Overview
The Miniature Adjustable Current switches are designed for use in any AC current
monitoring application in which you are looking for an adjustable current switch to
monitor normal operating conditions, equipment failure or preventative
maintenance scheduling for a particular piece of equipment. The adjustable current
switches should be installed on the line side of the power to the motor, pump,
compressor or other equipment. The miniature adjustable current switches are
available in both solid and split-core versions in a smaller enclosure style than that
of the NSA-A/ACS2 and NSA-A/ASCS2 Series adjustable current switches. The
solid-core versions are a great choice for new installations or OEM applications in
which cost sensitivity, lower trip points and environmental issues may be of
concern. The split-core version of the current switches work great in retrofit
applications and for use in service vehicles since one part will work in most applications and can be installed without
disconnecting any wires. The adjustable current status switches can also be used to determine the run time of your
equipment where you want to know when your piece of equipment runs and for how long it runs when logging the contact
closures on your building management system or PLC.
Applications: Overload Conditions, Under Load Conditions, Normal Load Conditions, Broken Belts, Belt Slippage, Locked
Rotors, Electrical Failure, Load Status, Local Alarms such as Strobes/Audible Alarms, Pumps, Fans, Compressors,
Lighting Status and Usage Information, Ovens, Process Control, Industrial Equipment, Equipment Maintenance, OEM
Part Numbers
NSA-A/MCS-A
Specifications
Monitored Current Type:
Maximum AC Voltage:
Operating Frequency Range:
Core Style:
Sensor Power:
Amperage Range:
Isolation Voltage:
Output Switch Rating
Trip Point Style | Adjustable Trip Point Range:
Hysteresis:
Contact Type:
Contact Rating:
Contact "On" Resistance | "Off" Resistance:
Response Time:
Status LED Indication
Aperture Size (Diameter):
Operating Temperature Range:
Operating Humidity Range:
Recommended Storage Temperature | RH Range:
Enclosure Material | Flammability Rating:
Wiring Connections:
Wire Size:
Terminal Block Torque Rating:
Catalog No. 11-808-762-01
NSA-A/MSCS-A
1
:
Specifications subject to change without notice.
Miniature Adjustable Current Switches
AC Current
600 VAC
50/60 Hz
NSA-A/MCS-A: Solid | NSA-A/MSCS-A: Split
Induced from the Monitored Conductor (Insulated Conductors only)
Max Sensing Current Voltage: 600 VAC | Max Continuous Current: 158 A
Max Current for 6 Seconds: 204 A | Max Current for 1 Second: 600 A
2200 VAC
1.00 Amp @ 36 VAC/VDC
Adjustable Trip Point | NSA-A/MCS-A: 0.32 – 150 A
NSA-A/MSCS-A: 0.70 - 150 A
10% Trip Point, typical
Normally-Open "N/O"
1A Continuous @ 36 VAC/VDC
< 0.5 Ohms (tripped) | > 1 Meg Ohms (Open)
NSA-A/MCS-A: < 90 mS, typical | NSA-A/MSCS-A: < 45 mS typical
Red LED (Current above trip point) | Blue LED (Current below trip point)
0.53" (13.46 mm)
-22 to 140ºF (-30 to 60ºC)
0 to 95%, non-condensing
41 to 95°F (5 to 35°C) | 40% to 85% RH, non-condensing
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
2 Position Screw Terminal Block (Not Polarity Sensitive)
2
16 to 22 AWG (1.31 mm
to 0.33 mm
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Installation and Operation
2
) Copper Wires only
Page 1 of 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NSA-A/MCS-A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier NSA-A/MCS-A

  • Page 1 Contact “On” Resistance | “Off” Resistance: < 0.5 Ohms (tripped) | > 1 Meg Ohms (Open) Response Time: NSA-A/MCS-A: < 90 mS, typical | NSA-A/MSCS-A: < 45 mS typical Status LED Indication Red LED (Current above trip point) | Blue LED (Current below trip point) 0.53”...
  • Page 2: Dimensional Drawing

    UL/CUL US Listed (UL 916) Energy Management Equipment (File # E334792), CE, RoHS2, WEEE Product Weight: NSA-A/MCS-A: 0.15 lbs. (0.068 kg) | NSA-A/MSCS-A: 0.20 lbs. (0.091 kg) NSA-A/MCS-A (Solid-Core): 2.510” (63.82 mm) x 0.940” (23.94 mm) x Product Dimensions (L x W x H): 2.000”...
  • Page 3: Installation

    6X the original current. Example: A small fan operating at 0.2A should be wrapped through the sensor 7 times to give you a total operating current of 1.4Amps flowing through the NSA-A/MCS-A or NSA- A/MSCS-A.
  • Page 4: Wiring Instructions

    Miniature Adjustable Current Switches Installation and Operation #NSA-A/MCS-A, NSA-A/MSCS-A – 11/14/2019 For applications in which the normal operating current is greater than 150 Amps or for conductor diameters larger than 0.530” (1.35 cm) in diameter, an external 5 Amp Current Transformer must be used as shown in Figure 4 below.
  • Page 5: Calibration Of Adjustable Trip Point

    Normal Loads With current flowing through the aperture of the NSA-A/MCS-A and NSA-A/MSCS-A current switches, first verify that the Blue LED is on. If the Blue LED is on, now slowly adjust the potentiometer clockwise until the Red LED just turns on and stop immediately.

This manual is also suitable for: