Carrier NSA-A/CS2 Installation Instructions Manual

Carrier NSA-A/CS2 Installation Instructions Manual

Advertisement

#NSA-A/CS2, NSA-A/SCS2, NSA-A/SCS2-L – 11/14/2019
Overview
The Carrier Fixed "Status" Current switches are designed for use in any AC current
monitoring application in which you are looking for a "Go/No Go" or On/Off status for a
particular piece of equipment. The current switches should be installed on the line side
of the power to the motor, pump, compressor or other equipment. The current switches
are available in both solid and split-core versions which also includes a Patented 35 mm
Din Rail mounting foot for easy installation in panel mount applications. The solid-core
versions are a great choice for new installations or OEM applications in which cost
sensitivity, lower trip points and environmental issues may be of concern. The split-core
version of the current switches work great in retrofit applications and for use in service
vehicles since one part will work in most applications and can be installed without
disconnecting any wires. The fixed current status switches can also be used to
determine the run time of your equipment and basic load trending applications where you want to know when your piece of
equipment runs and for how long it runs for when logging the contact closures on your building management system or
PLC.
Applications: Pump Status, Fan Status, Compressors, Motor Status, Ovens, Industrial Equipment, Lighting Status and
Usage, Electrical Load Status, Local Alarms (Strobes and Audible Alarms)
NOTE The Fixed Current Switches are not intended to be used in Life / Safety applications or in Hazardous / Classified
locations.
Part Numbers
NSA-A/CS2
Specifications
Monitored Current Type:
Maximum AC Voltage:
Operating Frequency Range:
Core Style:
Sensor Power:
Amperage Range:
Isolation Voltage:
Trip Point Style:
Trip Point:
Contact Type:
"Status" Contact Rating:
"Status" Contact "On" Resistance
"Off" Resistance:
Response Time:
Status LED Indication
Aperture Size:
Din Rail Size:
Operating Temperature Range:
Operating Humidity Range:
Recommended Storage Temp | RH Range:
Enclosure Material | Flammability Rating:
Wiring Connections:
Wire Size:
Terminal Block Torque Rating:
Catalog No. 11-808-756-01
NSA-A/SCS2
1
:
Specifications subject to change without notice.
NSA-A/SCS2-L
AC Current
600 VAC
40 to 1 kHz
NSA-A/CS2: Solid | NSA-A/SCS2: Solid | NSA-A/SCS2-L: Split
Induced from the Monitored Conductor
NSA-A/CS2: 0-250A | NSA-A/SCS2: 0-200A | NSA-A/SCS2-L: 0-200A
2200 VAC
Fixed
NSA-A/CS2: 0.25A or less | NSA-A/SCS2: 1.5A or less
NSA-A/SCS2-L: 1.5A or less
Normally open (N/O)
0.2A @ 200 VAC/VDC
< 10 Ohms (tripped)
> 1 Meg Ohms (Open)
See Response Time table below
Red LED (Monitored current is above Trip Point)
0.75" (19.05 mm)
35 mm | (U.S. Patent No. 7,416,421)
5 to 104ºF (-15 to 40ºC)
0 to 95%, non-condensing
41 to 95°F (5 to 35°C) | 40% to 85% RH, non-condensing
PC/ABS (Polycarbonate/ABS Blend) | UL94-V0
2 Position Screw Terminal Block (Not Polarity Sensitive)
2
16 to 22 AWG (1.31 mm
to 0.33 mm
4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm)
Fixed Status Current Switches
Installation and Operation
2
) Copper Wires only
Page 1 of 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NSA-A/CS2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier NSA-A/CS2

  • Page 1 #NSA-A/CS2, NSA-A/SCS2, NSA-A/SCS2-L – 11/14/2019 Overview The Carrier Fixed “Status” Current switches are designed for use in any AC current monitoring application in which you are looking for a “Go/No Go” or On/Off status for a particular piece of equipment. The current switches should be installed on the line side of the power to the motor, pump, compressor or other equipment.
  • Page 2: Response Time

    UL/CUL US Listed (UL 508) Ind. Control Equipment (File # E309723), CE, RoHS2, WEEE Product Weight: NSA-A/CS2: 0.216 lbs (0.099kg) | NSA-A/SCS2: 0.270 lbs (0.123 kg) NSA-A/SCS2-L: 0.280 lbs. (0.127 kg) Solid Core: 2.760” (70.11mm) x 3.343” (84.92mm) x 1.050” (26.67mm) Product Dimensions (L x W x H): Split Core: 2.780”...
  • Page 3: Installation

    This product is not intended to be used for Life or Safety applications.  This product is not intended for use in any hazardous or classified locations.  The NSA-A/CS2 and NSA-A/SCS2 Series Current Switches must be used on Insulated Conductors Only.  High Voltage ...
  • Page 4 Fixed Status Current Switches Installation and Operation #NSA-A/CS2, NSA-A/SCS2, NSA-A/SCS2-L – 11/14/2019 Latch Operation Press down on the side tab and swing the top of the unit up to open the split core current switch as shown in Figure 2.
  • Page 5: Application Notes

    Example: When using the NSA-A/CS2, a small fan operating at 0.1A should be wrapped through the sensor four times to give you a total operating current of 0.4 Amps flowing through the NSA-A/CS2. Formula Example: (0.25A/0.1A) = 2.5 + 1 = 3.5, which rounded up equals 4 loops.
  • Page 6 Fixed Status Current Switches Installation and Operation #NSA-A/CS2, NSA-A/SCS2, NSA-A/SCS2-L – 11/14/2019 Digital Circuit Figure 5 Motor/Fan Control Figure 6 Specifications subject to change without notice. Catalog No. 11-808-756-01 Page 6 of 7...
  • Page 7: Troubleshooting

    Fixed Status Current Switches Installation and Operation #NSA-A/CS2, NSA-A/SCS2, NSA-A/SCS2-L – 11/14/2019 Application Examples See Figure 5 and Figure 6 for two different current switch applications. Figure 5 shows the use of the Go/No Go Current Switch as a Digital Input to your BAS/PLC Controller. Figure 6 shows a Go/No/Go Current Switch in conjunction with a Contactor to control an exhaust fan.