• Heating mode
Model name
AOHG54KRTA
1-5. Compressor frequency limitation by outdoor temperature
I zone
20°C
H zone
16°C
G zone
12°C
F zone
7°C
E zone
2°C
D zone
-7°C
C zone
-10°C
B zone
-15°C
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
- (04-5) -
Limitation of compressor
frequency
46 rps
42 rps
35 rps
32 rps
23 rps
20 rps
17 rps
13 rps
16 rps