Prier C-633 Installation, Operation & Maintenance Instructions

Commercial wall hydrant

Advertisement

Quick Links

Thank you for purchasing the PRIER C-633/C-634 Commercial Wall Hydrant, the finest quality commercial
hydrant available. Your C-633/C-634 will provide you years of dependable service with little or no maintenance.
Please note: Your C-633/C-634 hydrant has drain holes under the packing nut. After shutoff, the drain holes will
allow water to drain for a few moments to prevent freezing. This is normal and according to design.
INSTALLATION
Installation procedures may vary slightly depending on the seat option purchased and the installation inlet
options. The C-633/C-634 wall hydrant is available with the following inlet options:
Inlet Style
N
P
V
*P and V inlets not available on C-633NSV model
C-634 AND C-633NCC (Straight)
1. No special installation tools are required. Determine the location for installation of the hydrant. This valve
is designed for installation in either horizontal or vertical position. If installing vertically, install with hose
connection in "up" position.
2. Using the template provided on the box, bore a 1-3/8" diameter hole through the wall in the desired position,
and a ¼" alignment hole that is ½" deep.
3. Insert the hydrant through the hole and secure it to the inside wall using the provided wall clamping ring.
Seal through wall penetration if required.
4. Flush all foreign particles from the water line before connecting the hydrant.
5. Connect the water supply piping to the hydrant as desired. With a closed-end hose on the valve creating
back pressure, test the installation for leakage.
6. If planning to solder the hydrant to the supply piping, open the hydrant to the full open position before
soldering. Excess heat to the valve will damage the sealing surfaces on the stem of the hydrant.
C-633NSV (Swivel)
1. No special installation tools are required. Determine the location for
installation of the hydrant. This valve is designed for installation in either
horizontal or vertical position. If installing vertically, install with hose
connection in "up" position.
2. Using the provided template, Bore two holes through the wall and remove
the excess material between those to create an opening for the swivel inlet of
the valve.
3. Align your rotating inlet to the supply piping and secure the valve to the
outside wall. Seal through wall penetration if required.
4. Flush all foreign particles from the water line before connecting the hydrant.
5. Secure the hydrant to the supply piping and test for leakage with a closed-
end hose as described above.
4515 E. 139th Street Grandview, MO 64030 | (800) 362-9055 | PRIER.com
Installation, Operation & Maintenance Instructions for the
PRIER C-633/C-634 Commercial Wall Hydrant
Please leave this sheet for the property homeowner
I
NSTALLATION
1. Determine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
I
NSTALLATION
the interior of the structure for securing the Freezeless
P
I
Hydrant to the waterline.
RIER
NSTALLATION
I
:
NSTALLATION
2. The Prier C-634 is designed for installation in either
1. Determine the location for installation of the Freeze-
1. Determine the location for installation of the Freeze-
horizontal or vertical position. If using vertical installa-
less Hydrant. Be sure there is adequate work area on
less Hydrant. Be sure there is adequate work area on
tion, it is recommended that the hydrant be installed with
the interior of the structure for securing the Freezeless
the interior of the structure for securing the Freezeless
the hose threads in the "up" position. Refer to drawings
Hydrant to the waterline.
Hydrant to the waterline.
to the right for correct installations.
2. The Prier C-634 is designed for installation in either
2. The Prier C-634 is designed for installation in either
3. Using the template provided on the box, bore a 1
horizontal or vertical position. If using vertical installa-
horizontal or vertical position. If using vertical installa-
diameter hole through the wall in the desired position,
tion, it is recommended that the hydrant be installed with
tion, it is recommended that the hydrant be installed with
and a
the hose threads in the "up" position. Refer to drawings
the hose threads in the "up" position. Refer to drawings
to the right for correct installations.
to the right for correct installations.
4. If planning to solder the Freezeless Hydrant to the
supply piping, remove the operating stem before apply-
3. Using the template provided on the box, bore a 1
3. Using the template provided on the box, bore a 1
ing heat to the valve. Heating the valve will damage the
diameter hole through the wall in the desired position,
diameter hole through the wall in the desired position,
sealing surfaces on the stem of the Freezeless Hydrant
and a
and a
/
" hole that is
/
1
1
4
2
5. Flush all foreign particles from the water line before
4. If planning to solder the Freezeless Hydrant to the
4. If planning to solder the Freezeless Hydrant to the
connecting the Freezeless Hydrant. Foreign particles
supply piping, remove the operating stem before apply-
supply piping, remove the operating stem before apply-
may clog the vacuum breaker/backflow preventor caus-
ing heat to the valve. Heating the valve will damage the
ing heat to the valve. Heating the valve will damage the
