INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: GY8S / GM8S / LY8S / LM8S / LF8
(Single Stage Upflow / Horizontal / LoNOx)
40 - 130 MBH INPUT
(11.72 - 38.10 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Furnace Base Rectangular Perforated Panel . . . . . . . . . . . . . . . . . . . 6
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Suspended Furnace / Crawl Space Installation . . . . . . . . . . . . 7
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Line Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Heating and Cooling Thermostat Connections . . . . . . . . . . . . . . . . . 11
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . . 11
Single Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . 12
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 4
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
High Altitude Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data - Upflow Models . . . . . . . . . . . . 10
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.

TABLE OF CONTENTS

TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .19
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
LIST OF FIGURES
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Typical Sidewall Vent Application . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .16
Typical Chimney Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Horizontal Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . .17
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .17
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Typical Heat/Cool Speed Tap Connections . . . . . . . . . . . . . . . . . . . .22
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
LIST OF TABLES
Horizontal Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .17
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
035-20464-002 Rev. A (1004)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GY8S and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group GY8S

  • Page 1: Table Of Contents

    HIGH EFFICIENCY EFFICIENCY RATING TUBULAR HEAT EXCHANGER SERIES CERTIFIED MODELS: GY8S / GM8S / LY8S / LM8S / LF8 (Single Stage Upflow / Horizontal / LoNOx) This product was manufactured in a plant whose quality system is certified/registered as being 40 - 130 MBH INPUT in conformity with ISO 9001.
  • Page 2: Safety

    When outdoor air is used for combustion, the combustion air intake duct system termination must be located external to the building and in an area where there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3: Ductwork

    Protection Association) as outlined in NFPA pamphlets 90A and tioned space. 90B (latest editions) or applicable national, provincial, or state, and local fire and safety codes. Unitary Products Group...
  • Page 4: Round Duct Size

    7 (18) 38.4 (248) drop across the return air filter. 8 (20) 50.2 (324) 9 (23) 63.6 (410) 10 (25) 78.5 (506) 11 (28) 95 (613) 12 (30) 113.1 (730) 13 (33) 132.7 (856) 14 (36) 153.9 (993) Unitary Products Group...
  • Page 5 3 3/4 115/92 (33.70/26.96) 2000 (56.63) 53.3 19 3/4 50.2 16 5/8 42.2 10.2 13 3/8 3 3/4 130/104 (38.09/30.48) 2000 (56.63) 24 1/2 62.2 23 1/4 59.1 20 1/8 51.1 10.2 15 1/8 27.6 3 3/4 Unitary Products Group...
  • Page 6 The sheet metal should be crosshatched to eliminate any popping of FIGURE 3: Typical Attic Installation the sheet metal when the indoor fan is energized. Unitary Products Group...
  • Page 7: Filters

    If a filter(s) is provided at another location in the return air system, the ductwork may be directly attached to the furnace side All installations must have a filter installed. panel. An accessory filter rack is available for mounting the filter exter- nal to the cabinet. Unitary Products Group...
  • Page 8: Gas Piping

    See propane nector. Do not use a connector that has previously serviced another gas instructions 035-14445-000 or the start up procedure at the back of appliance. these instructions on proper removal of the NOx screens. Unitary Products Group...
  • Page 9: Electrical Power

    Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures. Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes. The furnace shall be installed so that the electrical components are protected from water. Unitary Products Group...
  • Page 10: Accessory Connections

    The terminals provide 115 mostat wiring to connect the Y and C terminals on the furnace control VAC (1.0 amp maximum) during heating system operation. board to the proper wires on the condensing unit (unit outside). Refer to Figure 7. Unitary Products Group...
  • Page 11 If a mixing device is not furnace blower. used, any ducts that are connected down stream from the furnace that operates on W2, will be supplying cold air in the Heating mode to the Unitary Products Group...
  • Page 12 The twinning func- TO A/C tion of this board ensures that both blowers turn on and off simulta- WALL THERMOSTAT neously, and operate on the same blower speed. Even when only one FIGURE 15: Two-Stage Twinning Wiring Diagram Unitary Products Group...
  • Page 13: Vent Termination

    Over 20/12 to 21/12 2.44 tance of ten feet. The chimney must extend at least 5 ft (1.5 m) above the highest equipment draft hood or flue collar. Unitary Products Group...
  • Page 14: Typical Sidewall Vent Application

