Caution: NIN and NLINE are internally connected.
Input can be used as pulse counters (see settings chapter).

3.2 Output

Contact mode
Max. power commutable
Maximum switching voltage 250Vac~
Max. current
The output has pulse capability (minimum pulse duration is 100ms, maximum around 100 minutes),
so, instead to send two different commands (one to turn on and one to turn off the ouput), is possible
to send a duration command.
As application example, to safely turn on an output, send a ON-pulse command for a defined time (for
example, for the maximum allowed interval), and before the expiring time, another ON-pulse
command (making a kind of watchdog) if the output still needs to be ON, or a simply OFF command if
you want to turn it off.

3.3 Wiring examples

Load connected to the same supply of the sensor, connected to the relay output (normally open
contact):