CHAPTER 4
SERVICE AND
MAINTENANCE
Condensate pump AIR1-KP

4.0 Service and maintenance

The condensate pump must be checked for dirt and damage every 6 months.
Remove the acquisition unit cap and magnets. Clean the inside of the detection unit and the
float with water and 5 % bleaching agent. Rinse thoroughly after using a cleaning agent. Then
reinsert the float with the black dot at the top and the filter (Fig. 9). Reattach the cap in the
correct direction and perform a complete functional test.
Fig.9