Contents:
Dual Suction Groups w. Independant Disch. Pg. 12-13
▪ Fixed Suction Pressure w. Digital Scroll or Variable
▪ Fixed Suction Pressure w. Fixed Speed Compressors
▪ Floating Suction Pressure
▪ Variables Menu - Single Group
▪ Setpoints Menu - Single Group
▪ Critical & Cautionary Alarms - ALL Groups
▪ Safety Alarms - ALL Groups
▪ Status Page - Aux Relay Board
▪ Setpoints Page - Main Board Only
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 Compressor Sequencer OEM
Quick Start Guide
This reference should remain on site with the installed KE2 Compressor Sequencer
Product Summary:
Pg. 1
The KE2 Compressor Sequencer OEM allows control of up to 8 stages of loading for a single suc-
tion group, or up to 10 stages of loading (5 per suction group) for dual suction groups.
Pg. 1
Pg. 2
For dual suction groups, the controller is applicable to both racks with a shared common dis-
charge, or independent discharge lines. Suction pressure can be controlled to either a fixed
setpoint, or a floating suction pressure for maximum efficiency.
Pg. 3
Each stage of loading can be set to: fixed speed compressor, variable speed compressor
Pg. 4
① ②
tal compressor
Pg. 5
a Master Liquid Line Solenoid, or as a Hot Gas Defrost Relay.
Communication:
As is standard with many other KE2 Therm controllers, the KE2 Compressor Sequencer OEM has
the simplest and easiest communication platform in the industry. The controller uses standard
communication protocols and cables; no extra software is necessary, only an Ethernet connec-
tion to the controller. E-mail and/or text alerts can be sent out right from the controller. Com-
plete remote access is available during startup with one simple button press and an Internet
connection.
Pg. 14
Pg. 15
①
One per Suction Group
②
Pg. 16 - 18
Controller is designed to operate with a Copeland Scroll Digital Compressor, when Digital Compressor is selected.
Part Numbers
Pg. 18-19
Pg. 20
Part Number Description
KE2 Compressor Sequencer OEM
21768
Pg. 21
Aux Relay Board
Pg. 21
21323
Pg. 22 - 23
External Relays
21304
21032
Pressure Transducers
Pg. 24 - 25
20201③
20204③
20202
Pg. 26 - 27
20712
Pg. 28
Temperature Sensors
Pg. 29 - 37
21230
20199
20200
Replacement Relays
21374
Replacement Fuses
21375
21628
Pg. 38 - 40
③
Use transducers 20208 (10 ft.) or 20711 (40 ft.) for R-410A. Use 20202 (10 ft.) or 20712 (40 ft.) for R-744.
or unloaders. The relays for the stages can alternatively be used to control
- Controllers & Accessories
Controller only
Auxiliary Relay Board
Solid State Relay - Used to control digital compressor bypass valve
Used to pilot contactor for 5th compressor stage, control master liquid line
solenoid, hot gas solenoid or unloader valve with Aux Relay Board Relay #5.
Pressure Transducer 0 to 150 psia, 10 ft. lead - for suction pressure.
Pressure Transducer 0 to 150 psia, 40 ft. lead - for suction pressure.
Pressure Transducer 0 to 500 psig, 10 ft. lead - for discharge pressure.
Pressure Transducer 0 to 500 psig, 40 ft. lead - for discharge pressure.
High temp sensor for discharge at condenser inlet, 15 ft.
Standard temp sensor for all other temp inputs, 10 ft. (black)
Standard temp sensor for all other temp inputs, 40 ft. (black)
Replacement Form C Relay for Main Board
Replacement incoming power fuse for Main Board and Aux Relay Board
Replacement fuses for Aux Relay Board relays (5 pack)
Q.2.60
March 2019
pn 21768
①
, digi-
Need help?
Do you have a question about the Compressor Sequencer OEM and is the answer not in the manual?