R3G560-AH02-03
Line voltage faulty
Faulty connection
Broken motor winding Replace device
Deficient cooling
Ambient temperature
too high
Impermissible point of
operation (e.g. back
pressure too high)
In the event of further malfunctions, contact ebm-papst.
Item no. 50154-5-9970 · ENU · Change 89187 · Approved 2016-04-15 · Page 12 / 13
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Check line voltage,

6.1 Cleaning

restore power supply.
Attention! The error
message resets
automatically.
Device restarts
automatically without
warning.
Isolate from supply,
correct connection;

6.2 Safety inspection

see connection
diagram.
Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the line voltage for at
least 25 s and then
switch it on again.
What to check
Alternatively, reset
Contact
the error message by
protection
applying a control
cover for
signal of < 0.5 V to
intactness or
Din1 or by shorting
damage
Din1 to GND.
Device for
Reduce the ambient
damage to
temperature. Let the
blades and
device cool down.
housing
To reset the error
Fastening the
message, switch off
cables
the line voltage for at
Insulation of
least 25 s and then
cables for
switch it on again.
damage
Alternatively, reset
Impeller for
the error message by
wear/deposits/
applying a control
corrosion and
signal of < 0.5 V to
damage
Din1 or by shorting
Tightness of
Din1 to GND.
cable gland
Correct the operating
point. Let the device
Condensation
cool down.
drainage holes
To reset the error
for clogging,
message, switch off
where necessary
the line voltage for at
least 25 s and then

6.3 Disposal

switch it on again.
Alternatively, reset
For ebm-papst, environmental protection and resource preservation are
the error message by
top priority corporate goals.
applying a control
ebm-papst operates an environmental management system which is
signal of < 0.5 V to
certified in accordance with ISO 14001 and rigorously implemented
Din1 or by shorting
around the world on the basis of German standards.
Din1 to GND.
Right from the development stage, ecological design, technical safety
and health protection are fixed criteria.
The following section contains recommendations for ecological disposal
of the product and its components.
NOTE
Damage to the device during cleaning
Malfunction possible
→ Do not clean the device using a high-pressure cleaner.# Do
not use acid, alkali or solvent-based cleaning agents.
→ Do not use any pointed or sharp-edged objects for cleaning
NOTE
High-voltage test
The integrated EMC filter has Y capacitors. The tripping current
is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you perform the
legally required high-voltage test. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
How to check
How often
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
What action?
Repair or
replacement of
device
Replacement of
device
Fasten
Replace cables
Clean or
replace impeller
Retighten,
replace if
damaged