Grafik Eye GRX-WCI Installation Instructions Manual

Grafik Eye GRX-WCI Installation Instructions Manual

Wallbox input closure interface

Advertisement

Installation Instructions
Please Read before Installing
Overview
The GRX-WCI is for use
with GRAFIK Eye 3000
and 4000 series systems.
The GRX-WCI mounts
behind the user-supplied
switch to select or adjust
scenes in up to eight
control units. The
interface provides from
two to seven contact
closure inputs.
Specifications
• Operating voltage: PELV (Class 2: USA) low-voltage
type inputs, 12 V
when used on a GRX-3000 system
and 24 V
when used on a GRX-4000 system.
• If input switch is solid state, it must have an output with
an on-state saturation voltage less than 1 V
and an off-state leakage current of less than 1 mA.
Outputs must be capable of switching operating
voltage for desired life of system.
• The recommended wallbox depth is 61 mm. The
wallbox depth requirements vary with the depth of the
switch being used.
• The GRX-WCI uses one address on the communication
link.
• If there is any question as to whether a switch is
compatible with these specifications, contact the
manufacturer of the switch.
• Environment: Ambient operating temperature 0-40 °C
(32-104 °F), 0-90% humidity, non-condensing. Indoor
use only.
Caution: The GRX-WCI is not designed to work
with the line/mains voltage switches. Use with
line/mains voltage switches could result in
premature failure of the switch being used.
Caution: Install in accordance with all local and
national electric codes.
Input wiring
harness
Program
button
Power
Addressing
LED
and function
switches
at 1 mA
R
Wallbox Input Closure Interface
GRX-WCI
PELV (Class 2: USA) Devices
GRAFIK Eye 3000 12 V
GRAFIK Eye 4000 24 V
Low-Voltage PELV (Class 2: USA) Wiring
• Use low-voltage PELV (Class 2: USA) wiring to daisy-
chain the GRX-WCI to GRX-3000/4000 control units
and other components.
• Make connections inside the wallbox, switchbox, or
junction box with a maximum wire length of 2.5 m
from the link to the GRX-WCI.
When used with GRX-3000 control units:
• Use two 1.0 mm
(#18 AWG) conductors for common
2
(terminal 1) and 12 V
terminal 2 connection correctly; refer to the GRX-3000
Installation Guide.
• Use one shielded, twisted pair 1.0 mm
wires for data link (terminals 3 and 4).
When used with GRX-4000 control units:
• Use two 2.5 mm
(#12 AWG) conductors for common
2
(terminal 1) and 24 V
into terminals; see next page for connection details.
• Use one shielded, twisted pair 1.0 mm
wires for data link (terminals 3 and 4).
• Connect drain/shield as shown on next page.
-Do not connect ground/earth to GRX-WCI.
-Connect the bare drain wires and cut off the outside
shield.
200 mA
100 mA
(terminal 2). Be sure to wire the
(#18 AWG)
2
(terminal 2). These will not fit
(#18 AWG)
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GRX-WCI and is the answer not in the manual?

Questions and answers

Summary of Contents for Grafik Eye GRX-WCI

  • Page 1 -Connect the bare drain wires and cut off the outside switch being used. shield. • The GRX-WCI uses one address on the communication link. • If there is any question as to whether a switch is compatible with these specifications, contact the manufacturer of the switch.
  • Page 2: Installation

    GRX-WCI purposes. 4.Select Function. Set function switches 5 through 10 on the GRX-WCI to select its function. See the chart on the next page for switches and their functions. 5.Connect the GRX-WCI to the communication link. Strip insulation from the wires so that 10 mm (3/8 in.) of bare wire is exposed for 1.0 mm...
  • Page 3 GRX-WCI Function Switches FUNCTIONS Function Switch Settings 5 6 7 8 9 10 Inputs 1-4 Input 5 Input 6 Input 7 Scenes 1 to 4 Raise Lower 4-scene with Scenes 5 to 8 Raise Lower master raise/lower Scenes 9 to 12...
  • Page 4: Communication Link Wiring

    GRX-WCIs, wallstations, and/or control interfaces, for a follow the steps below. total of 24 control points. 1.Enter program mode (only one GRX-WCI can be in program mode at a time). Press and hold the program button for about 3 seconds, until the LED starts flashing.
  • Page 5: Troubleshooting

    Power is not present at WCI; make sure the lighting system is powered up and check for miswires Power LED flashes WCI is in program mode Power LED is on, but the system response WCI is improperly programmed. isn’t correct Verify correct function switch settings and check system programming GRX-WCI Installation Instructions...