    23.45 2000 56.63 10.16 1.37 34.5 10.82 115,000 33.70 92,000 26.96 1600 45.31 10.16 1.37 34.5 10.82 115,000 33.70 92,000 26.96 2000 56.63 10.16 1.37 34.5 10.82 130,000 38.10 104,000 30.48 2000 56.63 10.16 1.37 34.5 10.82 Unitary Products Group...
  • Page 15: Home Layout

    Termination should be located where it will not be affected by wind gusts, light snow, airborne leaves or allow recirculation of flue An appliance equipped with an integral mechanical means to either gases. draw or force products of combustion through the combustion chamber and/or heat exchanger. Unitary Products Group...
  • Page 16: Combustion Airflow Path Through The Furnace Casing To The Burner

    CHIMNEY OR GAS VENT VENTILATION LOUVERS (each end of attic) OPENING OUTLET INLET ALTERNATE OPENING AIR INLET FIGURE 24: Typical Chimney Connections VENTILATION LOUVERS FOR UNHEATED CRAWL SPACE FIGURE 22: Alternate Air Intake, Air Outlet and Chimney Connections Unitary Products Group...
  • Page 17: Free Area

    4. The blocking effects of louvers, grilles and screens must be given INLET AIR (b) consideration in calculating free area. If the free area of a specific AIR (a) louver aor grille is not known. FIGURE 26: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 18: Safety Controls

    The operation of this control indicates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. These are manual reset controls that must be reset before operation can continue. Unitary Products Group...
  • Page 19: Pressure Switch Tubing Routing

    • 2 – pieces of 4” (10 cm) length x 1/8” (0.3 cm) diameter tubing • 1 - 5/16” (0.8 cm) tee • 1 – 5/16” (0.8 cm) x 1/8” (3.175 mm) reducing coupling • 1 – 1/8” (0.3 cm) adapter Unitary Products Group...
  • Page 20 For altitudes above 2,000 ft. (610 m) the furnace input MUST BE DERATED. Refer to the GAS CONVERSION FOR PROPANE (LP) AND HIGH ALTITUDES IN SECTION IV for information on high altitude conversions. Unitary Products Group...
  • Page 21: Gas Valve

    Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following: FIGURE 29: Reading Gas Pressure TABLE 15: Nominal Manifold Pressure NOMINAL MANIFOLD PRESSURE Natural Gas 3.5" w.c. (0.87 kPa) Propane (LP) Gas 10.0" w.c. (2.488 kPa) Unitary Products Group...
  • Page 22: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    0.58 w.c. (144 Pa), 0.75 w.c. (187 Pa), etc.), the static pressure Determine the External System Static Pressure (ESP) without the may be rounded to the nearest value in the table determining the filter. airflow using Step 5 or calculate the airflow by using the following example. Unitary Products Group...
  • Page 23: Blower Performance Cfm - Upflow (Without Filter) - Bottom Return

    1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m /min). 2. Motor voltage at 115 V. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 24: Blower Performance Cfm - Upflow (Without Filter) - Left Side Return

    1. Airflow expressed in standard cubic feet per minute (CFM). 2. Return air is through side opposite motor (left side). 3. Motor voltage at 115 V. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 25 1BR0321 21” CABINETS 1BR0324 24-1/2” CABINETS 1CB0314 14-1/2” CABINETS 1CB0317 17-1/2” CABINETS COMBUSTIBLE FLOOR BASE for Downflow Units 1CB0321 21” CABINETS 1CB0324 24-1/2” CABINETS 1SR0302 EXTERNAL SIDE FILTER RACK - with Filter Rack (6 pack) ALL MODELS Unitary Products Group...
  • Page 26: Wiring Diagram

    035-20464-002 Rev. A (1004) SECTION X: WIRING DIAGRAM FIGURE 31: Wiring Diagram Unitary Products Group...
  • Page 27 035-20464-002 Rev. A (1004) NOTES Unitary Products Group...
  • Page 28 NOTES Subject to change without notice. Printed in U.S.A. 035-20464-002 Rev. A (1004) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: 035-20464-001 Rev. A (0704) Unitary 5005 Norman Product York Group Drive 73069...

This manual is also suitable for:

Gm8sLy8sLm8sLf8

Table of Contents