Cooper Crouse-Hinds Pro-flood PFM Series Installation & Maintenance Information

25l industrial led floodlight

Advertisement

Quick Links

Pro-Flood LED Floodlight
PFM Series 25L Industrial LED Floodlight
Installation & Maintenance Information

APPLIcAtIon

Pro-Flood LED Floodlights construction is designed for use indoors and outdoors in marine and wet
locations, where moisture, dirt, corrosion, vibration and rough usage may be present.
• UL1598 Luminaires, UL1598A Marine, UL8750
• Wet Locations, NEMA 4X
• IP66
• cUL
to avoid the risk of fire, explosion, or electric shock, this product should be
installed, inspected, and maintained by a qualified electrician only, in accordance with all
applicable electrical codes.
to avoid electric shock:
Be certain electrical power is OFF before and during installation and maintenance.
to avoid burning hands:
Make sure lens and lamp are cool when performing maintenance.
to avoid potentially unsafe operating conditions:
Make sure the supply voltage is within the floodlight voltage range stated on the nameplate.
Do not operate in ambient temperatures above those indicated on the floodlight nameplate.
Use only replacement parts from Cooper Crouse-Hinds.
Use proper supply wiring as specified on the floodlight nameplate.
All gasket seals must be clean.
Before opening, electrical power to the floodlight must be turned off. Keep tightly closed
when in operation.
Do not position the floodlight beyond the aiming range limits.
Do not exceed the maximum allowable current draw of 15 Amps when daisy chaining
floodlights, (S886 configuration only).

InStALLAtIon

Mounting

Yoke Mount - Post Mount Using Floodlight Yoke only
1.
Select a durable, corrosion resistant mounting surface capable of supporting the fixture's 50
lb (22.7 kg) weight and cantilevered mass (as applicable).
LINE IN (BLK)
NEUTRAL (WHT)
GROUND (GREEN)
IF 1664 • 05/13
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARnInG
WARnInG
WARnInG
DRIVER
INPUT
LINE IN (BLK)
NEUTRAL (WHT)
DRIVER
INPUT
LINE IN (BLK)
NEUTRAL (WHT)
Figure 2 - Wiring Diagram
Copyright © 2013, Cooper Industries, Inc.
Pro-Flood LED Floodlights are supplied for use with a choice of voltages:
• 100VAC – 277VAC, 50/60Hz and 127VDC – 250VDC
• 277VAC - 480VAC, 50/60Hz
2.
Using the floodlight yoke as a template, mark and drill desired location on mounting surface.
3.
Secure floodlight yoke to mounting surface by applying proper torque to corrosion resistant
1/2 in bolts or lag screws accompanied by lock washers.
4.
Ensure that the safety chain is securely fastened between the yoke bracket and back cover.

WIRInG

Wiring the Floodlight
1.
All components in the fixture are prewired so only line in, neutral, and ground need to be
connected in the fixture to the terminals per the wiring diagrams using methods that comply
with all applicable codes. Use supply cord with outer sheath diameter in accordance with
Table 1. Terminate the equipment grounding conductor (green) first, the common (white)
next, and finally, the line voltage (black) last. Secure all electrical connections.
Gland name PFM25L ordering Suffix thread type cable Diameter Range
NCG75-75
CAP816604
CAP816794
OUTPUT
V+ (RED)
+
V- (BLK)
-
OUTPUT
V+ (RED)
+
V- (BLK)
-
table 1
S886
3/4 in NPT
0.35 - 0.75 in (8.9 - 19.0 mm)
M20
M20 x 1.5
8.5 - 16.0 mm (0.34 - 0.62 in)
M25
M25 x 1.5
8.5 - 16.0 mm (0.34 - 0.62 in)
Figure 1
LED CIRCUIT BOARD
-
LED CIRCUIT BOARD
+
LED CIRCUIT BOARD
-
LED CIRCUIT BOARD
+
IF 1664
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Pro-flood PFM Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Cooper Crouse-Hinds Pro-flood PFM Series

  • Page 1 8.5 - 16.0 mm (0.34 - 0.62 in) Do not operate in ambient temperatures above those indicated on the floodlight nameplate. Use only replacement parts from Cooper Crouse-Hinds. Use proper supply wiring as specified on the floodlight nameplate. All gasket seals must be clean.
  • Page 2 VERTICAL REPLAcEMEnt PARtS Cooper Crouse-Hinds Pro-Flood LED Floodlights are designed to provide years of reliable lighting performance. However, should the need for replacement parts arise, they are available through your authorized Cooper Crouse-Hinds distributor. Assistance may also be obtained through your...
  • Page 3 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

This manual is also suitable for:

Champ pro pfma

Table of Contents