Page 1
This IOM contains confidential information and is issued in confidence on the condition that it be returned on demand and not be copied, reproduced, disclosed to others or used in manufacture of the subject matter thereof without the written consent of Westlock WESTLOCK CONTROLS CORPORATION 280 N.
Page 2
Phone: 011-44-189-251-6277 •Fax: 011-441-892-516279 Email: sales@westlockuk.com Internet: http://www.westlockuk.com South America Westlock Equipamentos de Controle Ltda. Sales: Operations: Al. Araguaia, 2044 – Sl. 1101, Bloco B Av. Antonio Bardella, 3000 Edifício CEA – Alphaville Galpões 2A e 2B – Alto da Boa Vista Barueri –...
Page 6
Appendix E - Grounding Schematic ..............198 Appendix F – Controlled Drawing ..............199 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 6 of 206...
Page 7
Appendix G – Procedure to Reset the Non-Volatile Memory to Factory Settings ......................201 Appendix H - Controlling the ICoT PA Position using the Proficore Ultra Interface, ProfiCaptain software ................. 202 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Disconnect power to and the inlet air supply before conducting any service or maintenance. Avoid the introduction of any contaminants into the manifold/valve assembly. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Current consumption of the ICoT is 12.5mA with an operating voltage of 9 – 32 Vdc. The ICoT PA version allows calibration and access to on-line diagnostic information via hand-held terminal or through software.
1.4 Principles of Operation 1.4.1 Enclosures The ICoT PA Positioner can be built in three different enclosure materials: engineered resin, 316 stainless steel and aluminum. Housing Material: Housing Material: 316 Stainless 1.4.2 Position Feedback Non-Contact Position Feedback To provide consistently accurate performance information, all linkages, levers and connecting rods, from the positioner to the control valve have been eliminated from the design.
Special Features On-Board Sensors The ICoT PA positioner has the capability to monitor its operation. If an error or failure condition occurs, it will be displayed on the local LCD, or if the positioner is supplied with a PA interface, the error codes will be displayed on a hand held terminal or a PC maintenance station.
- EMC requirements 3 Order Guide The ICoT PA positioner is designed to handle a wide range of control valve applications. Please use the following ordering guide to help choose the ICoT positioner that best suits the application. ICoT 5500 (ICoT PA) Positioner Ordering Guide...
Note: When ordering a liner ICoT PA positioner, (option “1” for the third digit in the part number). Be prepared to supply the exact stroke length and fail direction of the application. 4 Definitions This section contains definitions to all acronyms or abbreviations used in this document.
Page 16
Remote-Output mode Software Transducer Block TCP/IP Transport Control Protocol/Internet Protocol Virtual Communication Relationship Virtual Field Device WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 16 of 206...
Page 17
Electronic Device Description (EDD) For the complete list of definitions please see the Profile for Process Control Devices - Version 3.02 - April 2009 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 18
FDT is a technology where it standardizes the communication between the device and the application to provide sophisticated views of the device data for configuration, maintenance and operation. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
If actuator does not have a tapped hole, fasten using set screws on side of coupler. (See Figure 5-1) Figure 5-1 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 20
Output Port 1 is piped to turn the actuator clockwise Placed at 9:00 Placed at 6:00 Figure 5-2 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Output Port 1 is piped to turn the actuator clockwise Placed at 9:00 Placed at 6:00 Figure 5-3 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 22
Wire the positioner sensor back to the positioner using the cable provided and replaces cover. (See Figure 5-4). Figure 5-4 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
1/8” from the back of the positioner (1/16” is ideal), (See Figure 5-5) Figure 5-5 Note: For Fisher actuators model 657 & 667 sizes 34 thru 70, Westlock can supply a slotted mounting kit design. This will allow the user to easily center the positioner sensor between the limits of the magnet assembly’s stroke.
