Preaction 346f
June 1, 2011
6" MoDEL G-6000P PrEACTIoN
TECHNICAL DATA
wITH ELECTrIC rELEAsE
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

5. oPErATIoN

A. In the set position:
Air �ressure is introduced into the s�rinkler �i�ing for su�ervisory �ur�oses only for single interlock systems. For double interlock
systems, air �ressure is used for su�ervisory �ur�oses
air �ressure is used for su�ervisory �ur�oses and as one of the two initiation actions of the cross-zoned solenoid. Prime
Prime
water is routed to the normally closed solenoid valve, and to the �rime chamber. When �rime water enters the �rime chamber, the
�rime chamber assembly is �ressurized, causing it to ex�and downward onto the water seat.
Figure 6 - set Position