Prepare the Job File
6
Create a list of the ISD's and their location—using a laptop
·
Laptop and barcode
scanner: Pre-load the Signalink System Configurator (SSC)
software provided on CD with each system. Run SSC on the laptop. Note: the
laptop with barcode scanner is not essential, but is highly recommended for speed
of installation, accuracy of information, and to have a computer record of the job
details. A Barcode Scanner and the Cable Adapter are available in the DEALER KIT
·
Scan the VID number of each ISD
and write its intended location on the back label
·
Enter the job file, and set up the
system: Consult
a laptop, also consult
077.0046: Signalink System Configurator User's Manual
NEED HELP? CALL TECH SUPPORT (888) 765 7514
Install the ISDs in each suite (See ISD Installation Q/S Guide)
7
·
Introduce yourself: and tell the resident what you are doing
·
Select a suitable AC outlet for best audibility, plug it in. CAUTION!
BUZZER
DO NOT PLUG IT INTO AN AC OUTLET THAT CAN BE SWITCHED
OFF! FIX THE AC RECEPTACLE IF NEEDED FOR GOOD CONTACT
·
If no-one is sleeping, press TEST and let them hear the alarm
·
Explain the light will go green when the system is running
DO
·
Anchor each ISD using 4
screws, if permitted
·
Check for a one flash per
second blinking yellow
STATUS light after plugging
the ISD into a receptacle
·
Press the TEST button after
plugging the ISD into a
receptacle to test the alarm
TEST button
·
Instruct the tenant what the
STATUS light
device is and what it does
8
Enroll the ISDs and Test & Verify System Operation
·
Ensure the system time and date is set correctly, and clear all the log files
·
Consult
077.0045 NMC Programming Manual
the ISDs is fully automatic, and allows the NMC to verify that all ISDs are communicating
properly, and that they have good AC power, a good battery, and that the buzzer is working
properly (and strobe if fitted).
·
Test the complete system using the
ISD TEST ALL
·
If using the laptop, create and save a
9
Explain the System to the Building Manager
·
Give him or her document 077.0025: Building Manager's Guide.
troubles and how to resolve local troubles caused by residents' behavior
·
Explain the trouble log "LOG" and "VIEW"
©2011 Signalink Technologies: Fire-Link Quick-Start Guide
077.0045 NMC Programming Manual.
support@signalink.com
Do NOT:
·
Place the ISD over a
source of heat such as a
base board heater or hot air
register
·
Place the ISD in direct sunlight
·
Install the ISD into a switched
receptacle
·
Forget to leave behind the
resident's instruction "sleeve" to
advise the resident what the
device is and what it does
for Enrolment instructions. The act of enrolling
function
Commissioning Report
Explain how to silence
features: to see which suite is in trouble
Before going on-site: READ THIS SYSTEM GUIDE FIRST!
1
Make sure you have the appropriate training, and a site survey
Fire-Link is relatively simple to install. Nevertheless, it is a system and the installer needs to be
trained. Inadequate training leads to bad installations and unsatisfied customers:
Before making a sale, a Site Survey should be written up
If using
submitted to Signalink Technical Support.
installation will be fast and easy. Download from our website
Submit Site Surveys to:
Signalink has an on-line training and certification process on its website, and is available
by email.
satisfied customers, and will save your organization time and money
2
NMC-101
Panel
1 per system
(Connects to
existing Fire Alarm
)
Control Panel
Dealer Kit includes these items
Barcode
If your laptop has no
scanner:
Makes
life much easier!
Technical Support:
(888) 765 7514
Page 4
QUICK-START GUIDE
An approved survey ensures that your
support@signalink.com
Please take the time to get trained!
It only takes a short while, will give you
INSTALLATION ESSENTIALS
CHECK YOU HAVE EVERYTHING YOU NEED
CHK-400
TPC-101
Choke
3-Phase Coupler
1 per system
1, 2, or 3 per system
(provides filtered
(one for each
power to NMC
)
transformer)
USB-Serial
Instruction
Adapter Cable
Manuals
are provided in
DB9 serial port, you
hard-copy and on
will need a USB-
the CD sent with
On the CD shipped
serial adapter
every system
with every system
www.signalink.com
Signalink Technologies Inc.
14-2550 Acland Road, Kelowna BC, Canada, V1X 7L4
©2011 Signalink Technologies: Fire-Link Quick-Start Guide
after inspecting the building, and
www.signalink.com
(250) 491 3895
Fax
ISD 2501UW or ISD-2501UWS
Horn only or
Horn & Strobe
In-Suite Device (ISD)
1 per suite or bedroom,
or as per AHJ's instructions
Laptop
Laptop SSC
You will need to
software
provide a laptop. It
makes the job much
faster
077.0061 Rev 1, Aug 2011
Page 1
Need help?
Do you have a question about the FIRE-LINK II and is the answer not in the manual?
Questions and answers
What does a flashing yellow status light mean and does it stay flashing all the time?
A flashing yellow status light on the Signalink FIRE-LINK II indicates that the ISD is properly plugged into a receptacle. It blinks once per second and continues flashing as long as the unit is powered and operating normally.
This answer is automatically generated
What does a flashing status light mean
A flashing yellow status light on the Signalink FIRE-LINK II indicates that the ISD is operating correctly after being plugged into a receptacle.
This answer is automatically generated