Modine Manufacturing SmartCool Airedale Technical Manual

Modine Manufacturing SmartCool Airedale Technical Manual

One downflow dedicated chilled water

Advertisement

Quick Links

One Downflow
TM
SmartCool
Dedicated Chilled Water
Technical Manual
Original Instructions
FM00542
EMS52086

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SmartCool Airedale and is the answer not in the manual?

Questions and answers

Summary of Contents for Modine Manufacturing SmartCool Airedale

  • Page 1 One Downflow SmartCool Dedicated Chilled Water Technical Manual Original Instructions FM00542 EMS52086...
  • Page 2 SmartCool™ Precision Air Conditioning Special Precautions The guidance in this manual must be followed to provide safe, efficient and trouble-free operation. In addition, particular care must be exercised regarding the special precautions listed below. Failure to properly address these critical areas could result in property damage or loss, personal injury or death.
  • Page 3: Customer Services

    Precision Air Conditioning SmartCool™ NOTE Please specify preferred 4 digit Display Screen PIN at time of order. When adding to an existing controls scheme, please consult Airedale Controls to ensure strategy compatibility. The plugged unit-to-unit network termination ensures that the connections are made simultaneously. Failure to attach the cables in this way may cause damage to the controller.
  • Page 4: Health And Safety

    SmartCool™ Precision Air Conditioning Health and Safety The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. Safety The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results.
  • Page 5: Environmental Considerations

    Precision Air Conditioning SmartCool™ Environmental Considerations Units with supply water temperatures below +5°C (41°F) ● Glycol is recommended when a supply water temperature of +5°C (41°F) or below is required or when static water can be exposed to freezing temperatures. Unit pipework subject to ambient temperatures lower than 0°C (32°F) Glycol of an appropriate concentration must be used within the system to ensure adequate freeze protection.
  • Page 6: Table Of Contents

    SmartCool™ Precision Air Conditioning Contents Customer Services Health and Safety Environmental Considerations Nomenclature Introduction Construction System Configurations Chilled Water Airflow Electrical Controls General Installation Data Dimensions Minimum Unit Clearances For Maintenance Minimum Unit Ceiling Clearances For Airflow Unpacking Lifting Plinth Installation Pipework Schematics Recommended Pipework (External to Unit) Incoming Services...
  • Page 7: Nomenclature

    Precision Air Conditioning SmartCool™ Nomenclature Example: Product Name SmartCool One - Dedicated Chilled Product Variant Water 900mm / 35.4 in 1200mm / 47.2 in 1500mm / 59.1 in 1800mm / 70.9 in 2200mm / 86.6 in 2500mm / 98.4 in Case Width 3100mm / 122.0 in 3500mm / 137.8 in...
  • Page 8: System Configurations

    SmartCool™ Precision Air Conditioning System Configurations Isolator Floor Height Unit Control Display Floor Stand Control Panel Cooling Coil Air Filters Fans Example shown is SO09 with open floor stand. TM SmartCool One 5057724 v1.0_08_2022...
  • Page 9 Precision Air Conditioning SmartCool™ System Configurations Isolator Floor Height Unit Control Display Floor Stand Cooling Coil Air Filters Control Valve Fans Control Panel Example shown is SO31 with open floor stand. TM SmartCool One 5057724 v1.0_08_2022...
  • Page 10 SmartCool™ Precision Air Conditioning System Configurations Isolator Unit Control Display Floor Height Floor Stand Air Filters Cooling Coil Control Valve Control Panel Fans Example shown is SO60 with open floor stand. TM SmartCool One 5057724 v1.0_08_2022...
  • Page 11: Chilled Water

    Precision Air Conditioning SmartCool™ Chilled Water System Configuration Features ● ● ● ● ● ● ● ● ● ● ● ● RTPF Chilled Water Coil ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Low Flow Coil (9-12K / 16.2-21.6°F) ○...
  • Page 12 SmartCool™ Precision Air Conditioning Energy Valve The Belimo Energy Valve offers the same functionality of a traditional PICV by using a flow meter and ball valve in series as opposed to a mechanical diaphragm in a traditional PICV. The actuated ball valve regulates to changes in flow measured in the flow meter.
  • Page 13: Airflow

    Precision Air Conditioning SmartCool™ Airflow System Configuration Features ● ● ● ● ● ● ● ● ● ● ● ● EC Backward Curved Fans in Floor Stand ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ISO-C-80 Filtration (G4 equivalent) ○...
  • Page 14: Electrical

    SmartCool™ Precision Air Conditioning Electrical System Configuration Features ● ● ● ● ● ● ● ● ● ● ● ● 400V / 50Hz / 3Ph (-0) ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 460-480V / 3Ph / 60Hz (-3) ○...
  • Page 15 Precision Air Conditioning SmartCool™ Dual Power Supply (ATS) Disconnect Switches (60Hz) Disconnect switches (also known as isolator switches, safety switches, and load break switches) are used to isolate electrical circuits by disconnecting supply voltages and interrupting the flow of electrical current. By quickly stopping the flow of power, disconnect switches allow for emergency shutdowns, switching to alternate power sources and maintenance.
  • Page 16: Controls

