Electrical Information - Nordyne S5BP Series User Manual

Table of Contents

Advertisement

Model Number
S5BP-
Gross Cooling Capacity (95
o
F) Btuh
1
Net Cooling Capacity - Btuh
1
A.R.I. Rated Airfl ow - C.F.M.
2
Cooling - Effi ciency E.E.R. (Btu/Watt)
3
Cooling - Effi ciency I.E.E.R.
Volts / Phase / Hz.
Operating Voltage
Unit Rated Ampacity
Minimum Circuit Ampacity (MCA)
4
Max. Overcurrent Protection (MOP)
Compressor Data:
Compressor (Scroll)
Volts / Phase /Hz.
Rated Load Amps (RLA)
Lock Rotor Amps (LRA)
Stages / Percent
Crankcase Heater - Qty. / Type
Outdoor Fan Assembly:
Volts / Phase /Hz.
Motor - HP / RPM
Motor Amps
Fan Blade - Diameter / Pitch / # Blades
RPM / CFM (Max. - Total)
Outdoor Coil Assembly:
Area (Ft.
2
)
Rows - FPI
Tube Diameter
Refrigerant Suction Line - Length / OD
Refrigerant Liquid Line - Length / OD
Refrigerant Charge.
Factory Holding Charge - oz
5
Total System with 25' Line Set
High Pressure Switch (PSIG)
Loss of Charge Pressure Switch (PSIG)
Net Unit Weight - Lbs. (No Packaging)
Approximate Shipping Weight - Lbs.
Note: Net capacity includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.
1
Cetifi ed in accordance with A.R.I. Standard 340/360 at 95° F Outdoor DB and 80° F db/67° F wb evaporator entering air at minimum
external duct static pressures allowed by the standard.
2
E.E.R. - Energy Effi ciency Ratio. E.E.R. is determined @ 95° F Outdoor DB & 80° F DB / 67° F WB Air Indoor
3
I.E.E.R. - Integrated Energy Effi ciency Ratio. Cetifi ed in accordance with A.R.I. Standard 340/360.
4
Delay Fuse or HACR Type Curcuit Breakers can be used.
5
Add / Subtract 9.0 oz. of refrigerant per 5 feet change in length from original 25 Ft. lineset total system charge.
6
Requires a 1-3/8" to 1-1/8" reducer line to unit.
Table 4. Electrical Specifi cations & Physical Data - 11.2 E.E.R. - 3 Phase / 60 Hz

ELECTRICAL INFORMATION

090C
208-230V
920888
PERFORMANCE DATA
92,400
90,000
3,000
11.70
11.80
ELECTRICAL RATINGS
208-230 / 3 / 60
187-253
28.3
34.6
50
1 ea.
ZP83KCE-TF5
ZP83KCE-TFD
208-230 / 3 / 60
25.0
164
1 / 100
1 / Band
1 ea.
208-230 / 1 / 60
3/4 - 875
3.3
30" / 22 / 3
850 - 7,200
PHYSICAL DATA & REFRIGERANT SPECS
1 ea.
31.94
2 - 16
3/8" OD
0 - 75 Ft. / 1-1/8"
0 - 75 Ft. / 1-1/8"
76 - 100 Ft. / 1-3/8"
(6)
76 - 100 Ft. / 1-3/8"
All Lengths - 5/8" OD
All Lengths - 5/8" OD
R410A
90
416
386
420
090D
120C
460V
208-230V
920889
920890
92,400
121,700
90,000
117,000
3,000
4,000
11.70
11.20
11.80
11.50
460 / 3 / 60
208-230 / 3 / 60
414-506
187-253
13.9
33.4
17.0
40.9
25
70
1 ea.
1 ea.
ZP103KCE-TF5
460 / 3 / 60
208-230 / 3 / 60
12.2
30.1
100
225
1 / 100
1 / 100
1 / Band
1 / Band
1 ea.
1 ea.
460 / 1 / 60
208-230 / 1 / 60
3/4 - 875
3/4 - 875
1.7
3.3
30" / 22 / 3
30" / 26 / 3
850 - 7,200
850 - 8,000
1 ea.
1 ea.
31.94
38.33
2 - 16
2 - 18
3/8" OD
3/8" OD
0 - 100 Ft. / 1-3/8"
(6)
All Lengths - 5/8" OD
R410A
R410A
90
90
416
520
Cut Out: 650 +/- 15
Cut In: 460 +/- 15
Cut Out: 5 +/- 5
Cut In: 20 +/- 5
386
423
420
457
120D
460V
920891
121,700
117,000
4,000
11.20
11.50
460 / 3 / 60
414-506
18.4
22.6
35
1 ea.
ZP103KCE-TFD
460 / 3 / 60
16.7
114
1 / 100
1 / Band
1 ea.
460 / 1 / 60
3/4 - 875
1.7
30" / 26 / 3
850 - 8,000
1 ea.
38.33
2 - 18
3/8" OD
(6)
(6)
0 - 100 Ft. / 1-3/8"
All Lengths - 5/8" OD
R410A
90
520
423
457
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

S5bp-090cS5bp-090dS5bp-120cS5bp-120d

Table of Contents