ing it to fail.
sealing surfaces on the stem of the Freezeless Hydrant
sealing surfaces on the stem of the Freezeless Hydrant
6. Insert the Freezeless Hydrant through the previously
5. Flush all foreign particles from the water line before
5. Flush all foreign particles from the water line before
bored hole and secure the hydrant to the inside of the
connecting the Freezeless Hydrant. Foreign particles
connecting the Freezeless Hydrant. Foreign particles
wall with the provided wall clamping ring.
may clog the vacuum breaker/backflow preventor caus-
may clog the vacuum breaker/backflow preventor caus-
ing it to fail.
7. Secure the Freezeless Hydrant to the supply piping.
ing it to fail.
Test the installation for leakage.
6. Insert the Freezeless Hydrant through the previously
6. Insert the Freezeless Hydrant through the previously
bored hole and secure the hydrant to the inside of the
P
bored hole and secure the hydrant to the inside of the
ARTS
wall with the provided wall clamping ring.
wall with the provided wall clamping ring.
Inlet Specifications
1" MPT x 3/4" FPT
1" Male SWT x 3/4" Female SWT
3/4" ProPress Ready
I
, O
NSTALLATION
PERATION
P
C-634 H
RIER
:
I
, O
, O
NSTALLATION
& M
PERATION
PERATION
AINTENANCE
P
C-634 H
C-634 H
RIER
C
:
EAVY
OMMERCIAL
I
NSTALLATION
I
:
NSTALLATION
/
" hole that is
/
" deep.
1
1
4
2
1. Determine the location for installation of the Freeze-
less Hydrant. Be sure there is adequate work area on
the interior of the structure for securing the Freezeless
/
"
3
8
Hydrant to the waterline.
/
" hole that is
/
" deep.
1
1
O
" deep.
4
2
2. The Prier C-634 is designed for installation in either
horizontal or vertical position. If using vertical installa-
The operation of a Prier C-634 Freezeless Wall
tion, it is recommended that the hydrant be installed with
Hydrant is simple. The Freezeless Hydrant will
the hose threads in the "up" position. Refer to drawings
begin to flow at about 1 full turn of the key and will
to the right for correct installations.
achieve maximum flow at 2
3. Using the template provided on the box, bore a 1
After shutoff, the hydrant will drain water from be-
diameter hole through the wall in the desired position,
hind the packing nut. If the water drains for more
and a
/
" hole that is
1
than 1 minute, the stopper may need to be replaced.
4
Do not overturn when opening or closing the hydrant!
4. If planning to solder the Freezeless Hydrant to the
M
supply piping, remove the operating stem before apply-
:
ing heat to the valve. Heating the valve will damage the
The Prier C-634 Freezeless Wall Hydrant requires no
sealing surfaces on the stem of the Freezeless Hydrant
& M
I
AINTENANCE
NSTRUCTIONS FOR
4515 East 139th Street
C
W
EAVY
OMMERCIAL
ALL
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
& M
I
I
AINTENANCE
NSTRUCTIONS FOR
NSTRUCTIONS FOR
C
W
H
Recommended
EAVY
W
OMMERCIAL
H
ALL
ALL
YDRANTS
Recommended
Recommended
, O
& M
PERATION
/
"
3
Not Recommended
8
P
C-634 H
C
Acceptable
RIER
EAVY
OMMERCIAL
O
:
PERATION
The operation of a Prier C-634 Freezeless Wall
Hydrant is simple. The Freezeless Hydrant will
/
"
3
begin to flow at about 1 full turn of the key and will
Not Recommended
8
Acceptable
Not Recommended
achieve maximum flow at 2
O
:
PERATION
:
PERATION
After shutoff, the hydrant will drain water from be-
The operation of a Prier C-634 Freezeless Wall
hind the packing nut. If the water drains for more
Hydrant is simple. The Freezeless Hydrant will
than 1 minute, the stopper may need to be replaced.
begin to flow at about 1 full turn of the key and will
achieve maximum flow at 2
Do not overturn when opening or closing the hydrant!
/
full turns.
1
2
M
After shutoff, the hydrant will drain water from be-
AINTENANCE
/
"
3
hind the packing nut. If the water drains for more
The Prier C-634 Freezeless Wall Hydrant requires no
8
than 1 minute, the stopper may need to be replaced.
scheduled maintenance for long wear life. If the op-
/
" deep.
1
2
erating stem is removed, replacement of the O-Ring
Do not overturn when opening or closing the hydrant!
on the worm sleeve and worm drive is recommended.
M
AINTENANCE
:
AINTENANCE
The Prier C-634 Freezeless Wall Hydrant requires no
5
6
scheduled maintenance for long wear life. If the op-
4515 East 139th Street
Grandview, MO 64030
(800) 362-9055
Fax (800) 362-1463
4515 East 139th Street
H
Grandview, MO 64030
YDRANTS
(800) 362-9055
Fax (800) 362-1463
YDRANTS
4515 East 139th S
Acceptable
Grandview, MO
(800) 362-9055
Fax (800) 362-14
I
AINTENANCE
NSTRUCTIONS FO
Acceptable
Acceptable
W
H
ALL
YDRANTS
Acceptable
Recommended
1
/
full turns.
2
Accep
/
full turns.
1
2
:
Accep
Not Recommended
O
:
PERATION
The operation of a Prier C-634 Fr
:
Hydrant is simple. The Freezeless
ID
Part No.
Description
begin to flow at about 1 full turn of t
1
300-6003
Valve Stem Cap-Brass
achieve maximum flow at 2
/
full tu
1
2
300-6004
Hose Piece-Brass
2
3
336-0001
O-Ring for Worm Sleeve Buna

Advertisement

loading

Summary of Contents for Prier C-633

  • Page 1 Your C-633/C-634 will provide you years of dependable service with little or no maintenance. Please note: Your C-633/C-634 hydrant has drain holes under the packing nut. After shutoff, the drain holes will allow water to drain for a few moments to prevent freezing. This is normal and according to design.