Page 24
4. Lastly, mount the positioner to the bracket so that the positioner sensor (nose) of the ICoT lines up with the midpoint mark. (See Figure 5-6). WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
(See Figure 5-7) Figure 5-7 Note: For Fisher actuators model 657 & 667 sizes 34 thru 70, Westlock supplies a slotted mounting kit design, to ease the mounting process. This will allow the user to easily center the positioner sensor between the limits of the magnet assembly’s stroke.
Page 26
Wire the positioner sensor back to the positioner using the cable provided and replaces cover. (See Figure 5-8). Figure 5-8 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
5.8 Calibration The ICoT PA positioner has an on-board menu structure that can be accessed by pressing the Cal button. Exit any function by pressing both up and down arrow buttons simultaneously, anytime during calibration. If up and down arrow buttons are pressed simultaneous, while in the main screen it goes to PASSWORD screen, as shown below.
ACAL Manu. This Calibration is adequate for most applications. If no advanced calibration is required proceed to Section 5.8.3 to exit calibration. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Menu name only (MCAL Lo, etc.), press the up arrow key once to enter the Menu level and once more to exit CAL mode. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
(Configuration Routine Shown Below). Enter Cofg menu and change any of the parameters, if other than the factory settings are needed. The factory settings are shaded. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
The address 126 is reserved for new devices; The address 0 should be reserved WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 34 of 206...
(ACAL). The PID entry allows the user to modify the tuning parameters in two different ways: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 37
The EQUAL PERCENTAGE VALVE POSITION % OF TRAVEL WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 37 of 206...
Page 38
Position will display a modified value, not the actual Setpoint sent to the ICoT PA. For instance if Quick Opening is selected and a Setpoint of 20% is sent to the ICoT PA the LCD will display %SP 36.9 and when it reaches position (at 36.9% open) it will display %PS 36.9.
Page 39
This function sets the valve to the fully energized position via the keypad (Outlet Port 1 = Supply psi & Outlet Port 2 = 0 psi). This function places WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
F) The ICoT PA was designed to be used according to the PA specifications. For more details of how to setup the installation of the ICoT PA as well as any other PA device please refer to the following standards: ...
If the supply pressure is above 40 PSI a high pressure ICoT positioner must be used. If the supply pressure is below 40 PSI a low pressure ICoT positioner must be used. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
On loss of power the positioner fails full air pressure to output port 2. If this does not happen the positioner is damaged. Contact factory. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
If the cause for the Integrator Overflow error cannot be diagnosed, please contact Westlock for support. Please make sure that the valve is not stuck or if there is no air leakage in the actuator-positioner connections or if the working pressure is too different (50%) from the calibrated pressure.
Page 45
Remove power for at least 1 minute, perform a factory driver default (see Appendix I) and retry the calibration Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 46
Try to replace the Hall sensor and/or the magnet Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 46 of 206...
Page 47
Remove power for at least 1 minute, perform a factory calibration default (see Appendix H) and retry a full auto CAL Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 48
(see 17 - Appendix G – Procedure to Reset the Non-Volatile Memory to Factory Settings) and retry a full auto CAL Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 49
(see 17 - Appendix G – Procedure to Reset the Non-Volatile Memory to Factory Settings) and retry a full auto CAL Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 50
(see 17 - Appendix G – Procedure to Reset the Non-Volatile Memory to Factory Settings) and a full auto Call factory for additional support WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 51
Message Meaning Solution Calibration Calibration No action aborted aborted by the user WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 51 of 206...
Normal Mode – This field displays the mode that the function block is expected to be in during normal use. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 54
Notes: A – When the Transducer Block is in Man mode the AO channel is not processed and the valve position can be set by the working sp transducer parameter (WORKING_SP) WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
2 – the valve set point will be set to open position; 3 – The valve set point will be set to value assign to FAULT_STATE_VAL transducer parameter. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
8.3.7 The Physical Block The Physical block contains parameters to show and/or manipulate device hardware itself and firmware specific characteristics associated with the ICoT PA. The Physical block contains no direct WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
The Transducer block contains configuration parameters that are used when connecting function blocks to the ICoT PA physical input and output values. The Transducer block also performs functions, such as calibration, linearization, and scaling on I/O data to convert it to a form that will be usable on the Fieldbus network.
Page 58
- 100% Dynamic Speed custom – speed defined by Travel Time Close SP_DEVIATION_DB TRD Alert Group directory - Setpoint Deviation Dead band WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 59
Pressure Port A (as a percentage of the air pressure measured during (PRESSURE_A) calibration) Internal Temperature The ICoT PA module internal temperature as measured by (INTERNAL_TEMP) an on-board temperature sensor (°C) 8.3.8.3 Complete list of parameters of the Transducer Block Table 8-6...
Page 60
It helps to identify the location (plant unit) of an event. TARGET_MODE The TARGET_MODE WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 60 of 206...
Page 62
This takes place independent of the definition of a fail safe WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 63
RCAS_IN. Based on this set point the normal block algorithm determines the primary output value. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 64
Auto 3 Cas 2 (not used) RCas 1 ROut 0 ñ lowest (not used) The state machine defining WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 64 of 206...
Page 65
For this profile the current state part of the alarm is used only. ACT_STROKE_TIME_DEC Minimum of time to move WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 66
A valid entry has at least one value, X or Y, different of WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 67
(depending on the fail-safe position). SETP_CUTOFF_INC If the reference variable WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 67 of 206...
Page 68
T parameter for a value close with the new rate defined. TRAVEL_RATE_INC Configurable time of full span change (opening time of the WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 69
Name of Actuator- Manufacturer. VALVE_TYPE Type of valve. ACTUATOR_TYPE Type of actuator. Coding: 0: electro-pneumatic WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 69 of 206...
Page 70
WORKING_POSITION and POSITION FLOP Invert the HALL sensor value (WORKING_POSITION parameter). SIGNAL_ACTION Reverse the Servo PID WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 70 of 206...
Page 71
INTERNAL_TEMP_UNIT. XD_COMMAND Used to start part of auto calibration - HALL sensor WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 71 of 206...
Page 72
INTERNAL_TEMP <= INTERNAL_TEMP_MIN 3:DEVIATION - ON if the following sentence are TRUE for more than SP_DEVIATION_TIMEOUT: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 72 of 206...
Page 73
"-40ºC" the indication of TEMP_MAX_MIN alert. INTERNAL_TEMP_MAX Maximum temperature to 80ºC start the indication of WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 73 of 206...
Page 74
CLOSE_TIME_INTERVAL Last time interval to travel from opened to closed WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 74 of 206...
Page 75
CURVE_ENTRY_X_Y1_Y2 Array of values of the point 0,0,0 selected by the CURVE_SELECTION and WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 75 of 206...
Page 76
SPSR test. SPSR_STABLE_TIME Measured time in which the valve took to reach and stabilize at the SPSR_SP WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 76 of 206...
Step Response test. 8.3.9 Analog Input Block The Analog Input (AI) function block reads an ICoT PA input measurement via a specified I/O channel (in this case the actual measured valve position) and makes that data available to other Fieldbus function blocks.
8.3.10 Analog Output Block The Analog Output (AO) function block assigns a Fieldbus output value to the ICoT PA via a specified I/O channel (in this case it is the setpoint for the target position of the valve). The channel parameters must be set for the block to work properly.
When the PROFIBUS master detects a device is starting it automatically starts the cyclic data exchange. During the configuration phase the system gets from the GSD file the modules that are available for the cyclic data exchange. The ICoT PA has the following modules for the AO block: ...
Page 80
Set point value: defines the position of the regulation unit within the travel span (between the OPEN and CLOSED position) in units of Input Value. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 81
Value (OUT): Value of valve position from analog output block Status (OUT): Status of valve position from analog output block WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
The user needs an FTD application and a communication DTM installed to be able to work with the ICoT PA DTM. It is out of scope of this manual to show how to install a FDT application and how to install a communication DTM.