    SmartCool™ Precision Air Conditioning Controls System Configuration Features ● ● ● ● ● ● ● ● ● ● ● ● c.pCO Microprocessor ● ● ● ● ● ● ● ● ● ● ● ● Vu™ Touch Screen Display ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Filter Change Switch ●...
  • Page 17 Precision Air Conditioning SmartCool™ Password Protection The control system integrity shall be maintained by restricting access with a password PIN number. NOTE Please specify preferred 4 digit Display Screen PIN at time of order. Remote On/Off Screened cable should be used for the Remote ON/OFF to prevent negative effects to EMC levels. Terminals for interlocking are provided.
  • Page 18 SmartCool™ Precision Air Conditioning BMS Interface Card BMS Interface Cards can be factory fitted and interfaced with most BMS. A wide range of protocols can be accommodated through the use of interface devices, with ModBus/Jbus and Carel available as standard options. Please contact Airedale to discuss the licensing requirements for other interfaces such as SNMP, LonWorks, Metasys and BACnet.
  • Page 19: General

    Precision Air Conditioning SmartCool™ General System Configuration Features ● ● ● ● ● ● ● ● ● ● ● ● Open Discharge Floor Stand ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Rear Discharge Floor Stand ○...
  • Page 20: Installation Data

    SmartCool™ Precision Air Conditioning Installation Data Dimensions SO09-35 Case Height - B Case Depth Floor Stand* Case Width Door Units Quantity Extended Standard 1980 2280 SO09 35.4 78.0 89.8 35.0 23.5 1200 1980 2280 SO12 47.2 78.0 89.8 35.0 23.5 1500 1980 2280...
  • Page 21 Precision Air Conditioning SmartCool™ Dimensions SO30-60 Case Width Case Height Case Depth Floor Stand* Door Units Quantity 3000 2400 2200 SO30 118.5 94.5 86.6 24.7 4000 2400 2200 SO40 157.5 94.5 86.6 24.7 5000 2400 2200 SO50 196.9 94.5 86.6 24.7 6000 2400...
  • Page 22: Minimum Unit Clearances For Maintenance

    SmartCool™ Precision Air Conditioning Minimum Unit Clearances For Maintenance The minimum clearance requirements must be maintained around the units. This is to ensure filters can be maintained from the front or side* of the unit and that fans can be maintained from the front of the unit. For below floor floor stand installations, floor tile support posts must be removable to allow access to the fans.
  • Page 23: Minimum Unit Ceiling Clearances For Airflow

    Precision Air Conditioning SmartCool™ Minimum Unit Ceiling Clearances For Airflow The minimum unit ceiling clearances shown below correspond to the installation environment of the unit in relation to adjacent walls, units, ceilings and other obstructions. These clearances are the minimum required to ensure adequate unit return airflow is maintained during operation.
  • Page 24: Unpacking

    SmartCool™ Precision Air Conditioning Installation Data Packed Dimensions Single slab units may be shipped mounted on a wooden pallet and covered with polythene. The pallet shall be mechanically fixed to the unit for transportation only. The packaging adds 50mm (2”) to the length and width of the unit and 160mm (6.3”)to it’s height.
  • Page 25 Precision Air Conditioning SmartCool™ It is possible to lift from the front or rear, close to the floor stand legs if a forklift is to be used. The floor stand shall be provided with a roll of compressible foam tape to prevent air bypass during operation. The tape shall be applied to the top face of the floor stand to sufficiently prevent air bypass once the unit has been installed on top of the floor stand.
  • Page 26 SmartCool™ Precision Air Conditioning When using a forklift to position the unit, the forks must pass through the slots as shown. Forks must not exceed the depth of the unit to ensure the forks do not clash against the rear gland plate when against a wall. When not against a wall, all gland plates can be removed so the above does not apply.
  • Page 27 Precision Air Conditioning SmartCool™ 4 Point Lifting - Floor Stand 4 Point Lift Unit SO30 2389 94.1 SO40 3389 133.4 2152.8mm (84.76 in) 4 Point Lifting - Unit 4 Point Lift Unit SO30 97.5 2477 SO40 2950 2292mm (90.2in) TM SmartCool One 5057724 v1.0_08_2022...
  • Page 28 SmartCool™ Precision Air Conditioning 8 Point Lifting - Floor Stand 8 Point Lift Unit SO50 2557 100.7 1705 67.1 SO60 3007 118.4 2256 88.8 2292mm (90.2in) 2152.8mm (84.76 in) 8 Point Lifting - Unit 8 Point Lift Unit SO50 2340 1600 SO60 3380...
  • Page 29: Plinth Installation

    Precision Air Conditioning SmartCool™ Plinth Installation Image for illustration purposes only, showing standard foot design. Please contact Airedale for specific details. Seismic Applications In seismic applications the safety of persons and equipment is of the highest importance. The following considerations must be taken into account when installing the equipment in areas with a risk of seismic activity: Anchorage Requirements Anchorage and mounting requirements must be inspected approved by a registered Structural Engineer assigned to the...
  • Page 30: Pipework Schematics

