3.2.3.1.12.1
TP-UART-Reset.indication Service
The Reset.indication service is sent after each reset if 40 bit-times line idle was detected.
TP-UART-Controlfield
7
6
5
4
0
0
0
0
Fig. 29: TP-UART-Reset.indication-Service
3.2.3.1.12.2
TP-UART-ProductID.response Service
The ProductIdentifier.response service is sent if a U_ProductID.request service was received from the
host.
Release a:
0100 0001
TP-UART-Controlfield
7
6
5
4
i
i
i
r
Product ID
Fig. 30: TP-UART-ProductID.response-Service
3.2.3.1.12.3
TP-UART-State.indication/response Service
The TP-UART-State.response-service is sent if an U_State.request-Service was received from the
host. If the TP-UART is too hot (over-temperature), the TW-bit has the value 1. In case of Slave
Collision, Receive Error, Checksum Error or Protocol Error or Recognition Over-Temperature or
Recognition Leaving-Over-Temperature the TP-UART sends a State.indication-Service.
TP-UART-Controlfield
7
6
5
4
SC
RE
TE
PE
Fig. 31: TP-UART-StateIndication/Response-Service
SC = Slave Collision
RE = Receive Error (Checksum, Parity or Biterror)
TE = Transmitter Error (send 0 receive 1)
PE = Protocol Error
TW = Temperature Warning
Attention: A received L-Data-Frame can follow the State indication without any delay.
3.2.3.1.12.4
TP-UART-L_Data.confirm Service
The L_DATA.confirm service is transmitted to the host if an acknowledge was received or if the last
repetition is transmitted and no acknowledge was received.
TP-UART-Controlfield
7
6
5
4
x
0
0
0
Fig. 32: TP-UART-L_DATA.confirm-Service
X = 1 The transmission of the L_DATA-frame was successful
X = 0 The transmission of the L_DATA-frame was not successful
Siemens AG
Infrastructure and Cities Sector,
Building Technologies
Control Products and Systems
P. O. Box 10 09 53,
D-93009 Regensburg
3
2
1
0
0
0
1
1
3
2
1
0
r
r
r
r
revision number
3
2
1
0
TW
1
1
1
e.g. illegal controlbyte
3
2
1
0
1
0
1
1
© Siemens AG 2012