Page 83
Select “I accept…” and click “Next” at “License Agreement” dialog if you agree, or click “Cancel” to abort the installation; WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
And click “Next” again to start the file installation; And then click “Finish” at “Installation Wizard Complete” to close the setup. The ICoT PA DTM is installed after updating the FDT/DTM device catalog this DTM will be showed there. 9.2.2 Creating a PACTware project ...
Page 85
Right click over Communication DTM to add a device DTM; Click over “Add Device”; Choose ICoT PA to create the device into PACTware project; WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 86
DTM. Please refer to communication DTM supplier documentation for details; Right click over the ICoT PA and choose “Connect” to start the communication; WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Double click over ICoT PA to open the “#Parameterization”; At “Read Parameters from Device” choose “Read all parameters from device”; Now the DTM has all data from device and it is able to make changes. 9.2.3 Writing Data to Device To write all parameters to a specific directory, just press in the tool bar the “Write...
Page 89
If enabled, simply drag the selected scale to the new position. Delete curves Clear the displayed curve from the graph. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Manufacturer: Identification of device manufacture. Westlock manufacture ID is 77. The DTM will show the text “Westlock Controls”. Device ID: Westlock device identification. The DTM will show the text “ICoT PA”. Device Serial Number: Unique serial number WESTLOCK CONTROLS CORPORATION 280 N.
9.3.2.1 Basic Setup A sub directory of Parameters/Transducer, it has a group of initial configuration parameters. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 92
Deadband: Valve position dead band in general. This is used as dead band for the travel alert, setpoint deviation alert, LCD position filter, close position deviation alert and full stroke time measurement. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 93
Feedback Source: Select which position value will be copied to FEEDBACK_VALUE parameter. The available sources are the Working Position and Position. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 94
A subdirectory of Parameters/Transducer, it contains a group of parameters that allows the user to configure the type and information of the valve and actuator setup. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 95
Calibration Date: Date of the device’s last calibration. This value will change after a successful calibration. Self-calibration: A selection of auto-calibration commands, which are executed by pressing the “Execute” button. The WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 96
Travel Time OPEN: Set point for the time in seconds between the changes of the state from OPEN to CLOSED. Opening Speed Limit: Used to reduce the speed of the open valve movement. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 97
TIME_AND_DATE value must follow the same format, otherwise, the DTM will reject it. Independent to what's defined in Windows settings, the device will WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 98
Number: password in the WSN Password parameter must be correct. Revision ID: Firmware revision identification. Revision Date: Firmware revision release date. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
If the unit is %, then 100% is the maximum pressure used in the calibration. Internal Electronic board temperature in units as defined in the Temperature: INTERNAL_TEMP_UNIT parameter. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 99 of 206...
