INSTRUCTION SHEET
ESE REMOTE TESTER for RT models, (SIREMOTETESTER)
Description and Purpose
Remote detection of the operation status for Early Streamer Emission RT Terminal (ESE RT) models by luminous
information. Easily test the state of an nVent ERICO System 1000 Early Streamer Emission Terminal while on-site.
Instructions for Use
The SIREMOTETESTER works only in sunlight (minimum of 3300 lux of luminosity) and a minimum power load.
View the bottom of the device up to 100m away for a maximum of two minutes until LED light flashes, then proceed
according to the color indication.
Function of Indicators
1
3 4 5
2
Electrical Specifications
•
Self-powered with an included photovoltaic cell
•
Does not include a battery, increasing the device's lifespan
•
Tested with Impulse Current (I
Features
•
Waterproof: IP68
•
Dimensions: Length 80 mm, Depth 84 mm, Height 180 mm.
•
Weight: 1.25 Kg
Inspection Schedule Guidelines
To ensure proper maintenance, follow the required test schedule in section 8 of NFC 17-102 standard, on Table 7
(periodicity of inspection regarding the protection level).
Lightning Protection
Level
I and II
III and IV
NOTE:
Please adapt to the local regulations if more restrictive.
Electrical testing of the installation should be performed once a year.
TECHNICAL SUPPORT:
www.nVent.com
1.
Connection terminal for cables connecting to the ESE RT (ex. SI60I316RT).
2.
Conection to mast SIM28A2 or SIM28A2316.
3.
Red
LED (2 flashes at 1 second, every 2 minutes max) indicates:
ESE RT is out of service and needs to be replaced
4.
Green
LED (2 flashes at 1 second, every 2 minutes max) indicates:
ESE RT is operational
5.
Yellow
LED (2 flashes at 1 second, every 2 minutes max) indicates:
SIREMOTESTER operating problem is detected and requires attention or replacement*
*Note 1: Excludes charging issue or an insufficient charge level.
*Note 2: Immediately after assembly of the ESE RT and SIREMOTETESTER it will take up to 30 minutes
with sufficent sunlight for the tester to be operational, or 10 minutes with a high lumen flashlight.
*Note 3: A test cycle of the ESE RT is made every 3 hours after the SIREMOTETESTER is fully charged
and has sufficient sunlight.
Note 4: We recommend assembly 1 day before any job site installation, placing the assembly in sufficient
*
sunlight, so at least 1 test cycle can be completed.
) 100 kA, 10/350 µs.
imp
Visual
Complete
inspection
inspection
1 year
2 years
2 years
4 years
IP9021_A
Critical systems
In case of structures
complete inspection
with a risk of explosion
1 year
6 months
1 year
N/A
1 of 6
2022 nVent All Rights Reserved
Inspection after a
lightning event in
the structure
Complete
Visual