other KE2 Therm controllers, the KE2 Compressor Sequencer OEM has
the simplest and easiest communication platform in the industry. The controller uses standard
communication protocols and cables; no extra software is necessary, only an Ethernet connec-
tion to the controller. E-mail and/or text alerts can be sent out right from the controller. Com-
plete remote access is available during startup with one simple button press and an Internet
connection.
Pg. 14
Pg. 15
One per Suction Group
Pg. 16 - 18
Controller is designed to operate with a Copeland Scroll Digital Compressor, when Digital Compressor is selected.
Part Numbers
Pg. 18-19
Pg. 20
Part Number Description
KE2 Compressor Sequencer OEM
21768
Pg. 21
Aux Relay Board
Pg. 21
21323
Pg. 22 - 23
External Relays
21304
21032
Pressure Transducers
Pg. 24 - 25
20201③
20204③
20202
Pg. 26 - 27
20712
Pg. 28
Temperature Sensors
Pg. 29 - 37
21230
20199
20200
Replacement Relays
21374
Replacement Fuses
21375
21628
Pg. 38 - 40
Use transducers 20208 (10 ft.) or 20711 (40 ft.) for R-410A. Use 20202 (10 ft.) or 20712 (40 ft.) for R-744.
or unloaders. The relays for the stages can alternatively be used to control
- Controllers & Accessories
Controller only
Auxiliary Relay Board
Solid State Relay - Used to control digital compressor bypass valve
Used to pilot contactor for 5th compressor stage, control master liquid line
solenoid, hot gas solenoid or unloader valve with Aux Relay Board Relay #5.
Pressure Transducer 0 to 150 psia, 10 ft. lead - for suction pressure.
Pressure Transducer 0 to 150 psia, 40 ft. lead - for suction pressure.
Pressure Transducer 0 to 500 psig, 10 ft. lead - for discharge pressure.
Pressure Transducer 0 to 500 psig, 40 ft. lead - for discharge pressure.
High temp sensor for discharge at condenser inlet, 15 ft.
Standard temp sensor for all other temp inputs, 10 ft. (black)
Standard temp sensor for all other temp inputs, 40 ft. (black)
Replacement Form C Relay for Main Board
Replacement incoming power fuse for Main Board and Aux Relay Board
Replacement fuses for Aux Relay Board relays (5 pack)
Q.2.60
March 2019
pn 21768
, digi-

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Compressor Sequencer OEM and is the answer not in the manual?

Questions and answers

Summary of Contents for KE2 Compressor Sequencer OEM

  • Page 1: Table Of Contents

    Product Summary Pg. 1 The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc- tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups. Part Numbers - Controllers & Accessories Pg.
  • Page 2: Dimensions & Specifications - Main Board

    ① Digital Compressor Bypass Valve control requires PN 21304. -60°F to 150°F (-51°C to 65°C) ② Controller is designed to operate with Copeland Scroll Digital Compressor. ③ Requires KE2 Edge Manager PN 21634. Not available at release. High Temperature Sensor pn 21230 (15ft.) Operating Range: -40°F to 302°F (-40°C to 150°C)
  • Page 3: Dimensions & Specifications Auxiliary Relay Board

    KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group) Dual Suction / Independent Discharge KE2 Compressor Sequence OEM + 2 Aux Relay Boards (up to 5 stages per suction group) *Relays can also be used as a master liquid line solenoid valve relay and/or hot gas bypass relay.
  • Page 4: Setup Options

    Quick Start Guide Setup Options Option 1: Option 4: KE2 Compressor Sequencer OEM KE2 Compressor Sequencer OEM + 2 Aux Relay Boards Dual Suction Groups w. Common Discharge Single Suction Group w. Common Discharge Oil Line Oil Line To Condenser...
  • Page 5: Single Suction Group W. Common Discharge

    Black Discharge Pressure Transducer Shared Red Black Suction Pressure Transducer Green B – Ethernet Port Display (RJ-11) (RJ45) for remote communications * Use only chassis ground or spade connector ground © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 6: Main Board + 1 Aux Relay Board Single Suction Group W. Common Discharge

    Ethernet Port Display (RJ-11) (RJ45) for remote communications * Use only chassis ground or spade connector ground **Function Options are the same as list shown for the Main Board Aux Inputs. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 7 Not Used 0 - 10V INPUT 2 - Variable Speed (OV - 10V) - or - (0V to 5V) - Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304 © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 8: Main Board + 2 Aux Relay Boards Single Suction Group W. Common Discharge

    Ethernet Port Display (RJ-11) (RJ45) for remote communications * Use only chassis ground or spade connector ground **Function Options are the same as list shown for the Main Board Aux Inputs. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 9 **AUX 2 0 - 10V INPUT 2 - Variable Speed (OV - 10V) - or - (0V to 5V) - Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304 © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 10: Dual Suction Groups W. Common Discharge

    Ethernet Port Display (RJ-11) (RJ45) for remote communications * Use only chassis ground or spade connector ground **Function Options are the same as list shown for the Main Board Aux Inputs. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 11 - Variable Speed (OV - 10V) - or - (0V to 5V) AUX 2 - Digital Compressor Bypass Valve (OV/10V) requires Solid State Relay pn 21304 INPUT 2 Group 2 © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 12 Ethernet Port Display (RJ-11) (RJ45) for remote communications * Use only chassis ground or spade connector ground **Function Options are the same as list shown for the Main Board Aux Inputs. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 13 AUX 2 - Variable Speed (OV - 10V) - or - (0V to 5V) INPUT 2 - Digital Compressor Bypass Valve (OV/10V requires Solid State Relay pn 21304 Group 2 © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 14: Communication Setup Options