Read back by defining the value and the status. That means that the Transducer Block and the Function Block will be disconnected. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Simulation: Enable or disable the simulation. 9.5.3 Alert The Alert option under the Device\Additional Function\Diagnostics menu has device performance diagnostics and alerts. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 102
COMM_PROBLEM-check if the modem is detecting bus activity Alert Status: It will report an alert condition if it was enabled at available alerts. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 103
POSITION_HI alert: Maximum position to turn on the POSITION_HI_ALR. POSITION_LO alert: Minimum position to turn on the POSITION_LO_ALR WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Timeout: Limit time allowed to the valve complete the full stroke. Measured Break Time: The break time of the current curve. Time Interval: Time interval to complete the test. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Cause: Cause of the upper alarm. Alarm Output Value: Output value at the time of the upper alarm. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 109
Cause: Cause of the lower alarm. Alarm Output Value: Output value at the time of the lower alarm. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
FLOP and reverse acting (SIGNAL_ACTION) in POSITION_UNITS. Working Position: Position value (Hall sensor value) in engineering units defined in the POSITION_UNITS parameter. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Stable Timeout (SPSR): Maximum time allowed for the SPSR test to finish. Stable Time (SPSR): Measured time in which the valve took to reach and stabilize at the SPSR_SP during last test. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Permitted Mode: Defines the modes which are allowed in this instance of the block. Normal Mode: The mode which the block uses during normal operation conditions. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Target Mode: Sets the desired mode for the block. The input parameters of the block in conjunction with the state of the block are used to determine WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
For more information about each parameter of this directory, see the chart below: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
DTM will show is determined by the value defined in the TAB_ACTUAL_NUMBER parameter. 9.9 PA Profile 9.9.1 Physical Block 9.9.1.1 Standard Parameters WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 116
Permitted Mode: Defines the modes which are allowed in this instance of the block. Normal Mode: The mode which the block uses during normal operation conditions. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 117
Hardware Revision: Electronic board version Manufacturer: Identification of device manufacture. Westlock manufacture ID is 77. The DTM will show the text “Westlock Controls”. Device ID: Westlock device identification. The DTM will show the text “ICoT PA”. Device Serial Number: Unique serial number Diagnosis Diagnosis: Detailed status information about the field device’s...
Page 118
Local Operation: Enable or disable the local operation via keypad. IDENT_NUMBER_SELECTOR PROFIBUS Ident Number: Device Ident number in use. The hexadecimal number 0E88 is the specific identification number assigned to ICoT PA. HW_WRITE_PROTECTION HW Write Protection: This parameter shows the status of hardware write protection.
Page 119
Diagnosis Mapping Ext Diag Bit Status Mapping Ext Diag Bit 10: Diagnosis Mapping Ext Diag Bit Status Mapping Ext Diag Bit 11: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Device Revision and the Revision of the Device Description. DD Revision: Revision of the Device Description. Profile: PROFIBUS profile class. ICoT has PROFIBUS PA, WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 121
The alarm sum of the unacknowledged alarm state. Sum: Unreported Stated Alarm Sum: Unreported State Alarm Sum. Disabled State Alarm Sum: Disabled State Alarm Sum. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 122
PID setpoint. (See the Characterization Curve section to get details how to enter this table). RATED_TRAVEL Nominal Valve Stroke/Angle: Nominal stroke of the valve in units of OUT_SCALE. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 123
OPEN to CLOSED. Travel Time OPEN: Set point for the time in seconds between the changes of the state from OPEN to CLOSED. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 124
- Electro-hydraulic; - Others. Actuator Action: Fail-Safe position for power-loss of the actuator regarding the valve position. It has the following WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 125
- Fast: 80% Dynamic Speed; - Fastest: 100% Dynamic Speed; - Custom: Uses the travel rate defined in the Travel Time CLOSE filed (TRAVEL_RATE_DEC parameter). WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 126
Total Travel Deadband: In units of TRAVEL_COUNT, this parameter will setup a dead band to assume that the valve is totally open or WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 127
Timeout (FST): Time limit to wait the finish of full stroke test. Measured Break Time Measured break time of the last full stroke test. (FST): WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Block Objects: Type of related block. Parent Class: Defines the transducer block parent class. Class: Defines the transducer block class. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 129
Unacknowledged State Alarm The alarm sum of the unacknowledged alarm state. Sum: Unreported Stated Alarm Sum: Unreported State Alarm Sum. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 130
RCAS IN: Target setpoint provided by a supervisory host to the analog control or output block (RCAS mode). Status (RCAS IN): Contains the flowing states of quality: Good (Cascade), Uncertain and Bad. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 131
- Torque limit in CLOSE direction exceeded; - Actuator travel time exceeded; - Actuator moving to OPEN; - Actuator moving to CLOSE; - Update alert; WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Reserved Profile Parameter: This parameter is reserved and contains no relevant data. Block Objects: Type of related block. Parent Class: Defines the transducer block parent class. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 133
Current State Alarm Sum: The alarm sum of the current alarm state. Unacknowledged State Alarm The alarm sum of the unacknowledged alarm state. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 134
Unit (e.g. reactor, centrifuge, drier). Batch Operation: Identifies the active Control Recipe Operation. Batch Phase: Identifies the active Control Recipe Phase. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 135
It defines the associated transducer block. PV_FTIME Filter Time Const: This parameter contains the time constant for the rise time WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 136
Warning Output Value: Output value at the time of the upper warning. LO_LO_ALM Unacknowledged Alarms: Unacknowledged alarms Status: Status for the lower alarm. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 137
(see General Requirement) the user has the possibility to write the specific text in this parameter. The unit code is then equal to the ‘textual unit definition’. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
EDD, electronic device description, allow a graphic representation of the device features like, calibration, trends, basic and advance configuration, diagnostics and valve signature. The ICoT PA EDD is following the Spec IEC 61804-3 Ed2.0 2010 IEC. 10.2 Initial Setup The user needs an EDD application and a communication interface installed to be able to work with the ICoT PA EDD.
