Advertisement

Quick Links

LEMX - Installation Guide
- Read and follow all safety instructions.
- Disconnect power before performing work on electrical
equipment.
- Do not use outdoors.
- Do not let power cords touch hot surfaces.
- Do not install in hazardous locations or near gas or electric
heaters.
- The use of accessory equipment not recommended by
manufacturer, may cause an unsafe condition and will void the unit's
warranty.
Battery in this unit may not be fully charged at the time electrical connection is made. Let battery charge for at least 24 hours.
Then normal operation of this unit should take effect. To check, press the "TEST" button, the lamps of the unit should turn on.
1. During an electrical power failure, the lamps will automatically
come ON for a minimum of 90 minutes.

J-Box Mount: LEMX-L2

1. Feed fixture leads through main bottom case and
connect AC power supply (Fig. A).
2. Connect wires through the J-Box. Place bottom of case
on J-Box and secure with screws.
3. Connect batty only when AC power can be provided to
the unit (Fig. B).
4. Align snaps and push housing directly onto main
bottom case (Fig. C) and apply continuous AC power.
Press TEST button to verify.
1, 2. Fig. A
|
Headquarters: 4615 State Street, Montclair, CA 91763
|
Production Center: 7345 Syncamore Canyon Blvd, Riverside, CA 92508
Please read all the instructions before attempting installation

Operations

Unused wires must be capped using using enclosed wire nuts.
3. Fig. B
- Do not use this equipment for other than its intended purpose.
- Servicing of this equipment should be performed by qualified
service personnel.
- Equipment should be mounted in locations and at heights where
it will not readily be subjected to tampering by unauthorized
personnel.
- Allow battery to charge for 24 hours before first use.
- CAUTION - RISK OF FIRE
2. To test, press the TEST button and the emergency lamps will
illuminate. When the switch is released, the lamps will turn OFF.

Conduit

1. Secure main bottom case to wall surface. Route
wires through hole in conduit flange and make conduit
connection.
2. Connect battery only when continuous AC power can
be provided to the unit (Fig. B).
3. Align snaps and push housing directly onto main
bottom case (Fig. C) and apply continuous AC power.
Press TEST button to verify.
Plugin
4. Fig. C
archipelagolighting.com
+1(866) 912-3220

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LEMX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ARCHIPELAGO LIGHTING LEMX

  • Page 1 LEMX - Installation Guide Please read all the instructions before attempting installation - Read and follow all safety instructions. - Do not use this equipment for other than its intended purpose. - Disconnect power before performing work on electrical - Servicing of this equipment should be performed by qualified equipment.
  • Page 2 LEMX - Installation Guide 1. Fig. A 2. Fig. B LED Lamp Heads: LEMX-L2Sx 1. Remove the face cover by gently prying it open with a flat screwdriver. 2. Pass the wires through the mounting holes on the housing. Insert lamp heads into housing and twist them to lock firmly.
  • Page 3 LEMX - Installation Guide 1, 2, 3. Ceiling Mount: LEMX-L2Sx 1. Using a flat screwdriver, remove the front cover, remove and discard the canopy kit. 2. Feed excess wires into the junction box. 3. The system can accept input voltages of 120 VAC or 277 VAC.
  • Page 4 LEMX - Installation Guide 1. Fig. A 2, 3, 4. Fig. B Wall Mount: LEMX-Sx 1. Knock out the proper hole pattern in the back plate to mount to a standard junction box. Place a support on either side of the knockouts to be removed and then knock out with a screwdriver (Fig.
  • Page 5 LEMX - Installation Guide Side Mount: LEMX-Sx 1. Using a flat screwdriver, open the front cover, remove and discard the canopy kit. 2. Feed excess wires into the junction box. 2, 3. 3. The system can accept input voltages of 120 VAC or 277 VAC.

Table of Contents