Unitary products group P XU-V/G9V-UP Series Installation Manual

High efficiency tubular heat exchanger, two stage variable speed upflow, 60 - 120 mbh input, 17.58 - 35.17 kw input
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: P*XU-"V" / G9V-UP
Two Stage Variable Speed (Upflow)
60 - 120 MBH INPUT
(17.58 - 35.17 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . 9
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Furnace Base Rectangular Perforated Panel . . . . . . . . . . . . . . . . . . . 5
Furnace Filter Slot Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Filter Retainer Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Line Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Field Wiring for Single Stage Thermostat . . . . . . . . . . . . . . . . . . . . . . 9
Field Wiring for Two Stage Thermostat . . . . . . . . . . . . . . . . . . . . . . . . 9
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Horizontal Vent Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Termination Configuration - 1 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Termination Configuration - 2 Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 4
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
High Altitude Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical and Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
(All Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.

TABLE OF CONTENTS

CONDENSATE DRAIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .17
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
LIST OF FIGURES
Termination Configuration - 2 Pipe Basement . . . . . . . . . . . . . . . . . .12
Burner Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .15
Condensate Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
White Rodgers Intergrated Control . . . . . . . . . . . . . . . . . . . . . . . . . . .22
CFM / Timer Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
LIST OF TABLES
Combustion Air Supply and Vent Piping . . . . . . . . . . . . . . . . . . . . . . .10
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .14
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Replacement PSC Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
This product was manufactured
in a plant whose quality system
is certified/registered as being
in conformity with ISO 9001.
035-19624-001 Rev. A (0104)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the P XU-V/G9V-UP Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group P XU-V/G9V-UP Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING TUBULAR HEAT EXCHANGER SERIES CERTIFIED MODELS: P*XU-”V” / G9V-UP Two Stage Variable Speed (Upflow) 60 - 120 MBH INPUT This product was manufactured in a plant whose quality system (17.58 - 35.17 KW) INPUT is certified/registered as being in conformity with ISO 9001.
  • Page 2: Safety

    • Provide clearances for servicing ensuring that service access is mination must be located external to the building and in an area where allowed for both the burners and blower. there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3: Ductwork

    Unitary Products Group...
  • Page 4: Minimum Duct Sizing For Proper Airflow

    The External Static Pressure is determined by adding the Supply Duct Static Pressure reading to the Return Duct Static Pressure reading. The total external static pressure includes the pressure drop across the return air filter and A-coil. Unitary Products Group...
  • Page 5: Dimensions

    FIGURE 2: Furnace Base Rectangular Perforated Panel can be removed by performing the following steps: IMPORTANT: if an external mounted filter rack is being used see the Lay the furnace on its back. instructions provided with that accessory for proper hole cut size. Unitary Products Group...
  • Page 6: Filters

    FIGURE 6: Gas Valve IMPORTANT: Plan your combustion air piping before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and conventional 90-degree elbow(s) to enter through the cabinet access holes. Unitary Products Group...
  • Page 7: Gas Piping

    Gas piping may be connected from either side of the furnace using any personal injury, property damage and/or death. of the gas pipe entry knockouts on both sides of the furnace. Refer to Figure 1 dimensions. Unitary Products Group...
  • Page 8: Electrical Wiring

    Remove the screws and cut wire tie holding excess wiring. Reposition on the left side of the furnace and fas- ten using holes provided. Use wire tie's to secure any loose wires. FIGURE 9: Line Wiring Connections Unitary Products Group...
  • Page 9: Combustion Air And Vent System

    ½” Armaflex type insulation. Vent piping must be insulated with 1/2” Armaflex insulation if it will be subjected to freezing temperatures such as routing through unheated areas or through an unused chimney. Unitary Products Group...
  • Page 10: Combustion Air Intake And Vent Connection Size At Furnace

    COMBUSTION AIR / VENT CLEARANCES side termination. IMPORTANT: The vent must be installed with the following minimum Ventilated combustion air systems from the furnace to the clearances, and must comply with local codes and requirements. attic or crawl space termination. Unitary Products Group...
  • Page 11: Home Layout

    Vertical vent system. This vent system can be installed completely Termination should be positioned where vent vapors will not dam- vertical or a combination of horizontal, vertical, or offset using age plants or shrubs or air conditioning equipment. elbows. Unitary Products Group...
  • Page 12: Horizontal Vent Drain