The following sub session will assume that the EDD for the ICoT PA is already open and all data was retrieve from the device 10.3 Calibration and Configuration 10.3.1 Identification Located under ICoT PA/Identification, at this option is possible to see and modify some information to describe the device.
Enable or disable the local operation via keypad. 10.3.2 Basic Setup A sub directory of ICoT PA, it has a group of initial configuration parameters. Valve Type: Type of valve movement (rotary or linear). It has the following option: - Rotary moving valve;...
Option: 10.3.4 Feedback Configuration A sub directory of ICoT PA, it has a group that displays the valve actual position and the values resulting from the user defined characterization. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
The available sources are the Working Position and Position. 10.3.5 Units A sub directory ICoT PA, it has a group to configure the engineering units used to display the readings of the device's sensors. Position Unit: Engineering unit for the position, defined in the AO.PV_SCALE parameter.
INTERNAL_TEMP_UNIT parameter. 10.3.6 Valve and Actuator Info A subdirectory of ICoT PA, it contains a group of parameters that allows the user to configure the type and information of the valve and actuator setup. Valve Manufacturer: Name of the valve manufacturer.
Page 144
Device option at menu bar and select the option calibration, Figure 10-3. Figure 10-1 Figure 10-2 Figure 10-3 WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
(in% of span) 10.3.8 Slew Rate Setup A subdirectory of ICoT PA, it contains a group of parameters that allows the user to configure the valve's open and close speeds. Min. Travel time CLOSE: Time interval from opened to closed positions registered during the last calibration.
10.3.9 Clock The clock is showed as subdirectory of ICoT PA, Figure 10-4, where is possible to check the current values, and an option in the device menu, Figure 10-5, where it is possible to write at available parameters. To allow the user to configure the time and date of the device’s RTC, goes to Device option at menu bar and select the option...
Page 147
Use this option to sync with computer time and date. This option will copy the computer current time and date to Time and Date parameter. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
10.3.10 LCD Contrast, Serial Number, Revision A subdirectory of ICoT PA, where is possible to check the values of a group of parameters to set the clock, LCD contrast, device’s serial and revision information, Figure 10-7. But to change the values, goes to device option at menu, and select the option LCD Contrast…, Figure 10-8, to have write access to those parameters, Figure...
Page 149
Number: password in the WSN Password parameter must be correct. Revision ID: Firmware revision identification. Revision Date: Firmware revision release date. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
. Clicking over it a window will be open to choose the file name and the folder where the file will be saved. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 151
12,48 It is possible to import any CSV file format by pressing the import button selecting the file to be imported. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 152
Servo PID derivative gain Integral-Action Coefficient: Servo PID integrative gain Target Mode: Target mode for the transducer block WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 152 of 206...