    SA (KE2 Smart Access). The controller is asking if remote access The remainder of the setup is done via the browser interface. There through KE2 Smart Access will be used. It will then blink diS (dis- are many ways to connect to the controller, in addition to KE2 Smart abled).
  • Page 15: Setting Up Groups

    ❻ Under Compressor Configuration, select the correct application from the list: ❻ ❺ ❼ ❼ Select the correct setup for the application and number of Aux Relay Boards, ❽ then click Save. ❽ © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 16: Designating Relay Functions

    ❸ Once saved, Comp HP will appear below any ❶ ❸ relays selected as a compressor. Enter the correct horsepower for each compressor, then click the Save button again. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 17: Single Group Or Dual Group +Aux Boards

    From the Home Page click on the icon for the Aux Board: ❶ ❷ ❸ ❷ On the Aux Relay interface, Drivers (relays) are listed to the left. ❸ Inputs are listed to the right. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 18: Running The System

    Setpoint). Clicking this button again will put the system back into System Off. When the KE2 Compressor Sequencer OEM is started for the first time, or anytime a critical setpoint is changed, the controller enters Note: When two suction groups are used, there will be two Setpoints System Off mode.
  • Page 19 The suction group will now be in System Off, or running, depending ured for Single Group. SY1 and SY2 indicate their respective groups on what was selected. when configured for Dual Group. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 20: Determining Compresor On/Off Order

    Min Speed setpoint ① The KE2 Compressor Sequencer OEM has the ability to float the tar- get suction pressure for maximum efficiency. When the Fixed/Float Suction setpoint is set to Float Suction, all Room Temperature sen- sors connected to a group will be compared to the Room Temp set- ①...
  • Page 21: Selectable Inputs

    Sys Off Off mode. In System Off mode, no relays will be energized, and a user must manually take the group (System Off) out of System Off mode to resume operation. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 22 Abbrev. Full Name Default Description Turn KE2 Smart Access on or off: EnA to enable / diS to KE2 SMART ACCESS disable KE2 Smart Access. Turn DHCP mode on or off: EnA to enable / diS to disable DHCP mODe DHCP mode.
  • Page 23: Remote Display

    Abbrev. Full Name Default Description Turn KE2 Smart Access on or off: EnA to enable / diS to disable KE2 SMART ACCESS KE2 Smart Access. Turn DHCP mode on or off: EnA to enable / diS to disable DHCP DHCP mODe mode.
  • Page 24 High Int Comp Temp [Group 2] Alarm compressor until temp lowers. Group 2 discharge pressure is higher than Max Disch Pres for longer ▪ High Disch Pres [Group 2] Alarm than Max Dis Prs Del. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 25: Alarms

    Group 2 discharge pressure is above Max Safety Pressure. Control- High Safety Disch Pres 2 [Group 2] ler will attempt to unload stages and not load anymore stages until Alarm pressure is well below Max Safety Pressure. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 26: Webpage Setpoints - Main Board

    Q.2.60 March 2019 Page 26 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Webpage Setpoints - Main Board The following setpoints are available on the broswer interface of the Main Board. Setpoint Description Range / Options Default Disabled, Fixed Speed, Variable Speed ①...
  • Page 27 PROPORTIONAl CMP 0 to 255 INTEgRAl CMP 0 to 255 Should not be adjusted unless instructed to by KE2 Therm technical support. DERIVATIVE CMP 0 to 255 PID TIME CMP 0 second to 255 seconds 1 second Minimum Safety Suction Superheat.
  • Page 28: Webpage Setpoints - Auxiliary Relay Boards

    ② In dual suction group applications, Input 2 on Aux Relay Board 2 acts as suction temperature sensor for group 2. ③ In dual suction group applications with independent discharge, Input 2 on Aux Relay Board 1 acts as discharge temperature sensor for group 2. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 29: Webpage Screen Shots

    Q.2.60 March 2019 Page 29 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Home Page © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 30: Status Page - Main Board

    Q.2.60 March 2019 Page 30 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Status Page - Main Board © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 31 Q.2.60 March 2019 Page 31 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Status Page- Auxiliary Board © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 32: Settings Page

    Q.2.60 March 2019 Page 32 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Settings Page © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 33: Login Page

    Q.2.60 March 2019 Page 33 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Login Page © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 34: Network Page

    Q.2.60 March 2019 Page 34 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Network Page © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 35 Q.2.60 March 2019 Page 35 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Setpoints Page - Single Group - Main Board Only © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 36: Setpoints Page - Main Board + Aux Relay Board(S)

    Q.2.60 March 2019 Page 36 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Setpoints Page - Main Board + Aux Relay Board(s) © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 37: Graphs Page

    Q.2.60 March 2019 Page 37 KE2 Compressor Sequencer OEM pn 21768 Quick Start Guide Graphs Page © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 38: Alphabetical List Of Abbreviations

    Main Board, Aux Input 3 Sensor is shorted or open. 1] Alarm Aux Addr 1: Input 2 Sensor [Group Alarm - Cautionary Aux Board 1, Input 2 Sensor is shorted or open. 1] or [Group 2] Alarm © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 39 Controller will attempt to unload stages and not load High Safety Disch Pres 1 [Group 1] Alarms - Safety / Preemptive anymore stages until pressure is well below Max Safety Pressure. © Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090...
  • Page 40 Max Safety Alarm Pressure. Setpoints - Single Group Turn KE2 Smart Access on or off: EnA to enable / diS to dis- KE2 Smart Access Setpoint - Dual Group able KE2 Smart Access.