INSTALLATION GUIDE
1 Channel Timer
Model: TC1
SPECIFICATIONS
Power supply
Terminals
Output
Programming
Programming resolution
Operating temperature
Storage temperature
IP Rating
Relay capacity
Operating humidity
Width
Maximum Load
Backup Battery life/type
Dimensions
DISPLAY
240Vac (-15% to +10%)
50/60Hz
2
1 x 4mm
cable maximum
Normally open relay
Weekly (a different program for
every day of the week), or Daily
(same program each day)
30 minutes
-20 to +50 ° C
-10 to +70 ° C
IP20
16A @ 240Vac
-20 to 90% non-condensing
1 DIN module wide
LED 500 VA
Incandescent 2000 W
Fluorescent 250 VA
Low voltage halogen 1000 VA
Halogen (240 V) 2000 W
CFL 200 VA
4 years/Lithium CR-1632
18 mm wide x 91 mm high x 65
mm overall depth
TYPICAL CONNECTIONS
UNSWITCHED
ACTIVE
INSTALLATION
The device comes with the backup battery inserted. Therefore, if
required, the timer can be switched on and programmed without
a mains connection. To turn the timer on without a mains
connection, press the PRG button.
Note that when programming without a mains connection, the
LED backlight display and relay will not operate.
The backlight display will turn on when the device is mains
powered and remains on while mains is connected.
MANUAL RELAY SWITCHING
To change the state of the relay output (from ON to OFF or vice
versa) press the ▼ button. The state is maintained until the ▼
button is pressed again or until the next programmed switching.
Locking the relay output
To lock the current relay output state and prevent it switching,
press the ▼ button for 3 seconds.
In this condition the
symbol is lit.
To unlock, press the ▼ button for 3 seconds.
BATTERY REPLACEMENT
When the backup battery is low the device displays 'bAtt CHG'
and the battery should be replaced as soon as possible.
DEFAULT PARAMETERS
The default parameters are:
•
Geographical Zone: 1 (Australia)
•
Automatic Summertime / Wintertime change: OFF
To reset to factory defaults
To reset the timer to factory defaults
From the main screen, press all three buttons (▼PRG )
•
simultaneously with a pen or similar for at least 3 seconds.
•
'dEF' (flashing) will appear on the screen,
•
When dEF is seen flashing, press the PRG button to
confirm the reset
•
If the PRG is not pressed within 5 seconds, the timer
returns to the main screen without performing a reset.
LOAD
(switched Active
1 2
controlled by timer)
3 4
NEUTRAL
NOTE
•
Before you access the battery
compartment, disconnect mains.
•
So that the date and time is not
lost, replace the battery within one
minute of removing it.
•
Only use a CR-1632 type battery