    SmartCool™ Precision Air Conditioning Pipework Schematics SO09-35 PDZAL UNIT DESCRIPTION UNIT DESCRIPTION INLET LEG (") [A] INLET LEG (") [A] OUTLET LEG (") [B] OUTLET LEG (") [B] MANIFOLDS (") [C] MANIFOLDS (") [C] BYPASS LEG (") [D] BYPASS LEG (") [D] Water Temperature Sensor Reducer 2-WAY VALVE...
  • Page 31 Precision Air Conditioning SmartCool™ Pipework Schematics SO30-60 PDZAL UNIT DESCRIPTION UNIT DESCRIPTION INLET LEG (") [A] INLET LEG (") [A] OUTLET LEG (") [B] OUTLET LEG (") [B] STEEL MANIFOLDS (") [C] STEEL MANIFOLDS (") [C] STEEL-COPPER LEG (") [D] STEEL-COPPER LEG (") [D] COIL MANIFOLDS (") [E] COIL MANIFOLDS (") [E]...
  • Page 32: Recommended Pipework (External To Unit)

    SmartCool™ Precision Air Conditioning Recommended Pipework (External to Unit) The following diagram shows the recommended pipework and auxiliary components that should be installed external to the SmartCool One unit. Do not use a differential pressure control valve and a PICV in the same system. These two components will work against each other and will affect performance.
  • Page 33: Incoming Services

    Precision Air Conditioning SmartCool™ Incoming Services SO09-12 SO15-35 Image shows LHS terminations; RHS terminations are mirrored. SO09-12 12.4 1630 64.2 1810 71.3 SO15-35 38.2 1705 67.1 Incoming Services SO30-50 SO60 Image shows RHS terminations; LHS terminations are mirrored. SO30-50 2200 86.6 2400 94.5...
  • Page 34: Electrical Connections

    SmartCool™ Precision Air Conditioning Electrical Connections SO09-35 422.6 352.6 252.6 Front of unit 1.97 16.64 13.88 9.94 Electrical incoming positions are the same on both LHS/RHS for both standard and extended height units. SO09-35 allows electrical terminations to be on the same or opposite side as the pipe terminations. Electrical Connections SO30-60 3.35...
  • Page 35: Wire Flow Guide - 50Hz

    Precision Air Conditioning SmartCool™ Wire Flow Guide - 50Hz Cable Routing General Wire Path Only LHS Pipe Termination Red: LHS Electrical Cable Route Blue: RHS Electrical Cable Route Both left and right hand side wiring entry is available on units with LHS pipework termination. LHS Pipe Termination Single Power Supply LHS Pipe Termination Dual Power Supply General wire path shown only.
  • Page 36 SmartCool™ Precision Air Conditioning RHS Pipe Termination Blue: LHS Electrical Cable Route Red: RHS Electrical Cable Route Both left and right hand side wiring entry is available on units with RHS pipework termination. RHS Pipe Termination Single Power Supply RHS Pipe Termination Dual Power Supply General wire path shown only.
  • Page 37: Wire Flow Guide - 60Hz

    Precision Air Conditioning SmartCool™ Wire Flow Guide - 60Hz Cable Routing General Wire Path Only LHS Pipe Termination Red: LHS Electrical Cable Route Blue: RHS Electrical Cable Route Both left and right hand side wiring entry is available on units with LHS pipework termination. LHS Pipe Termination Single Power Supply LHS Pipe Termination Dual Power Supply LHS Pipe Termination Dual Power Supply + Disconnect Switches...
  • Page 38 SmartCool™ Precision Air Conditioning RHS Pipe Termination Blue: LHS Electrical Cable Route Red: RHS Electrical Cable Route Both left and right hand side wiring entry is available on units with RHS pipework termination. RHS Pipe Termination Single Power Supply RHS Pipe Termination Dual Power Supply RHS Pipe Termination Dual Power Supply + Disconnect Switches General wire path shown only.
  • Page 39: Flood Detection

    Precision Air Conditioning SmartCool™ Flood Detection SmartCool One has three methods of flood detection: Probe sensor (solid state), supplied loose for remote mounting when the SmartCool One unit is provided with a single unit level drip tray. Rope sensor, supplied loose with self-adhesive clips for remote mounting on site, standard on all SmartCool One units.
  • Page 40: Unit To Unit Network Termination

    SmartCool™ Precision Air Conditioning Drip Tray Drain P-Trap 1000 A P-Trap must be included when connecting the drain to the coil drip tray. This allows water to drain properly while the unit is running and prevents any air from bypassing the chilled water coil through the drain tube. The P-Trap should be filled with a column of water during the commissioning phase.
  • Page 41: Glycol

