REX A-1-9 and REX A-3-9 – STANDALONE OR
ACCESS CONTROLLER
The Rex is a controller with built-in proximity card reader. It is
designed for residential and business buildings, offices, shops, etc.
In various operation modes, the controller allows access for up to
500 users (2 master cards + 500 user cards). The controller can
have 125kHz or 13.56MHz reading frequency.
As a standalone controller, the entire set-up procedure is carried
out with master card. User cards can either be registered or
deleted.
As an access controller, the entire set-up procedure is carried out
with the software.
The controller signals normal operation with flashing red and green
LED It can also be used as a Wiegand 26-bit reader, if needed.
TECHNICAL DATA
REX A
REX A-1-9 reading frequency
REX A-1-9 reading distance
REX A-1-9 current consumption
REX A-3-9 reading frequency
REX A-3-9 reading distance
REX A-3-9 current consumption
Dimensions (mm)
Protection
Communication
Operating voltage
Operating temperature
Cabel
Memory
Inputs
Outputs
Clock
CONNECTION CABLE
Description/Wiegand 26-
Wire-Color
bit
1 – red
9-14V DC
2 – gray/black
GND
3 – green
El. strike output / Data 0
4 – white
Alarm output/ Data 1
Door status switch input/
5 – yellow
Buzzer input
Push button input /
6 – orange
LED input
7 – blue
CA
8 – brown
CB
Black line
REX A-1-9 and REX A-3-9 – Standalone or access controller
125kHz
Up to 15cm
60mA
13.56MHz
Up to 7cm
90mA
120x96x15 (WxHxD)
IP65
RS485
From 9V to 14V DC
From -20°C to 70°C
Cable through or on the wall –
3m
500 cards
500 events
Door status
Push button
Transistor output for el. strike
0.5A
Real time clock, battery backup
(max. ten hours)
Specification
Power supply
Ground
Max. 0.5A
Active = GND
Active = GND
Active = GND
Active = GND
RS485 A line
RS485 B line
LED DIODES
Color
Description
Flashing red/green
Normal mode
Lit green
El. strike is unlocked
Lit red
Card has no rights
Power supply
The controller need's external power supply to operate. The Spider
W40 power supply is sufficient to power two controllers and two
12V electric strikes or two 12V magnetic locks (0.5A). If you will
use it as a standalone controller and low consumption electric
strike (0.25A) you can use power supply Spider W5.
Voltage drops and cable signal interferences
When you connect the controller, use cable with a diameter of at
least 0.22mm
2
. If the cable length exceeds 25m, use one twisted
pair of UTP cables for the positive (+) pole and one for the
negative (-) pole. The cable length between power supply and the
controller should not exceed 50m.
Take into consideration that a 0.22mm
approximately 9 ohm per 100m. The power supply at the end of
cable should be a minimum of 9V. If you are using el. strike, it is
highly recommended that the voltage drop is calculated. At greater
distances, a thicker cable of 0.5mm
wherever possible.
If the load is, for example, 0.5A (with el. strike) then, on the
2
0.22mm
cable voltage drop will be 4.5V at 100m. For the device
with 60mA consumption, the voltage drop is 0.5V.
Reading distance depends on where the controller is installed. The
presence of metal or interferences can significantly reduce the
reading distance. DO NOT install the controller directly on metal
surfaces and/or cover it with a metal cover.
It is not recommended to install controllers closer than 30cm
from each other in any direction. Otherwise, it may result in
inaccurate readings or, indeed, in the controller not reading at
all.
For the Rex A-3-9 to comply with EMC directives (CE), you
have to put ferrite core on the cable as close to the
controller as possible, making two turns!
Inputs, outputs and environment
Inputs:
Inputs are realized with opto-isolators. The input is active, when
pulled to ground with an open collector transistor or mechanical
switch, which is connecting the input pin of the controller to the
Ground.
Outputs:
Output has a pre-installed protection diode for an inductive load. It
is also protected from current overload. The best way is to use a
0.25A el. strike or a 0.5A el. magnet, which has to be connected to
the same positive pole (+) as the controller. Connect the negative
pole (-) to the door strike output (wire 3). When the output is
active it is pulled to ground. This can be changed with function 5 –
negate output (for el. magnet).
Environment:
If the plastic housing is in a different color than black, then there is
a chance that the color will change (to some extend) in a few
months or years if exposed to direct sunlight.
IP65 protection, but you must assure good cable joints, protected
against moisture, otherwise corrosion may damage the controller.
Damage in such cases is not covered by the warranty.
Reading range:
The controller has a program algorithm that, at power start, sets
parameters based on the installation environment, so as to ensure
an optimal reading range. DO NOT install the controller directly on
metal surfaces and/or cover it with a metal cover; it may stop
working/reading. If you plan to test the controller and move it onto
different surfaces, then you have to reset it (power off/on) on each
surface.
2
cable has a resistance of
2
or more should be used
The controller has
3/2015
www.jantar.si

Advertisement

loading

Summary of Contents for Jantar REX A-1-9

  • Page 1 REX A-1-9 and REX A-3-9 – Standalone or access controller LED DIODES Color Description Flashing red/green Normal mode Lit green El. strike is unlocked Lit red Card has no rights Power supply The controller need’s external power supply to operate. The Spider W40 power supply is sufficient to power two controllers and two 12V electric strikes or two 12V magnetic locks (0.5A).
  • Page 2 REX A-1-9 and REX A-3-9 – Standalone or access controller Installation of Rex A user card is now registered and with it, you can open output on the A special holder, provided with the controller, is needed for controller. If the card has already been registered, it is now deleted attachment to the wall.
  • Page 3 REX A-1-9 and REX A-3-9 – Standalone or access controller Function 6) Delete a lost card Set with master card: Delete the next card on the list. Use this function if you lost a card Approach the master card and remove it after 15 double beeps.
  • Page 4 Spider W5-USB, Spider W5-NET, Spider W40+NET. The RS485 communication bus is used between the controllers and Jantar software. Up to 128 controllers can be lined up into one communication line. The maximum length of the communication line is 1000 cable meters. It is recommended that you use an FTP or S-FTP cable.

This manual is also suitable for:

Rex a-3-9