Global Fire Equipment GFE-CS Installation Wiring Diagram

Photoelectric smoke detector

Advertisement

Quick Links

TYPICAL WIRING DIAGRAM
Figure 1(a) shows the typical wiring diagram of the
2-wire multiple-station smoke detector system.
FIRST DETECTOR BASE
+
INITIATING
LOOP
-
-
+
5
2
EN54 LISTED
COMPATIBLE
CONTROL
6
1
3 4
PANEL
REMOTE
INDICATOR
CLASS A OPTIONAL WIRING
NOTE: IF REMOTE INDICATOR IS NOT USED. POLARITY TO DETECTOR MAY BE REVERSED.
Figure 1(b) shows the typical wiring diagram of the
4-wire multiple-station smoke detector system.
WARNING
TO
PREVENT
DETECTOR
SUBSEQUENT
WARRANTY
SMOKE DETECTOR MUST REMAIN COVERED UNTIL
THE AREA IS CLEAN AND DUST FREE.
INSTALLING THE BASE
1. To insure proper installation of the detector head to the
base, all the wires should be properly addressed at
installation:
(A) Position all the wires flat against terminals.
(B) Fasten the wires away from connector terminals.
2. If you use a jumper wire to connect the poles of
terminal 2 and 5 when testing the detector loop
continuity, be sure to remove the jumper wire prior to
the installation of the detector head.
3. The end-of-line device shown in fig. 1(a) and 1(b)
should be compatible with the control unit. The
end-of-line supervisory relay used should be rated for
the DC power voltage used.
4. Open area smoke detectors are intended for mounting
on a ceiling or a wall in accordance with the fire
standard in your country.
5. The base of the smoke detector can be mounted
directly onto an electrical junction box such as an
octagonal (75mm, 90mm or 100mm), a round (75mm),
or a square (100mm) box without using any type of
mechanical adapter.
INSTALLING THE HEAD
1. Align the components as shown in Figure 2.
2. Mate the detector head onto the base and twist
clockwise to secure it.
3.
Do not install the detector head until the area is
EOL
LAST DETECTOR BASE
RESISTOR
-
+
5
2
6
1
3
4
CONTAMINATION
AND
CANCELLATION,
THE
Photoelectric Smoke Detector
GFE-CS
Installation Wiring Diagram
thoroughly cleaned of construction debris, dusts, etc.
The maximum number of smoke detector installed in
the same zone is 30 units, see control panel manual
for details.
Fig. 2 Mating detector head onto base
ADJUSTING THE RELAY FOR NO/NC
The normal condition for the relay is "normally open"
(NO).
1. To adjust the normal condition of the relay to
"normally closed" (NC), insert a screwdriver into the
rectangular hole located on the side between the front
cover and base and rotate to remove the front cover.
2. Refer to figure 3. There is a jumper head next to the
relay on the PCB. Remove the jumper head and reinsert
it in the NC position.
3. Carefully replace the front cover.
Relay contact rating:
1A@30VDC,
.
0.5A@125VAC
Fig. 3 Schematic of detector structure
TESTING
1.
All the alarm signal services, releasing device and
extinguisher system should be disengaged during the
test period and must be re-engaged immediately at the
conclusion of testing.
2. After energizing the detector head for approximately
one minute, check to see the indicator green LED
flashing once every 3~5 seconds. If green LED fails to
flash, it indicates the non-functioning of the detector or
faulty wiring. Re-check the wiring or replace the
detector if necessary.
3. Allow smoke from a cotton wick or a test smoke
aerosol to enter the detector-sensing chamber for at
least 10 seconds. When sufficient smoke has entered
the chamber, the detector will signal an alarm, this
being visible by a continuous illumination of the LED.
Reset each detector and/or control unit before
attempting to test any additional detectors in the same
zone.
If a detector fails to activate within 60 seconds,
confirm connections and programming. If necessary
replace and return to distributor for recalibration.
When front cover is open.

Advertisement

loading
Need help?

Need help?

Do you have a question about the GFE-CS and is the answer not in the manual?

Questions and answers

Summary of Contents for Global Fire Equipment GFE-CS

  • Page 1 Photoelectric Smoke Detector GFE-CS Installation Wiring Diagram thoroughly cleaned of construction debris, dusts, etc. TYPICAL WIRING DIAGRAM The maximum number of smoke detector installed in Figure 1(a) shows the typical wiring diagram of the the same zone is 30 units, see control panel manual 2-wire multiple-station smoke detector system.
  • Page 2 LIMITED WARRANTY STATEMENT Global Fire Equipment Ltd. declares that this product is free from defects in material and workmanship. And it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of 24 months from the date of purchase. Please visit the Global Fire Website for a full description of Global Fire Equipment’s LIMITED WARRANTY, which, among other things, limits the duration of warranties...

This manual is also suitable for:

Gfe-cs-2Gfe-cs-2lGfe-cs-4-12Gfe-cs-4-24Gfe-cs-2hGfe-cs-2hl ... Show all