Page 153
Close: Close the window. 10.3.11.2 Servo PID Step response This option is available at Device/Servo PID Step Response, WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 153 of 206...
10.3.12 Characterization Curve This option is available at Device/Characterization curve. Use this feature to configure and visualize the characterization curve. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 156
- Gradient of edge too high: - Values not accepted: The written table doesn’t have all the requisites of a valid curve. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
This option at EDD allows the user to see many variables from device as a bar graph or as a trend curve. To open this windows click over the Process Variable && Trend Curves option at toolbar. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
The offset has a variation of 3.5% for each 1ºC of variation. If the unit is %, then 100% is the maximum pressure used in the calibration. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
FLOP and reverse acting (SIGNAL_ACTION) in POSITION_UNITS Feedback: The actual position of the final control element in units defined in the POSITION_UNITS parameter. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Value: Output Analog output feedback. This parameter will be use as setpoint for the transducer. Check back This parameter is not implemented. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Device Status The diagnostics/Device Status option shows general information, profile information and the diagnostics bits, diagnostics masks, feature supported and feature mask. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 163
TAG: Physical device tag. Manufacturer: Identification of device manufacture. Westlock manufacture ID is 77. The DTM will show the text “Westlock Controls”. Product designation: Westlock device identification. The DTM will show the text “ICoT PA”. Device Serial Number: Unique serial number...
PROFIBUS Ident Number: Device Ident number in use. The hexadecimal number 0E88 is the specific identification number assigned to ICoT PA. Static Revision No.: Counter used to indication of any change in a static parameter from function block Diagnosis : Detailed status information about the field device’s operating condition.
Page 166
POSITION_HI alert: Maximum position to turn on the POSITION_HI_ALR. POSITION_LO alert: Minimum position to turn on the POSITION_LO_ALR WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Save Reference Curve: This option will save the last curve as reference. The measured break time and time interval will be saved as well. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
10.6 PA Profile – Block View Here is possible to view all function block parameters. They are dividing by function block. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Actual Mode: Indicates the current mode of operation the block is able to achieve. Permitted Mode: Defines the modes which are allowed in this instance of the block. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 170
Hardware Revision: Electronic board version Manufacturer: Identification of device manufacture. Westlock manufacture ID is 77. The DTM will show the text “Westlock Controls”. Device ID: Westlock device identification. The DTM will show the text “ICoT PA”. Device Serial Number: Unique serial number Diagnosis Diagnosis: Detailed status information about the field device’s...
Page 171
Local Operation: Enable or disable the local operation via keypad. IDENT_NUMBER_SELECTOR PROFIBUS Ident Number: Device Ident number in use. The hexadecimal number 0E88 is the specific identification number assigned to ICoT PA. HW_WRITE_PROTECTION HW Write Protection: This parameter shows the status of hardware write protection.
Page 172
Diagnosis Mapping Ext Diag Bit 9: Status Mapping Ext Diag Bit Diagnosis Mapping Ext Diag Bit 10: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 172 of 206...