    BETWEEN BOTTOM OF COMBUSTION AIR PIPE AND BOTTOM OF VENT MAINTAIN 12” MIN. CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE, WHICHEVER IS HIGHER FIGURE 14: Horizontal Vent Drain FIGURE 17: Termination Configuration - 2 Pipe Basement Unitary Products Group...
  • Page 13: Double Horizontal Sealed Combustion Air And Vent Termination

    Be sure the terminal assembly follows the outdoor clearances FIGURE 19: Double Vertical Sealed Combustion Air and Vent listed in Section #1 “Outdoor Air Contaminants.” Termination Unitary Products Group...
  • Page 14: Combustion Airflow Path Through The Furnace Casing To The Burner Box

    CARBON MONOX- EXAMPLE: Square feet is based on 8 foot ceilings. IDE, which can lead to serious injury, property damage and/or 28,000 BTUH X 50 Cubic Ft. = 1,400 = 175 Sq. Ft. death. 1,000 8’ Ceiling Height Unitary Products Group...
  • Page 15: Outside And Ambient Combustion Air

    If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not have enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can function safely. Unitary Products Group...
  • Page 16: Condensate Drain

    Blower and burner must never be operated without the blower It is recommended that either 1/2” or 3/4” PVC or equivalent pipe panel in place. be field installed as drain pipe from the furnace to the floor drain or condensate pump. Unitary Products Group...
  • Page 17: Start-Up And Adjustments

    Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life. Unitary Products Group...
  • Page 18: Gas Valve

    Seconds it took to measure the 2 cu.ft. of gas NATURAL GAS INPUT CALCULATION PROPANE (LP) GAS INPUT CALCULATION EXAMPLE: EXAMPLE: 1030 x 2 x 0.960 x 3600 2500 x 1 x 0.960 x 3600 79,997.38 80,000.00 90.5 Natural Gas Propane Gas BTU/SCF 1030 BTU/SCF 2500 Unitary Products Group...
  • Page 19: Inlet Gas Pressure Range

    ATED. Refer to the GAS CONVERSION FOR PROPANE (LP) AND Minimum 4.5” W.C. (1.12 kPa) 8.0” W.C. (1.99 kPa) HIGH ALTITUDES IN SECTION IV for information on high altitude con- versions. Maximum 10.5” W.C. (2.61 kPa) 13.0” (3.24 kPa) W.C. Unitary Products Group...
  • Page 20: Nominal Manifold Pressure

    Be sure that gas valve regulator cap is in place and burner box to Turn on power and energize main and redundant (P.M.) solenoids gas valve pressure reference hose is connected. as well as the HI terminal. Unitary Products Group...
  • Page 21: Reading Gas Pressure

    Circ. Input. Connect brown door switch wire to jumper. the ducts, about six feet from the furnace where they will not be affected by radiant heat. Increase the blower speed to decrease the temperature Connect white main harness lead to Line neutral. Unitary Products Group...
  • Page 22: White Rodgers Intergrated Control

    Integrated (Ignition) Control. This will cause the blower trol) does not function on variable speed models. Dip switch # 3 should to operate at the HIGH COOL speed. Dip switch 3 must be in the OFF be left in the off position. position. Unitary Products Group...
  • Page 23: Air Flow Data

    NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the instructions for the electronic air cleaner for further details. Unitary Products Group...
  • Page 24: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    Multiply percentage by airflow difference to obtain airflow reduction. (0.8) X (-90) = -72 Subtract airflow reduction value to airflow @ 0.50 w.c. (125 Pa) to obtain actual airflow @ 0.58 inwc (144 Pa) ESP. 2125 - 72 = 2053 Unitary Products Group...
  • Page 25: Wiring Diagram

    035-19624-001 Rev. A (0104) SECTION X: WIRING DIAGRAM FIGURE 30: Wiring Diagram Unitary Products Group...
  • Page 26 035-19624-001 Rev. A (0104) NOTES Unitary Products Group...
  • Page 27 035-19624-001 Rev. A (0104) Unitary Products Group...
  • Page 28 Subject to change without notice. Printed in U.S.A. 035-19624-001 Rev. A (0104) Copyright © by York International Corp. 2004. All rights reserved. Supersedes: Nothing Unitary 5005 Norman Product York Group Drive 73069...