    Precision Air Conditioning SmartCool™ Glycol Specific Heat Capacity (Cp) - kJ/kg.K (Btu/lb.°F) Water/Glycol Ethylene Glycol (Volume) / Freezing Point °C Temperature 0% / 10% / 20% / 30% / 40% / 0°C (32°F) -4°C (24.8°F) -9°C (15.8°F) -15°C (5°F) -23°C (-9.4°F) °C (°F) 20 (68) 4.183 (0.999)
  • Page 42: Technical Data

    SmartCool™ Precision Air Conditioning Technical Data Interconnected Wiring Mains Incoming ○ ← ○ ← Mains Incoming Supply - Primary ○ ← 380V/400V 50Hz 3PH + N Standard ○ ← 460V 60Hz 3PH ○ ← ○ ← ○ ← Mains Incoming Supply - Secondary ○...
  • Page 43 Precision Air Conditioning SmartCool™ Interconnected Wiring ○ ← ○ ← Fan 11 Unit to Floor Stand Fan 11 Power ○ ← (Connector X30) SO60 ○ ← ○ ← ○ ← Fan 12 Unit to Floor Stand Fan 12 Power ○ ←...
  • Page 44: Operating Temperature Limits

    SmartCool™ Precision Air Conditioning Technical Data Operating Temperature Limits Minimum Design Maximum °C °F °C °F °C °F Return Air Temperature 82.4 75.2 113.0 Return Air Relative Humidity (%) 9.4% 22.6% 32.7% 82.4 96.8 Inlet Water Temperature Temperature Difference (K / °R) 10.8°R 14.4°R...
  • Page 45: Waterside Pressure Drop Low Flow 50Hz

    Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO09D004CLBSx-0/-A SO12D006CLBSx-0/-A SO09D004CLBXx-0/-A SO12D006CLBXx-0/-A SO09D004CLCSx-0/-A SO12D006CLCSx-0/-A SO09D005CLCXx-0/-A SO12D007CLCXx-0/-A SO09D005CLDSx-0/-A SO12D007CLDSx-0/-A SO09D005CLDXx-0/-A SO12D008CLDXx-0/-A SO09 Low Flow 50Hz Unit SO09 Low Flow 50Hz 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.00 0.20 0.40 0.60 0.80 1.00...
  • Page 46 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO15D007CLBSx-0/-A SO18D009CLBSx-0/-A SO15D009CLBXx-0/-A SO18D010CLBXx-0/-A SO15D008CLCSx-0/-A SO18D010CLCSx-0/-A SO15D010CLCXx-0/-A SO18D011CLCXx-0/-A SO15D009CLDSx-0/-A SO18D011CLDSx-0/-A SO15D010CLDXx-0/-A SO18D013CLDXx-0/-A SO15 Low Flow 50Hz Unit SO15 Low Flow 50Hz 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.00 0.50 1.00 1.50 2.00 2.50...
  • Page 47 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO22D011CLBSx-0/-A SO25D013CLBSx-0/-A SO22D013CLBXx-0/-A SO25D015CLBXx-0/-A SO22D013CLCSx-0/-A SO25D015CLCSx-0/-A SO22D015CLCXx-0/-A SO25D017CLCXx-0/-A SO22D014CLDSx-0/-A SO25D016CLDSx-0/-A SO22D016CLDXx-0/-A SO25D019CLDXx-0/-A SO22 Low Flow 50Hz Unit SO22 Low Flow 50Hz 120.0 100.0 80.0 60.0 40.0 20.0 0.00 1.00 2.00 3.00 4.00 5.00 6.00...
  • Page 48 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO31D017CLBSx-0/-A SO35D019CLBSx-0/-A SO31D020CLBXx-0/-A SO35D022CLBXx-0/-A SO31D019CLCSx-0/-A SO35D021CLCSx-0/-A SO31D022CLCXx-0/-A SO35D025CLCXx-0/-A SO31D020CLDSx-0/-A SO35D023CLDSx-0/-A SO31D024CLDXx-0/-A SO35D027CLDXx-0/-A SO31 Low Flow 50Hz Unit SO31 Low Flow 50Hz 120.0 100.0 80.0 60.0 40.0 20.0 0.00 1.00 2.00 3.00 4.00 5.00 6.00...
  • Page 49: Waterside Pressure Drop High Flow 50Hz

    Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO09D004CHBSx-0/-A SO12D006CHBSx-0/-A SO09D005CHBXx-0/-A SO12D007CHBXx-0/-A SO09D004CHCSx-0/-A SO12D006CHCSx-0/-A SO09D005CHCXx-0/-A SO12D008CHCXx-0/-A SO09D005CHDSx-0/-A SO12D007CHDSx-0/-A SO09D005CHDXx-0/-A SO12D008CHDXx-0/-A SO09 High Flow 50Hz Unit SO09 High Flow 50Hz 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 0.00 0.50 1.00...
  • Page 50 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO15D008CHBSx-0/-A SO18D009CHBSx-0/-A SO15D009CHBXx-0/-A SO18D011CHBXx-0/-A SO15D009CHCSx-0/-A SO18D010CHCSx-0/-A SO15D010CHCXx-0/-A SO18D012CHCXx-0/-A SO15D009CHDSx-0/-A SO18D011CHDSx-0/-A SO15D011CHDXx-0/-A SO18D013CHDXx-0/-A SO15 High Flow 50Hz Unit SO15 High Flow 50Hz 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 0.00 1.00 2.00...
  • Page 51 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO22D012CHBSx-0/-A SO25D014CHBSx-0/-A SO22D014CHBXx-0/-A SO25D016CHBXx-0/-A SO22D013CHCSx-0/-A SO25D015CHCSx-0/-A SO22D015CHCXx-0/-A SO25D018CHCXx-0/-A SO22D014CHDSx-0/-A SO25D016CHDSx-0/-A SO22D016CHDXx-0/-A SO25D019CHDXx-0/-A SO22 High Flow 50Hz Unit SO22 High Flow 50Hz 100.0 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 0.00 2.00 4.00...
  • Page 52 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO31D018CHBSx-0/-A SO35D020CHBSx-0/-A SO31D021CHBXx-0/-A SO35D024CHBXx-0/-A SO31D019CHCSx-0/-A SO35D022CHCSx-0/-A SO31D023CHCXx-0/-A SO35D026CHCXx-0/-A SO31D021CHDSx-0/-A SO35D024CHDSx-0/-A SO31D025CHDXx-0/-A SO35D028CHDXx-0/-A SO31 High Flow 50Hz Unit SO31 High Flow 50Hz 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 0.00 2.00 4.00 6.00...
  • Page 53 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO30D043CLDSx-0/-A SO40D059CLDSx-0/-A SO30D045CHDXx-0/-A SO40D061CHDXx-0/-A SO30 50Hz Unit SO30 50Hz 120.0 100.0 80.0 60.0 40.0 20.0 0.00 2.00 4.00 6.00 8.00 10.00 12.00 Flowrate (l/s) SO40 50Hz Unit SO40 50Hz SO30D043CLDSx-0/-A SO30D045CHDSx-0/-A 120.0 100.0 80.0...
  • Page 54 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO50D074CLDSx-0/-A SO60D097CLDSx-0/-A SO50D077CHDXx-0/-A SO60D101CHDXx-0/-A SO50 50Hz Unit SO50 50Hz 120.0 100.0 80.0 60.0 40.0 20.0 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00 20.00 Flowrate (l/s) SO60 50Hz Unit SO60 50Hz SO50D074CLDSx-0/-A SO50D077CHDSx-0/-A...
  • Page 55: Waterside Pressure Drop Low Flow 60Hz

    Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO09D004CLBSx-3 SO12D006CLBSx-3 SO09D005CLBXx-3 SO12D007CLBXx-3 SO09D004CLCSx-3 SO12D007CLCSx-3 SO09D005CLCXx-3 SO12D008CLCXx-3 SO09D005CLDSx-3 SO12D007CLDSx-3 SO09D006CLDXx-3 SO12D007CLDXx-3 SO09 Low Flow 60Hz Unit SO09 Low Flow 60Hz 50.0 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 0.00 5.00 10.00 15.00...
  • Page 56 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO15D008CLBSx-3 SO18D010CLBSx-3 SO15D009CLBXx-3 SO18D011CLBXx-3 SO15D009CLCSx-3 SO18D010CLCSx-3 SO15D010CLCXx-3 SO18D012CLCXx-3 SO15D009CLDSx-3 SO18D011CLDSx-3 SO15D011CLDXx-3 SO18D013CLDXx-3 SO15 Low Flow 60Hz Unit SO15 Low Flow 60Hz 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 0.00 10.00 20.00 30.00 40.00...
  • Page 57 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO22D012CLBSx-3 SO25D014CLBSx-3 SO22D014CLBXx-3 SO25D017CLBXx-3 SO22D013CLCSx-3 SO25D016CLCSx-3 SO22D016CLCXx-3 SO25D018CLCXx-3 SO22D014CLDSx-3 SO25D017CLDSx-3 SO22D017CLDXx-3 SO25D020CLDXx-3 SO22 Low Flow 60Hz Unit SO22 Low Flow 60Hz 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 0.00 10.00 20.00 30.00 40.00...
  • Page 58 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO31D018CLBSx-3 SO35D021CLBSx-3 SO31D021CLBXx-3 SO35D024CLBXx-3 SO31D020CLCSx-3 SO35D023CLCSx-3 SO31D023CLCXx-3 SO35D027CLCXx-3 SO31D022CLDSx-3 SO35D025CLDSx-3 SO31D025CLDXx-3 SO35D029CLDXx-3 SO31 Low Flow 60Hz Unit SO31 Low Flow 60Hz 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 0.00 20.00 40.00 60.00 80.00...
  • Page 59: Waterside Pressure Drop High Flow 60Hz

    Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO09D004CHBSx-3 SO12D006CHBSx-3 SO09D005CHBXx-3 SO12D007CHBXx-3 SO09D005CHCSx-3 SO12D007CHCSx-3 SO09D005CHCXx-3 SO12D008CHCXx-3 SO09D005CHDSx-3 SO12D007CHDSx-3 SO09D006CHDXx-3 SO12D008CHDXx-3 SO09 High Flow 60Hz Unit SO09 High Flow 60Hz 35.0 30.0 25.0 20.0 15.0 10.0 0.00 5.00 10.00 15.00 20.00 25.00 30.00...
  • Page 60 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO15D008CHBSx-3 SO18D010CHBSx-3 SO15D010CHBXx-3 SO18D012CHBXx-3 SO15D009CHCSx-3 SO18D011CHCSx-3 SO15D011CHCXx-3 SO18D013CHCXx-3 SO15D010CHDSx-3 SO18D012CHDSx-3 SO15D011CHDXx-3 SO18D014CHDXx-3 SO15 High Flow 60Hz Unit SO15 High Flow 60Hz 35.0 30.0 25.0 20.0 15.0 10.0 0.00 20.00 40.00 60.00 80.00 100.00 120.00...
  • Page 61 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO22D013CHBSx-3 SO25D015CHBSx-3 SO22D015CHBXx-3 SO25D017CHBXx-3 SO22D014CHCSx-3 SO25D016CHCSx-3 SO22D016CHCXx-3 SO25D019CHCXx-3 SO22D015CHDSx-3 SO25D017CHDSx-3 SO22D017CHDXx-3 SO25D020CHDXx-3 SO22 High Flow 60Hz Unit SO22 High Flow 60Hz 35.0 30.0 25.0 20.0 15.0 10.0 0.00 20.00 40.00 60.00 80.00 100.00 120.00...
  • Page 62 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO31D019CHBSx-3 SO35D022CHBSx-3 SO31D022CHBXx-3 SO35D025CHBXx-3 SO31D021CHCSx-3 SO35D024CHCSx-3 SO31D024CHCXx-3 SO35D028CHCXx-3 SO31D022CHDSx-3 SO35D025CHDSx-3 SO31D026CHDXx-3 SO35D029CHDXx-3 SO31 High Flow 60Hz Unit SO31 High Flow 60Hz 30.0 25.0 20.0 15.0 10.0 0.00 50.00 100.00 150.00 200.00 250.00 Flowrate (gpm) SO35 High Flow 60Hz Unit...
  • Page 63 Precision Air Conditioning SmartCool™ Waterside Pressure Drop Coil only SO30D043CLDSx-3 SO40D059CLDSx-3 SO30D044CHDXx-3 SO40D061CHDXx-3 SO30 60Hz Unit SO30 60Hz 35.0 30.0 25.0 20.0 15.0 10.0 0.00 20.00 40.00 60.00 80.00 100.00 120.00 140.00 160.00 180.00 Flowrate (gpm) SO40 60Hz Unit SO40 60Hz SO30D043CLDSx-3 SO30D044CHDSx-3 40.0...
  • Page 64 SmartCool™ Precision Air Conditioning Waterside Pressure Drop Coil only SO50D074CLDSx-3 SO60D096CLDSx-3 SO50D076CHDXx-3 SO60D100CHDXx-3 SO50 60Hz Unit SO50 60Hz 35.0 30.0 25.0 20.0 15.0 10.0 0.00 50.00 100.00 150.00 200.00 250.00 300.00 350.00 Flowrate (gpm) SO60 60Hz Unit SO60 60Hz SO50D074CLDSx-3 SO50D076CHDSx-3 35.0 30.0...
  • Page 65: Sound Measurement Method

    Precision Air Conditioning SmartCool™ Sound Measurement Method Measurement Of Sound Power All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated sound pressure meter in accordance with BS EN ISO 3746:2010. All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO 3746:2010.
  • Page 66: Sound Data - 50Hz

    SmartCool™ Precision Air Conditioning Technical Data Sound Data - 50Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO09xxxCxBSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO12xxxCxBSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 67 Precision Air Conditioning SmartCool™ Technical Data Sound Data - 50Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO12xxxCxCSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO15xxxCxCSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 68 SmartCool™ Precision Air Conditioning Technical Data Sound Data - 50Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO15xxxCxDSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO18xxxCxDSx-0/A Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 69: Sound Data - 60Hz

    Precision Air Conditioning SmartCool™ Technical Data Sound Data - 60Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO09xxxCxBSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO12xxxCxBSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 70 SmartCool™ Precision Air Conditioning Technical Data Sound Data - 60Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO12xxxCxCSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO15xxxCxCSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 71 Precision Air Conditioning SmartCool™ Technical Data Sound Data - 60Hz Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SO15xxxCxDSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air SO18xxxCxDSx-3 Case Breakout Sound Pressure @ 3m (9.8ft) Discharge Air Return Air...
  • Page 72: Mechanical And Electrical Data - 400V

    SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) (1) kW 36.9 55.4 73.9 88.1 112.5 131.0 167.4 192.5 43.1 64.8 86.5 103.1 Nominal Fan Power Input (Fan 1.08 1.71 2.28 2.60 3.71 3.97...
  • Page 73 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 132.0 152.7 196.8 224.9 41.1 61.6 82.2 98.0 125.5 145.4 186.9 214.2 Nominal Fan Power Input (Fan 4.90 5.41 7.01 8.33 1.27 2.00 2.68 3.10...
  • Page 74 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 48.1 72.0 96.2 114.6 146.3 169.8 218.5 250.0 45.0 67.3 90.1 107.0 Nominal Fan Power Input (Fan 1.64 2.68 3.52 4.09 5.75 6.27 8.13 9.56...
  • Page 75 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 137.2 159.5 205.0 234.4 52.5 77.8 104.4 125.3 159.9 186.2 238.5 272.2 Nominal Fan Power Input (Fan 4.92 5.42 7.03 8.10 1.85 2.96 3.87 4.51...
  • Page 76 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 430.0 590.2 739.5 965.9 39.0 58.5 77.7 92.7 118.4 137.4 176.3 201.8 Nominal Fan Power Input (Fan 21.46 28.28 35.33 51.00 1.08 1.71 2.28 2.60...
  • Page 77 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 45.6 68.2 90.6 108.3 138.0 159.9 205.9 235.2 43.0 64.3 85.5 102.1 Nominal Fan Power Input (Fan 1.40 2.35 3.01 3.51 4.90 5.41 7.01 8.33...
  • Page 78 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 130.2 151.1 194.0 222.7 50.3 75.1 99.7 119.1 151.8 175.9 226.6 260.8 Nominal Fan Power Input (Fan 4.40 4.73 6.14 7.14 1.64 2.68 3.52 4.09...
  • Page 79 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 46.7 69.7 92.8 110.8 141.3 164.9 211.0 241.3 54.3 81.2 107.8 128.9 Nominal Fan Power Input (Fan 1.46 2.29 3.03 3.57 4.92 5.42 7.03 8.10...
  • Page 80 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 400V Mechanical Data Capacity Nominal Cooling (Gross) 164.3 192.0 245.2 281.0 445.2 609.3 765.1 1005.2 Nominal Fan Power Input (Fan 6.32 6.88 8.90 10.42 21.46 28.28 35.33 51.00 Gain) Nominal EER 26.0 27.9...
  • Page 81: Mechanical And Electrical Data - 380V

    Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 36.9 55.4 73.9 88.1 112.5 131.0 167.4 192.5 43.1 64.8 86.5 103.1 Nominal Fan Power Input (Fan 1.08 1.71 2.28 2.60 3.71 3.97 5.15 6.05...
  • Page 82 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 132.0 152.7 196.8 224.9 41.1 61.6 82.2 98.0 125.5 145.4 186.9 214.2 Nominal Fan Power Input (Fan 4.90 5.41 7.01 8.33 1.27 2.00 2.68 3.10...
  • Page 83 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 48.1 72.0 96.2 114.6 146.3 169.8 218.5 250.0 45.0 67.3 90.1 107.0 Nominal Fan Power Input (Fan 1.64 2.68 3.52 4.09 5.75 6.27 8.13 9.56...
  • Page 84 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 137.2 159.5 205.0 234.4 52.5 77.8 104.4 125.3 159.9 186.2 238.5 272.2 Nominal Fan Power Input (Fan 4.92 5.42 7.03 8.10 1.85 2.96 3.87 4.51...
  • Page 85 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 430.0 590.2 739.5 965.9 39.0 58.5 77.7 92.7 118.4 137.4 176.3 201.8 Nominal Fan Power Input (Fan 21.46 28.28 35.33 51.00 1.08 1.71 2.28 2.60...
  • Page 86 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 45.6 68.2 90.6 108.3 138.0 159.9 205.9 235.2 43.0 64.3 85.5 102.1 Nominal Fan Power Input (Fan 1.40 2.35 3.01 3.51 4.90 5.41 7.01 8.33...
  • Page 87 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 130.2 151.1 194.0 222.7 50.3 75.1 99.7 119.1 151.8 175.9 226.6 260.8 Nominal Fan Power Input (Fan 4.40 4.73 6.14 7.14 1.64 2.68 3.52 4.09...
  • Page 88 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 46.7 69.7 92.8 110.8 141.3 164.9 211.0 241.3 54.3 81.2 107.8 128.9 Nominal Fan Power Input (Fan 1.46 2.29 3.03 3.57 4.92 5.42 7.03 8.10...
  • Page 89 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 380V Mechanical Data Capacity Nominal Cooling (Gross) 164.3 192.0 245.2 281.0 445.2 609.3 765.1 1005.2 Nominal Fan Power Input (Fan 6.32 6.88 8.90 10.42 21.46 28.28 35.33 51.00 Gain) Nominal EER 26.0 27.9...
  • Page 90: Mechanical And Electrical Data - 460V

    SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 40.0 60.0 80.2 95.5 122.0 142.1 181.6 208.8 46.7 70.3 93.8 111.7 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 1.26 2.00 2.67 3.07 4.38 4.70 6.10 7.11...
  • Page 91 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 143.1 165.6 213.3 244.0 43.7 65.7 87.6 104.3 133.7 155.2 199.3 228.4 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 5.73 6.27 8.13 9.59 1.50 2.38 3.15 3.74...
  • Page 92 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 51.2 76.8 102.6 122.2 156.0 181.2 233.0 266.6 47.4 71.0 94.9 112.7 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 1.93 3.13 4.12 4.82 6.77 7.40 9.61 11.20...
  • Page 93 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 144.6 168.2 215.8 247.2 55.4 81.2 110.2 132.0 168.3 196.3 251.4 286.9 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 5.87 6.65 8.63 9.84 2.20 3.39 4.57 5.42...
  • Page 94 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 427.8 586.9 735.6 960.7 41.9 63.0 83.7 99.8 127.6 148.2 190.1 217.7 Nominal Cooling (Gross) 1460 2003 2510 3278 Nominal Fan Power Input (Fan 19.36 25.66 32.06 46.05...
  • Page 95 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 49.1 73.5 97.8 116.6 148.8 172.6 222.0 253.8 45.4 68.1 90.6 108.0 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 1.63 2.70 3.51 4.07 5.73 6.27 8.13 9.59...
  • Page 96 SmartCool™ Precision Air Conditioning Technical Data Mechanicaland Electrical Data - 460V Mechanical Data Capacity 138.0 160.2 205.7 236.0 53.2 79.6 105.7 126.1 160.8 186.6 240.1 276.4 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 5.19 5.72 7.43 8.54 1.93 3.13 4.12 4.82 6.77...
  • Page 97 Precision Air Conditioning SmartCool™ Technical Data Mechanical and Electrical Data- 460V Mechanical Data Capacity 48.8 73.0 97.3 116.0 148.2 172.8 221.0 253.0 57.0 84.1 113.0 135.1 Nominal Cooling (Gross) Nominal Fan Power Input (Fan 1.74 2.76 3.61 4.38 5.87 6.65 8.63 9.84 2.20...
  • Page 98 SmartCool™ Precision Air Conditioning Technical Data Mechanical and Electrical Data - 460V Mechanical Data Capacity 172.2 201.1 257.0 294.5 444.7 608.6 764.2 1003.4 Nominal Cooling (Gross) 1005 1517 2077 2608 3424 Nominal Fan Power Input (Fan 7.50 8.25 10.71 12.39 19.36 25.66 32.06...
  • Page 99: Commissioning Procedure

    Precision Air Conditioning SmartCool™ Commissioning Procedure General To be read in conjunction with the commissioning sheets provided. Please ensure all documents have been completed correctly and return to Airedale Technical NOTE Support immediately to validate warranty. The unit shall be commissioned with the return air dew point above the water inlet temperature to prevent condensation build up on any unit pipework without pipework lagging.
  • Page 100 SmartCool™ Precision Air Conditioning Fan Section AHU Fan Motor Record the following information on the commissioning sheet: Fan motor size • Drive type • • Is the rotation correct? Motor currents (L1, L2 and L3) • Fan speed • • Overload settings •...
  • Page 101: Maintenance

    Precision Air Conditioning SmartCool™ Maintenance ALL work MUST be carried out by technically trained competent personnel. The equipment contains live electrical and moving parts, ISOLATE remotely prior to maintenance WARNING or repair work. Ensure electrical lock-off procedures are carried out. General Maintenance The maintenance schedule indicates the time period between maintenance operations.
  • Page 102 SmartCool™ Precision Air Conditioning Remove rail to release filter. Fan Access To ensure suitable access for removing and maintaining fans that are located in the floor void, a removable floor tile and support post must be provided when positioned in front of the unit. On A-frame unit designs where the coil drain tube passes through the fan deck, the drain IMPORTANT tube must be disconnected to allow the fan module to be removed.
  • Page 103 Precision Air Conditioning SmartCool™ Fan Removal 1. Remove any external panels by removing fixings. 2. Loosen fixings to lower the fan assembly to the rail for removal, this will clear the fan inlet ring. 3. Pull the fan assembly out. *An additional length of cable is provided to allow fan removal/replacement.
  • Page 104 SmartCool™ Precision Air Conditioning For double fan modules, to replace the rear fan you must first remove the front fan to access the rear fan fixings. The fan will slide out of the front of the unit as one complete assembly, including the inlet ring. 1.
  • Page 105: General Inspections

    Precision Air Conditioning SmartCool™ Maintenance General Inspections General Maintenance - The maintenance schedule indicates the time period between maintenance operations. Access to the various components is via the doors to the front and sides of the unit. Filters - It is good practice to check filters at each maintenance visit. Unit filter condition is monitored via the microprocessor.
  • Page 106: After Sales

    SmartCool™ Precision Air Conditioning After Sales Warranty All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full ‘Parts and Labour’ warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
  • Page 107 Head Offi ce Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel: +44 (0) 113 2391000 Fax:+44 (0) 113 2507219 E-mail enquiries@airedale.com Web www.airedale.com...

Table of Contents