Block Objects: Type of related block. Parent Class: Defines the transducer block parent class. Class: Defines the transducer block class. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 174
Unacknowledged State Alarm The alarm sum of the unacknowledged alarm state. Sum: Unreported Stated Alarm Sum: Unreported State Alarm Sum. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 175
(RCAS mode). Status (RCAS IN): Contains the flowing states of quality: Good (Cascade), Uncertain and Bad. Channels WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 176
Setpoint Deviation: Difference between Setpoint and Readback in % travel span (span between OPEN and CLOSED position). Check Back WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 177
OUT_SCALE Upper Value: Upper value (Output Signal Range): Upper range value of the process variable (100%) in engineering units. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Block Modes Target Mode: Sets the desired mode for the block. The input parameters of the block in conjunction with the state WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 179
DEVICE_CALIB_DATE Calibration Date: Date of the device’s last calibration. This value will change after a successful calibration. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 180
Total Valve Travel Accumulated valve travel in nominal duty cycles. Limit Total Valve Travel Limit for the “Total Valve Travel” in duty cycles. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
Page 181
Feedback: The actual position of the final control element in units defined in the POSITION_UNITS parameter. Status (Feedback Value): The status of actual position. Contains the following WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 182
The options available are: - Increase to Open - Increase to Close WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 183
INTERNAL_TEMP_UNIT parameter. Transducer Command: A selection of calibration procedures, which are executed by pressing the “Execute” button. The procedures are: WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 184
Fault State Value: If the POSITIONING_VALUE status is bad and the FAULT_STATE_OPTION is set to FAULT_STATE_VALVE then parameter TRD_SP will be set to this value. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 185
WSN Serial Number: Show the current serial number. To write a new value, the password in the WSN Password parameter must be correct. Revision ID: Firmware revision identification. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Block Modes Target Mode: Sets the desired mode for the block. The input parameters of the block in conjunction with the state WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 187
Upper Value: Upper value (Output Signal Range): Upper range value of the process variable (100%) in engineering units. Lower Value: Lower Value (Output Signal Range): Lower range WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 188
An alarm occurs when a value exceeds an upper limit. The alarm’s status remains true until the value drops below the limit minus the WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 189
Transducer Block and the Function Block will be disconnected. Status (Simulation Value): Status for the simulate value. Simulation: Enable or disable the simulation. OUT_UNIT_TEST WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424...
Page 190
(see General Requirement) the user has the possibility to write the specific text in this parameter. The unit code is then equal to the ‘textual unit definition’. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
ISA dS50.02, Part 2 Amendment; Fieldbus Standard for Use in Industrial Control Systems - Part 2: Physical Layer Specification and Service Definition, Amendment to Clause 22 (Formerly Clause 11 and 24). WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
7. Vary air pressure around low pressure setting and observe LCD to test if setting is correct. 8. Re-regulate the supply air to the normal operating pressure. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com...
A filter/regulator with a 5 micron or better element, just prior to the positioner, is therefore recommended. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 196
Do not cock the spool. Make sure the spool spins and moves freely. After the spool valve is cleaned and reassembled the positioner should recalibrated using the auto CAL function. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
10 CM 50CM Any cable subject to 50 CM 50 CM 50 CM ray exposure WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O. 21424 Page 198 of 206...
Page 201
17 Appendix G – Procedure to Reset the Non-Volatile Memory to Factory Settings The ICoT PA positioner is a microprocessor controlled digital device. Its operation relies on data that is stored in the positioner’s non-volatile memory. Calibration and configuration data that has been established during the positioner’s setup and calibration is stored in this memory.
Page 202
18 Appendix H - Controlling the ICoT PA Position using the Proficore Ultra Interface, ProfiCaptain software First we need to add the GSD file. If the GSD file was added before skip to step 6. From the ProfiTrace main dialog, press the Now if you check the GSD catalog in the tab ProfiCaptain.
Page 203
13. Set the Active. 10. Go to ProfiCaptain tab and select "New Project" in the File menu option. 11. At GSD catalog drag and drop the ICoT PA near of the ProfiCore icon at Network Sheet. 14. On the Slave Setup Dialog, click over "Setup Modules &...
Page 204
24. Using the keypad menu change the address to match the address used in the project or change the address set in the project. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 205
30. To change the AO.SP.status via I/O set Memory Address as 4, Memory Type as Output, Data Type as Unsigned8 (byte) and click on "Add Watch". WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.
Page 206
LCD. status was sent to device). The device will show PA-CTR indicating the setpoint is been update through AO channel. WESTLOCK CONTROLS CORPORATION 280 N. MIDLAND AVE., STE. 258, SADDLE BROOK, NJ 07663 TEL: 201-794-7650 FAX: 201-794-0913 www.westlockcontrols.com 10/5/2013 TECH-477/D.W.O.