  • Page 2 Control head ASi-Bus ES/ABSL 5630 xxx 010-000 with platine V4.x for Double seat valve Single seat valve Butterfly valve Ball valve KIESELMANN GmbH Paul-Kieselmann-Str.4-10 D - 75438 Knittlingen   +49 (0) 7043 371-0 Fax: +49 (0) 7043 371-125 ...
  • Page 3: Table Of Contents

    1. List of contents List of contents ......................2 Information for your safety..................... 3 Marking of safety instructions in the operating manual ..........3 Variants of control heads ASi-Bus ES/ABSL..............4 Double seat valve (pneum. Lifting valve) ............4 Single seat valve (pneum. Lifting valve).............. 4 Butterfly valve / Ball valve (pneum.
  • Page 4: Information For Your Safety

    2. Information for your safety We are pleased that you have decided for a high-class KIESELMANN product. With correct application and adequate maintenance, our products provide long time and reliable operation. Before installation and initiation, please carefully read this instruction manual and the security advices contained in it.
  • Page 5: Variants Of Control Heads Asi-Bus Es/Absl

    4. Variants of control heads ASi-Bus ES/ABSL 4.1 Double seat valve (pneum. Lifting valve) Valve function Electrical connection Solenoid valves Article No. without lifts 1 solenoid valve 5630 201 010–000 with upper seat lift 2 solenoid valves 5630 202 010–000 Plug M12 4-pin Socket plug M12 5-pin with lower seat lift...
  • Page 6: Safety Instructions

    5. Safety instructions 5.1 Field of application The control heads are used to pilot valves of production systems of the beverage and foodstuff industry, pharmaceutical industry, bio-technology, and chemical industry. They contain the complete actuator, sensory, and electronic technology for connection and integration to up-dated and efficient control systems.
  • Page 7: Initial Operation

    ES way. Encoding takes place from the Kieselmann society. The counter is sealed after the choice. A suitable mark of the type of the manage- ment is indicated on the frame.
  • Page 8: Electrical Installation

    = Butterfly / Ball valve air open/air closed LED 5 Red Valve closed = Butterfly / Ball valve air closed/spring open = reserved KIESELMANN LED 6 Green Valve open = reserved KIESELMANN LED 5 / LED 6 Flashing alternately indicates...
  • Page 9: Electrical Connection Design Of Control Head Asi-Bus Es/Absl

    11.4 Electrical connection design of control head ASi-Bus ES/ABSL = Valve selector switch for valve type see Tab.1 = Selector switch: Position 1 Standard Position 2 ES-mode = Plug electrical connection for solenoid valve (MV) P1 = JTAG Interface (Onbord programming) P2 = Plug ASi-Bus 24V (+) braun/brown...
  • Page 10: Position Control And Position Indication

    12. Position control and position indication 12.1 Lifting valve The repeat signal message ‘valve opened‘ or ‘valve closed‘ occurs contactless through the magnet field of the pulse initiator‘s toric magnets at coverage of the Hall sensors on the board.  NOTE The installation position of the pulse generator is characterized by a marking in the spindle.
  • Page 11: Rotary Valve

    12.2 Rotary valve The stop position feedback signal valve "OPEN" or "CLOSED" is carried out contactlessly over the magnetic field of the bar magnets in the pulse generator during overlap with the hall sensors on the printed circuit board. Valve Position Indicator ➣...
  • Page 12: Electrical And Pneumatical Piloting Asi-Bus Es/Absl

    13. Electrical and pneumatical piloting ASi-Bus ES/ABSL  NOTE • Connect power supply and connect control air. Check valve functions. 13.1 Valve piloting - Double seat valve Valve selector Valve function Solenoid valve (MV) switch position (D) Valve without lifts MV 1 Valve with upper lift MV1 / MV3...
  • Page 13: Valve Piloting - Lifting Valve

    13.2 Valve piloting - Lifting valve Valve selector Valve function Solenoid valve (MV) switch position (D) air open / spring closed MV 1 air closed / spring open MV 1 air open / air closed MV1 / MV3 Bit-assignment Valve function Solenoid valve Pneum.
  • Page 14: Valve Piloting - Rotary Valve

    13.3 Valve piloting - Rotary valve Valve selector Valve function Solenoid valve (MV) switch position (D) air open / spring closed MV 2 air closed / spring open MV 2 air open / air closed MV2 / MV3 Bit-assignment Valve function Solenoid valve Pneumatic INPUT...
  • Page 15: Demontage Und Montage

    14. Disassembly and assembly 14.1 Disassembly • Disconnect the compressed-air pipe, control air pipe and elec- trical lines from the control head. • Unlock the cab (21) by rotary movement and lift it (bayonet socket). 1) - when replacing the valve actuator •...
  • Page 16: Spare Parts List

    15. Spare parts list Item. Article No. Designation Dimension Material 5630 000 004-152 Position indicator ----- ABS gn 5630 200 012-000 Board ASi-Bus AB-Slave ----- ----- 2304 094 023-158 O-Ring ø94x2,3 MVQ bl 65 a 8095 006 016-020 Socket head cap screw DIN912 (2x) M6x16 1.4301 / AISI 304 b 2304 006 012-078 O-Ring...
  • Page 17: Technical Data

    16. Technical data Bus-system: Control of valve position Principle of effectiveness: 1 - 62 AB-Slave Function of evaluation: -10°C to +50°C Range of address: II (Control head with cap transparent) I (Control head with cap stainless steel) Operating temperature: IP 67 (Control head with cap transparent) IP 65 (Control head with cap stainless steel) Appliance classes: 22 - 30V DC...