2. Thermostats with adjustable differential
2. Thermostats with adjustable
differential
The switching differential is changed by
turning the grub screw (2) inside the
setting screw (1). The switching point is
not changed by adjusting the differential,
only the reset point is shifted by the
amount of the differential. One 360°-
rotation of the differential screw varies the
switching differential by approx. 25 % of
the total differential range.
1
Fig. 9.
44
2
Switching differential
CAUTION
With TRM...-303, there is a risk of
touching the mains power. Therefore,
switch off power.
Turning to the right
Greater switching differential.
Turning to the left
Smaller switching differential.
Caution
Grub screw without end-stop to the left.
Drive out only max. flush to the surface of
the adjustment screw, otherwise risk of
loosing the screw.
MU2B-0375GE51 R0211A